Air-cooled heat exchangers are classified as forced draft when the tube section is located
on the discharge side of the fan, or induced draft when the tube section is located on the
suction side of the fan. Forced draft units are more common.
Typically, 25.4 mm (1 in) OD carbon steel tubes are fitted with aluminum fins, 12.7 to
15.9 mm high ( to 5/8 inch), providing outside surface area about 14 to 21 times greater
than the area of the bare tubes. The process stream, flowing inside the tubes, can be
cooled to about 10C to 15C (20F to 30F) above the dry-bulb temperature of the air.
Air flows at a velocity of 3 to 6 m/s (10 to 20 ft/s)/
Table 2-10: Comparison of forced draft and induced draft air-cooled heat exchangers (Ref 8)
Table 2-12: Variables that must be optimized for air-cooled heat exchanger design (Ref 18)
Variable Considerations
Air flow rate Rule of thumb for face velocity approaching the tube bundle (total flow divided by
total area of bundle):
- 3 row coil: 240 to 275 m/min (800 to 900 ft/min)
- 4 row coil: 150 to 210 m/min (500 to 700 ft/min)
- 5 row coil: 140 to 180 m/min (450 to 600 ft/min)
- 6 row coil: 100 to 150 m/min (350 to 500 ft/min)
Air-side film coefficient varies to the 0.5 power of air mass velocity
Air-side pressure drop varies to the 1.75 power of air mass velocity
Tube length Length is established in conjunction with the bundle width. There are usually two
bundles in a section, and two fans per section. Bundle width normally limited to 3.2 m
to 3.5 m (10 ft to 11.5 ft); fans are commonly 3.6 m to 4.3 m (12 ft to 14 ft) in
diameter. API 661 specifies minimum fan coverage of 40%. Therefore, tubes are
typically in the range of 8 m to 10 m long (26 ft to 33 ft).
Tube outside Cost of exchanger is lower with smaller diameter tubes
diameter Cleaning is more difficult with smaller diameter
Minimum recommended (and most common) tube size is 25 mm (1 in) OD
Optimize with pressure drop by adjusting the number of passes and tube size
Fin height Usual fin heights are 9.5 mm, 12.7 mm, and 15.9 mm (3/8 in., 1/2 in., and 5/8 in.)
Selection depends on relative values of air-side and tube-side film coefficients
With higher fins, fewer tubes can be accommodated per row
Typically, use higher fins for steam condensers and water coolers
Typically, use lower fins for gas coolers and viscous liquid hydrocarbon coolers
Fin spacing Spacing usually varies between 276 to 433 fins/m (7 to 11 fins/in)
Typically, use higher density for steam condensers and water coolers
Typically, use lower density for gas coolers and viscous liquid hydrocarbon coolers
Tube pitch Staggered pattern almost invariably employed
Designers tend to use the following combinations of bare-tube OD, finned-tube OD,
and tube pitch:
25 mm / 50 mm /60 mm (1 in / 2 in / 2.375 in)
25 mm / 57 mm / 67 mm (1 in / 2.25 in / 2.625 in)
As tube pitch is decreased, air-side pressure drop and power consumption increase
more rapidly than the air-side heat transfer coefficient
Excerpt from Rules of Thumb for Chemical Engineers, Fifth Edition, by Stephen Hall (Butterworth-
Heinemann, 2012). Table of Contents and accompanying spreadsheet templates at
www.pipesizingsoftware.com/book
Variable Considerations
Number of tube Most exchangers have for to six tube rows, but can range from three to ten
rows Air-side film coefficient varies inversely with number of tube rows
More rows advantage: more heat transfer area in the same bundle width, reducing
number of bundles and sections
More rows disadvantage: increases fan horsepower for the same air velocity and
lowers the Mean Temperature Difference
Typically, four or five tube rows for steam condensers and water coolers
Typically, six or seven tube rows for gas coolers and viscous liquid hydrocarbon
coolers
Number of tube Distribution of tubes in the various passes need not be uniform; especially useful in
passes condensers where the flow area in each pass can be gradually reduced as the liquid
fraction increases progressively
Optimize to obtain uniform pressure drop in each pass
Fan power Power varies directly with volumetric air flow rate and pressure drop
consumption Fan horsepower varies to the 2.75 power of the air mass velocity
Optimum air mass velocity is higher when air-side heat transfer coefficient is highly
controlling (e.g., steam condensers and water coolers)
Exchangers are usually designed with a pressure drop between 0.3 in H2O and 0.7 in
H2O