You are on page 1of 4

Model: AU-H300CC - PAGE 1

13/05/2022 - Dorin Software v. 21.10


All data subject to change

Calculation - AU

Input
Model AU-H300CC
Refrigerant R404A
Evaporating temperature 5.0 °C
Ambient temperature 32.0 °C
Reference temperature Dew temperature
Suction temperature 20.0 °C
Evaporator outlet temperature 20.0 °C
Voltage / phases / frequency 380-420 V / 3 / 50 Hz

A = "CC" models only


B = Standard application
C = Head cooling fan or max superheating
20K
• = Dew temperature

Performance calculation
Standard conditions At evaporator At compressor
Cooling capacity 13160 W 13760 W 13760 W
Absorbed power
4.46 kW 4.46 kW 4.46 kW
including fans
Condenser capacity 17.62 kW 17.97 kW 18.22 kW
COP 2.95 3.08 3.08
Mass flow 407.4 kg/h 407.4 kg/h 407.4 kg/h
Condensing
44.0 °C 44.0 °C 44.0 °C
temperature
Liquid subcooling 0.0 K 3.0 K 3.0 K
Absorbed current 7.7 A 7.7 A 7.7 A
Max operating
9.4 A 9.4 A 9.4 A
current
Locked rotor current 43.5 A 43.5 A 43.5 A
Model: AU-H300CC - PAGE 2
13/05/2022 - Dorin Software v. 21.10
All data subject to change

Technical data
Compressor model H300CC
Displacement @ 50 Hz 14.74 [m³/h]
Displacement @ 60 Hz 17.69 [m³/h]
Motorfans: Air Flow (tot.) @50Hz 5700.0 [m³/h]
Motorfans: Air Flow (tot.) @60Hz 6420.0 [m³/h]
Motorfans: Power @50Hz 1×245 n° × [W]
Motorfans: Power @60Hz 1×355 n° × [W]
Motorfans: Current consumption (tot.) @50Hz 1.1 [A]
Motorfans: Current consumption (tot.) @60Hz 1.55 [A]
Motorfans: Condenser capacity @50Hz 1×8 n° × µF
Motorfans: Condenser capacity @60Hz 1×8 n° × µF
Motorfans 1×450 n° × Ø
Receiver volume 5.7 [L]
Connections: Suction 22 s. [mm]
Connections: Liquid 5/8"
Net weight 110.0 [kg]
Sound pressure (free field) 1,8 m @50Hz 61.4 [dBA]
Sound pressure (free field) 1,8 m @60Hz 62.6 [dBA]
Sound pressure (free field) 5 m @50Hz 52.5 [dBA]
Sound pressure (free field) 5 m @60Hz 53.7 [dBA]
Sound power @50Hz 77.5 [dBA]
Sound power @60Hz 78.7 [dBA]
Model: AU-H300CC - PAGE 3
13/05/2022 - Dorin Software v. 21.10
All data subject to change

Overall dimensions [mm]

FL - Refrigerant outlet SV - Safety valve


SL - Suction service valve

Configuration: Standard \ Optional (Air-cooled condensing units)


L.P. and H.P. dual pressure switch Optional
High pressure switch Optional
Filter driers Optional
Moisture-liquid indicator Optional
Solenoid valve Optional
Suction flexible hose Optional
Oil separator Optional
Fan speed regulator Optional
Weather protection housing Optional
Model: AU-H300CC - PAGE 4
13/05/2022 - Dorin Software v. 21.10
All data subject to change

Configuration: Standard \ Optional (Semi-hermetic compressors)


TK=Thermik protection Standard
REL=Motor protection electronic module Optional
CH=Crankcase heater Optional
DTC=Liquid injection Optional
IP65=Electrical box IP65 Standard
CB=CB approved compressor Optional
For operation with HFC refrigerants the compressor must be ordered with
POE OIL. For operation with HCFC refrigerant the compressor shall be
ordered with mineral oil.
The DTC can decrease the duty by up to 10% depending upon pressure ratio,
suction temperature and ambient temperature. Please contact our
Technical Department for more informations.
Motors suitable for operation at different voltage from those listed above
may be supplied on request.
220-240/3/50 (Δ) 380-420/3/50 (Y) Standard
265-290/3/60 (Δ) 440-480/3/60 (Y) Optional
475-525/3/50 570-630/3/60 Optional
200/3/50-60 (Δ) Optional
208-230/3/60 (Δ) 360-400/3/60 (Y) Optional

You might also like