TOTAL HEAD CALCULATION

Customer : PT AIRCONTECH INDONESIA

Item : Pompa Centrifugal - Chiller Water Pump

Diket : Q = 330 m 3/h = 5500 l/min = 91.67 l/s = 0.092 m 3/s

Ha = 1 Bar = 10 m ( Tidak ada perbedaan elevasi )


Dpipa = 10 Inch = 254 mm = 0.254 m A (m2) = 0.0506
Lpipa = 300 m (panjang pipa)
g = 9.8 m 2/s

V = 1.8100 m/s

DARCY FORMULA : ( Head Loss Pada Pipa )


L V2
Hf = f x
D 2g

0.0005 0.0005
f = 0.020 + = 0.020 + = 0.022
D 0.254

L V2 300 3.2760
Hf = f x = 0.022 x x = 4.34 m
D 2g 0.254 19.6

HAZEN-WILLIAMS FORMULA : ( Head Loss Pada Pipa )


Q1.85 L
Hf = 10.666 x x
C1.85 D4.87

0.0120252 300
= 10.666 x x = 3.74 m
8143.20 0.0012634

Direction Change Bend ( Fuller Formula ) : ( Head Loss on Elbow )


D 0 V2
Helbow = 0.131 + 1.847 x x x
2R 90 2g

3.28
= 1.978 x 0.206 x = 0.07 m
19.6

HL Total = Hf + Helbow + H

= 4.34 + 1.63 + 10.00

= 15.971 m

HL Total = 15.971 x 1.200 ( SF )

= 19.17 m ~~ dibulatkan ke 20 meter.

Note : **** Pressure drop Chiller 0,5 bar ~~ 5 meter

H Total = 20 + 5 = 25 meter

REMARK :
1. Perhitungan loss pd pipa discharge keseluruhan utk 300 meter panjang, asumsi diameter pipa 10 inch.
2. Perhitungan termasuk 24 belokan dengan panjang pipa total maksimal 300 meter.