Professional Documents
Culture Documents
Chapter7 PDF
Chapter7 PDF
Flow.
The flow is calculated from the heat requirement in watts, W, and the
temperature drop across the radiator in Kelvin, K. The valve size can then
either be determined from a selection flow chart or be calculated.
Valve size.
The last valve in the design circuit, (which determines the pump head
throughout the entire system) ought to have a resistance of about 5 kPa.
The other valves should be sized according to the differential pressure
available for them, i.e. the penultimate valve in the design circuit has an
available pressure equal to the resistance across the last valve plus the
resistance in the pipes between the two valves.
∆p 5 kPa
1
∆p 80 kPa
140 133 125 7
∆p 72 kPa ∆p 9 kPa
RTD-N 15
l/h kvs -value Pre-set value l/s
500
,1
300 N ,07
200 7 6 ,05
1 7
100 5 ,03
4
70 0,60 0,45 ,02
50 3
0,36 0,27 2 ,01
kv 30
1 2 3 4 5 6 7 N 0,20 0,12 ,007
20 ,005
RTD-N 15 0,04 0,08 0,12 0,20 0,27 0,36 0,45 0,60 1
RTD-N 20 0,10 0,15 0,17 0,25 0,32 0,41 0,62 0,83
RTD-N 25 0,10 0,15 0,17 0,25 0,32 0,41 0,62 0,83 10 0,08 ,003
7 0,04 ,002
5
Radiator l/h ∆p kPa Pre-set ,001
1 140 5 N 3
1 2 3 4 5 7 10 20 30 kPa
∆pvalve
7 140 9 7
0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 mWG
125 140 72* 3,5
0,01 ,02 ,04 ,06 0,1 ,2 ,3 Bar
140 140 80* 3,5
*too high ∆p, will create a problem with noise. Finding the pre-set values for the thermostatic valves in the above heating system.
Fig. 7:3
Pre-setting.
Adjusting a valve implies a calculation of the difference between the
available and the required pressure for the valve. The resistance across the
valve should then be increased, through adjustment, so that all the
available pressure is utilized. The setting values providing the required
resistance can be read from the selection flow charts.The values for each
valve should be stated on the drawing so that the setting can be made in
connection with the installation.
The control unit has to sense the room temperature to be able to control it.
Fig. 7:4
Control valves.
Primary systems.
Two-way valves and consequently varying flow are recommended for the
primary systems.
∆ppump
∆pmin
∆p ∆psystem
600 Min ∆p = 150 kPa 100
Flow %
500
400 50
300
200
0
100
0
If the pump is equipped with pressure control the valves must be calculated for the
lowest available ∆p. In this case 150 kPa, 1,5 bar, minus the resistance in the heat
exchanger.
Fig. 7:5
Valve size.
Enter information of flow and available differential pressure into the
valve selection flow chart and then select the valve size! The dimension
of the pipe in which the control valve is to be installed has no influence
on the required valve size.
1 2 3 4 5 7 10 15 20 mWG
0,1 ,2 ,3 ,4 ,5 ,7 1,0 1,5 2 Bar
Secondary systems.
Two-way valves should also be used in the secondary systems, with a
main pump supplying the water out to each mixing loop or shunt.
∆ppump
1 2 3 4 5 6 7 8 9
∆pvalve
∆psystem < 15 kPa
60
50 ∆p at 0% flow
40 with max ∆p
30
20 with proportional ∆p
10
0
∆pvalve
With proportional or parallel pump control
This combination provides the control valve with the • a constant ∆p at control valve located the farthest away gives design
same available pressure when the flow fluctuates. values for all the control valves equal to the lowest set differential pres-
Fig 7:8 sure
Valve size.
Enter information of flow and available differential pressure into the
valve selection flow chart and then select valve size! The dimensions of
the pipe in which the control valve is to be installed has no influence on
the required valve size.
