You are on page 1of 2

Specification for Hydrogen Gas detector

Description Hydrogen detector (PPM)


Range 0 to 100% LEL)
Alarm Audible (75 dB) and visual (red LED)
Power supply 24VDC, 16-28VDC
Display Digital OLED/LCD in terms of % of LEL
Accuracy 3%FS
Operating Temperature -20C to 50C`
Operating Humidity 095%RH
Analog Output 420mA
Response Time(T90) <30 sec
Sampling Method Diffusion
Alarm Function Two level alarm and the alarm value is adjustable
Protecting Class IP66
Property
Gas Detected H2/Hydrogen
Working Principle Electrochemistry
Display OLED
Sampling Method Diffusion
Accuracy 3%FS
Repetitiveness 2%FS
Response Time(T90) <30 sec
Alarm Function Two level alarm and the alarm value is adjustable
Service Conditions
Protecting Class IP66
Ambient Temperature -40+70
Ambient Humidity 095%RH
Certification
Explosive-proof Class Exd IIC T6
CMC Certificate CMC Code No.: 01080303 No.1
Fire Protection Certificate CCCF, Code No.: 073104852119R0S
Electric Features
Analog Output 420mA current output, max. load 500
Cable Type 3-core shielded cable
Max. Transmission Distance 1,500m
Digital Communication MODBUS RTU Protocol RS-485/HART Protocol
Alarm Relay Dry contact output.
Contact capacity: 30VDC 1A
Power Consumption 3W
Working Current 60mA (80mA) (non-alarm state)
120mA (150mA) (alarm state)
Working Voltage 24VDC, 16-28VDC
Structural Features
Electric Interface 3/4"NPT
Housing Material Aluminum alloy/stainless steel (alternative)
Dimension 200mm(H) x 130mm(W) x 120mm(D)
Weight 2.5kg
Installation Mode 2" Post-mounted/wall-mounted