Model: HEX701CS - PAGE 1

18/01/2016 - Dorin Software v. 15.07


All data subject to change

Calculation - HEX

Input
Model HEX701CS
Refrigerant R404A
Evaporating temperature -10.0 C
Condensing temperature 45.0 C
Reference temperature Dew temperature
Suction temperature 20.0 C
Evaporator outlet temperature 20.0 C
Liquid subcooling 0.0 K
Voltage / phases / frequency 380-420 V / 3 / 50 Hz

B = Standard application
C = Max superheat 20K
= Dew temperature

Performance calculation
Standard conditions At evaporator At compressor
Cooling capacity 15110 W 15110 W 15110 W
Absorbed power 6.86 kW 6.86 kW 6.86 kW
Condenser capacity 21.96 kW 21.96 kW 21.96 kW
COP 2.20 2.20 2.20
Mass flow 453.4 kg/h 453.4 kg/h 453.4 kg/h
Absorbed current 11.5 A 11.5 A 11.5 A
Discharge
88.6 C 88.6 C 88.6 C
temperature
Max operating current 14.5 A 14.5 A 14.5 A
Locked rotor current 63.1 A 63.1 A 63.1 A
Model: HEX701CS - PAGE 2
18/01/2016 - Dorin Software v. 15.07
All data subject to change

Technical data
No. cylinders 4
Bore 54 [mm]
Stroke 40 [mm]
Displacement @ 50 Hz 31,88 [m/h]
Displacement @ 60 Hz 38,26 [m/h]
Suction valve 28 s. [mm]
Discharge valve 22 s. [mm]
Oil charge 2,0 [kg]
Net weight 91 [kg]

Overall dimensions

A - Oil sight glass F - Crankcase heater


B - Oil charge plug G - Oil return plug
C - Low pressure connection M - Max. discharge temperature sensor
D - High pressure connection DL - Discharge service valve
E - Oil drain plug SL - Suction service valve
Model: HEX701CS - PAGE 3
18/01/2016 - Dorin Software v. 15.07
All data subject to change

Accessories
TE=Thermistor protection Standard
REL=Motor protection electronic module Standard
CH=Crankcase heater Standard
WH=Water cooled head Optional
US=Unloaded start by-pass Optional
IP65=Electrical box IP65 Standard
CR1=Capacity control 50-100% Optional
TMAX=Max discharge temperature sensor Standard
For operation with HFC refrigerants the compressor must be ordered with
POE OIL. For operation with HCFC refrigerant the compressor shall be
ordered with mineral oil. For operation with HC, please contact our technical
department.
For low temperature application external cooling must be provided.
Motors suitable for operation at different voltage from those listed above
may be supplied on request.
ATEX=ATEX version
220-240/3/50 () 380-420/3/50 (Y) Optional
265-290/3/60 () 440-480/3/60 (Y) Optional
475-525/3/50 570-630/3/60 Optional
200/3/50-60 () Optional
380-420/3/50 (PWS) 440-480/3/60 (PWS) Standard
208-230/3/60 () 360-400/3/60 (Y) Optional