0,1 ,03
1 2 3 4 5 7 10 20 30 40 60 100 150 200 kPa
∆pvalve
Sizing valves from a diagram will not give the same mathematical accuracy
as a calculation, but it is good enough when considering the inaccuracy of the
underlying calculations.
Fig 7:9
Valve size.
Divide ∆pv2 by two and choose a control valve from the valve selection
flow chart according to the ∆p and the flow in question. The remaining
∆p, i.e.120 kPa minus ∆pv is the available differential pressure for the
differential pressure control. Enter the differential pressure and the flow
for the differential pressure control into the selection flow chart and
then select size!
∆ppump
∆psystem ∆pmin
∆p
600 Flow % 100
500
400 50
300
200
0
100
0
Min ∆p = 150 kPa
If the pump is equiped with pressure control, the valves must be calculated for the
lowest available ∆p. In this case 150 kPa, 1,5 bar, minus resistance in the heat
exchanger. All valves for which the available ∆p will exceed the design ∆p with
more than 50% require a ∆p control.
Fig, 7:12
Example, control valve and differential pressure control:
∆t = 50 oC
m3/h Valve kvs - value l/s
1 P = 1.500 kW; Q = 1.500 × 0,86 / 50 = 25.800 l/h.
50 15 ∆p available = 1,5 bar. ∆p heat exchanger = 0,3 bar.
0 ∆p = 1,5 - 0,3 = 1,2 bar.
30 1 3 2 4 4 25 10
7
20 16 5 2 ∆p available for ∆p valve = 1,2/2 = 0,6 bar;
10 3 Values for ∆p - valve from diagram: kvs = 40 m3/h;
10
7 6,3 2
3 ∆pv = 0,41 bar
5 4,0
1,0
3 2,5 0,7 4 ∆p available for control valve = 1,2-0,41 = 0,79
2 1,6 0,5 bar
1,0 1,0 0,3 kvs = 40 m3/h; ∆pv = 0,41 bar;
0,7 ,63 0,2 Pre-set value for the ∆p control = 0,41 bar;
0,5 ,4
0,3 0,1
,07
0,2
,05
0,1 ,03
10 20 30 40 60 100 150 kPa
∆pvalve
1 2 3 4 5 7 10 15 20 mWG
Setting value.
A differential pressure control keeps the differential pressure constant
across a circuit. The setting value for the differential pressure control is
equal to the resistance in that particular circuit.
Secondary systems.
In the secondary systems differential pressure controls are used to keep
the differential pressure constant across a control valve or a part of the
system, for example a riser or a two-pipe radiator circuit containing
several thermostatic valves.
Valve size.
Differential pressure control across a control valve.
In the designed circuit first of all check if the differential pressure control
requires a minimum differential pressure. Is this the case, select a size of
control which requires at least this pressure. Even if the resistance across
the smallest valve is not large enough make sure that at least the
minimum differential pressure is available. Select accordingly the size of
the control valve.
The available pressure in the other circuits is divided by two. The control
valve is selected first and the remaining differential pressure is used for
selection of the differential pressure controller.
∆pvalve
< 15 kPa
∆ppump
1 2 3 4 5 6 7 8 9
Example
∆psystem ∆p 100%
∆p Pa ∆p at 0% Q = 3m2/h
With max ∆p ∆ppump = constant
60
50
40 With proportional ∆p ∆pavailable = from the calculation of the design
30
circuit, including valve no 9.
20
∆pvalves no
10 Here: from the above diagram ∆p valve 9.
0
Excessive ∆p ∆pexc. = ∆pavailable - ∆pvalve
Design ∆p ∆ppump = ∆psytem + ∆p control and differential
Available ∆p with or without Without pump control or with constant ∆p pressure valves no 9.
pump control at different flow With proportional or parallel pump contol ∆psystem = 60 kpa.
Fig. 7:14 Sizing of the control and differential pressure
control valves no 9.
Sizing of the control valves and differential pressure control valves in the above See flow chart: 9. 3m3/h ∆p control valve <15 kPa.
heating circuit.
∆p valve no 9 kvs 10, ∆p = 9 kPa.
The ∆p control valve will be the same size
m3/h Valve kvs-value m3/h l/s and ∆p ∆pvalves = 18 kPa.
200 50 ∆ppump = 60 + 9 + 9 = 78 kPa.
145 Selecting valve size from flow chart:
100 30
100 Divide the total available ∆p by 2.
63 20
Find in flow chart the cutting point between flow,
50 40
10
3 m3/h, and the ∆p available for the valve.
30 25 Choose the first valve size which is big enough.
7
20 16 5 Find ∆p across the chosen valve, that is the set pressure
10 for the differential pressure control.
10 3
42 The two valves will have the same size.
7 7 6,3 2
5 Valve ∆pavailable kvs ∆pvalve ∆pvalves
9 8 6 3 1 4,0
5 1,0
3 2,5 0,7
Total 1 valve
2 1,6 0,5 1 53+18=71 35 6,3 23 46
2 44+18=6 31 6,3 23 46
1,0 1,0 0,3 3 39+18=57 28 6,3 23 46
0,7 ,63 0,2 4 34+18=52 26 6,3 23 46
0,5 5 29+18=47 23 6,3 23 46
,4 6 24+18=42 21 10 9 18
0,3 0,1
,07 7 19+18=37 18 10 9 18
0,2 8 12+18=30 15 10 9 18
,05
,03 Calculation of valve no 9.
0,1
1 2 3 4 5 7 10 20 30 40 60 100 150 200 kPa 3
kv = ; kv = 7,8; => valve with kv 10,0;
∆pvalves
∆p 5 kPa 1
∆p 9 6
∆p 9
∆p 80 kPa 140 133 125 ∆p 9 kPa 7
∆p 72 kPa
Setting value.
A differential pressure control keeps the differential pressure constant
across a circuit. The setting value for the differential pressure control is
equal to the resistance in that particular circuit.
∆p 5 kPa 1
∆p 9 6
∆p 9
140 133 126 ∆p 9 kPa 7
20 19 18 2 1
∆p kPa 89 85 81 22 18
,7 1 2 3 4 5 7 10 mWG
20 980 89 10 79 1,6 37
,06 ,1 ,2 ,3 ,4 ,5 ,1 1
Flow limitation.
Flow limitation is required in both primary and secondary systems.
Primary systems.
In a primary system, it is the flow to a whole sub-station or to the applied
heat exchangers that should be limited.
The heat supply is controlled by a control valve and if the differential
pressure across this valve is kept constant with a differential pressure
control the sub-station contains the required components to limit the
flow.
Calculate the differential pressure that is necessary across the fully open
valve to obtain required flow. Set the differential pressure control so that
it will provide the differential pressure and the maximun flow is limited.
Combined flow limiters consisting of a differential pressure control and
k vs 4,0 a setting valve are available. The differential pressure control keeps a
constant differential pressure across the integrated pre-set valve. The size
∆pvalve kPa of the flow is determined by changing the resistance across the setting
valve. When large sizes are required a flow limitation is obtained as a
differential pressure control can keep a constant differential pressure
across a integrated pre-set valve. The valve size is determined in a
Example, limiting the flow in a primary circuit.
selection flow chart on basis of the available differential pressure and the
Control valve kvs 4,0
flow.
Ex. no Q m3/h ∆pvalve. ∆pvp-set m3/h kvs-value l/s
10 3
1. 3 55 55 7 2
2. 4 100 100 5
1 2 1,0
3. 1 6,3 6,3 3
0,7
2 4 0,5
The ∆p necessary for a specific flow through a fully
3
open control valve is equal to the setting ∆p for the 1,0 0,3
differential pressure control. 0,7 0,2
Calculation 0,5
1 ∆pv = ( 43 ) ; ∆pv = 0,56 bar => 56 kPa;
2
0,3
0,1
,07
0,2 ,05
∆pv = ( 44 ) ; ∆pv = 1 bar => 100 kPa;
2
2
0,1 ,03
∆pv = ( 1 ) ; ∆pv = 0,0625 bar => 6,3 kPa;
2 1 2 3 4 5 7 10 20 30 40 60 100 kPa
3
4
∆p 0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 10 mWG
Fig. 7:20 0,01 ,02 ,04 ,06 0,1 ,2 ,3 ,4 ,5 ,7 1,0 Bar
Limiting the flow in a sub - station equiped with ∆p control valve
Fig. 7:21
Secondary systems.
In secondary systems the limitation of the flow could come into
question to a shunt coupling, a riser or a one-pipe circuit.
If there already is a control valve and a differential pressure control in a
shunt coupling, use these for the flow limitation too! Calculate the resis-
tance across a fully open control valve at the maximum required flow and
set the differential pressure control on this differential pressure!
In other cases there are flow limiters keeping the differential pressure
constant across a built-in adjustment valve. They are often sized
according to the available differential pressure and the required flow.
Setting value is read in the selection flow chart.
1 2 3 4 5 7 10 20 30 40 60 100 kPa
∆pv = ( 1,6 ) ; ∆pv = 0,25 bar => 25 kPa;
0,8 2
∆p 0,1 0,2 ,3 ,4 ,5 ,7 1 2 3 4 5 7 10 mWG 2
Fig. 7:23
Limiting the flow for a control valve in a secondary circuit with ∆p control.
Fig. 7:22
Example, ASV-Q
ASV-Q Capacity l/h Setting value
15 100-800 1-8
20 200-1400 2-14
25 400-1600 4-16
32 500-2500 5-3
Q = 1100 l/h
Choose ASV-Q 20
(always choose the smallest possible valve)
Setting value = 11
∆p one-pipe circuit
∆pv
∆p available
Control equipment.
Different control equipment is required for different purposes. The
control of the flow temperature to radiators requires one type of control,
hot water heating requires another, and ventilation devices require a third
type. For the last two cases there is also a choice between electronic and
self-acting control.
Radiator systems.
The flow temperature in radiator systems is controlled according to the
outdoor temperature by a weather compensator.
The electronic central control can be equipped with timers with twenty-
four hours or weekly functions. This is however only the case if the heat
supply is set back during a period of several days and nights and if the
system is not connected to a computer.
A pump stop is an optional function which shuts off the circulation
pump when the outdoor temperature is so high that the building requires
no heating.
The limitation of the return temperature is usually not required in the
two-pipe systems with thermostatic valves.
A computerized supervision and control system is a labour-saving and
efficient way of controlling large systems with many sub-stations.
Weather compensator
Flow compensated thermostatic valve for control of domestic hot water tempera-
ture.
Fig. 7:26
Heat exchangers.
Modern heat exchangers, plate and coil units, contain small quantities of
water and the flow channels are narrow. By making them short and by
Domestic hot water, Q l/s Effect, P kW laying a large number of them parallel, the flow resistance is kept at a low
2,5
400
level in spite of a relatively high water rate.
2,0 350
300 The high water rate is necessary to prevent deposits from settling on the
1,5
250
200
heat transferring surfaces.
1,0
150
0,5 100 The resistance across the coil unit is in the range of 20-30 kPa and for
0
50
0
the plate heat exchanger the resistance is up to 50 kPa. The choice of size
1 10 50 100 150 200 250 is made according to the instructions from the manufacturer. There are
Number of apartments
domestic water selection flow charts, based on empirical values, giving
Maximum required flow according to the Swedish the total consumption for various number of apartments.
Board for District Heating
Fig. 7:27
Heat meters.
Heat meters register the delivery to each building/apartment, but they
also indicate if anything goes wrong in the system. As there are large
variations in the flow, a flow meter must also be able to measure low flows Accumulator
with great accuracy. Heat meter
% ∆p, P
100
50 2
∆p n =∆Q x p 0
3
P n =∆Q 0 xP 0
0
Q 0 50 100%
The resistance varies by the square of the flow change and the effect of the pump
by the cubic
Fig. 7:30