Professional Documents
Culture Documents
When is passive or
active the better desiccant approach? When is one out of the question? We’ll discuss how to control
the latent load, arrive at a smart design decision for the circumstance, and consider recent research
on first cost and performance.
BY STANLEY A. MUMMA, PH.D., P.E.
T
wo essential attributes of mechanical systems intended to facility and may adversely affect the IEQ and IAQ. Consequently,
provide building occupants with good IAQ and indoor one should generally assign the DOAS the entire task of moisture
environmental quality (IEQ) are uncompromised venti- removal, both in the OA and within the occupied spaces.
lation air delivery and ensured humidity control. When the DOAS has the task of removing all moisture generated
Engineers have numerous mechanical system selection options and/or leaked into the occupied spaces, the required SA DPT is a func-
at their fingertips, however, most options fail one or both of the tion of the design space DPT (related to the design space drybulb tem-
required attributes. One mechanical system capable of economi- perature (DBT) and % rh), the latent load, and the rate of DOAS SA to
cally meeting the essential attributes is a properly designed dedi- an individual space. Each individual space needs to be scrutinized.
cated outdoor air system1. DOASs are designed to deliver at least the The required SA DPT for DOAS is often around 45°, or below
minimum 100% OA specified by ASHRAE 62.1 to each occupant, the ordinary 52° DPT associated with conventional VAV. Increasing
and to completely and continually meet the individual space latent the SA flow rates to the space requiring the lowest SA DPT (gener-
cooling loads with dry air. ally at the perimeter) will allow the design DPT to be increased,
relaxing the SA DPT required for the entire facility.
SELECTING THE DOAS SUPPLY AIR DEWPOINT The lower than normal SA DPTs have led some to employ low
TEMPERATURE temperature techniques, others to use ice thermal storage and associ-
A DOAS, delivering the required ASHRAE 62.1 ventilation air, ated low chilled water/brine temperatures, and still others to employ
rarely supplies more than a small fraction of the air delivered by desiccants (active desiccant and passive dehumidification compo-
an all air system, such as a VAV. Consequently, the DOAS is seldom nents) with conventional temperature DX cooling equipment.
able to meet the space sensible loads, even if the supply air (SA) Desiccants use either adsorption or absorption to attract water
dewpoint temperature (DPT) is low (40°F to 50°), thus requiring molecules to accumulate at the desiccant. Adsorption desiccants
parallel sensible cooling equipment. The design engineer must include zeolites (molecular sieve) and silica gel. Absorption des-
make a conscious decision to allow the parallel cooling equipment
to also meet either none or a part of the space latent load.
Some parallel cooling equipment can accommodate latent cooling
More to the story
(e.g., fancoil units). Other parallel cooling equipment — such as chilled Humidity control and DOAS are big topics. So big, in fact, that we have
ceilings, beams, and floors — must not be allowed to handle any of the more to offer on the subject. For an expanded version of this article,
space latent load, in order to avoid condensation on the cool surfaces. plus additional graphics to support the text, visit its online version at
Even when the terminal equipment is permitted to remove www.esmagazine.com.
moisture, the drain pans become septic amplifiers throughout the
w w w. esmag a zin e. co m 37
DOAS & Desiccants
100
iccants include hygroscopic salts such as
lithium chloride.
90
2 DOAS EQUIPMENT IN THE
80 MARKETPLACE
Due to limited space, this article can
70
not discuss all equipment. However, let’s
60
attempt to cover the general classes.
5, 6
3, 4 50 NO ENERGY RECOVERY CLASS
The simplest and lowest first-cost class is
40 simply a cooling coil (CC) used to suppress
45 50 55 60 65 70 75 80 85 90 the SA DPT to 52° (removing all the OA latent
DBT, F load, but only part of the space latent load),
and allowing the parallel equipment to take
FIGURE 2. Psychrometric chart for CC and EW+CC. care of the balance of the sensible and latent
loads not accommodated by the ventilation air. The 52° SA DOAS mim- 150
ics a VAV system when the VAV box has modulated to the minimum air 1
140
mode. Neutral air temperatures would never seem to be desired. Modu- 7 130
lating the ventilation airflow rates based upon occupancy could save
cooling or heating energy at off-design occupancy ventilation rates, since 120
equipment is about 0.7, the high latent loads of the OA require equip- 60
5
ment capable of delivering sensible cooling well beyond the needs. To 6
3 50
prevent overcooling, the equipment cycles on and off without provid- 4
ing adequate dehumidification, unless equipped with reheat. 40
45 50 55 60 65 70 75 80 85 90
DBT, F
TOTAL ENERGY RECOVERY CLASS
The next step in the progression of DOAS equipment classes adds a FIGURE 3. Psychrometric chart for EW+CC+SW.
total energy recovery (TER) component (wheel or plate type) upstream
of the CC to recover total energy from the exhaust airstream. TER
(employing passive desiccants) is not able to drop the SA DPT low
enough to do space dehumidification by itself, so a CC is still required.
ASHRAE 90.1 requires TER (for most climates) in all but low-rise
buildings when the DOAS is handling 5,000 cfm or more. The TER
device employs a desiccant that is regenerated without the expenditure
Type I
Type II
Type III
0 20 40 60 80 100
% RH in process air stream
150
1
140
130
7
120
110
3 100
2 90
80
70
60
6
50
4 5
40
45 50 55 60 65 70 75 80 85 90
DBT, F
CC BPD
State 2
Bypass
State 1,
OA State 2
OA
State 3 State 4
Supply
State 5
ADesW HC
100
90 Mumma is an
ASHRAE fellow and
80 a professor of archi-
70 tectural engineering
2
at Penn State Uni-
60 versity. Write him at
50
sam11@psu.edu or
visit http://doas-radi-
4 40 ant.psu.edu.
30
3 WORKS CITED
20
30 40 50 60 70 80 90 100 110 1. TIAX LLC, “Energy Consumption
DBT, F Characteristics of Commercial Building
HVAC Systems: Volume III, Energy Sav-
FIGURE 12. Psychrometric chart depicting active dehumidification.
ings Potential,” 2002: http://doas-radiant.
psu.edu/DOE_Brodrick_report.ppt.
at the link in the references). The ASHRAE are superior for office and retail applica- 2. TIAX LLC, 2003. “Matching the Sensible
research did not analyze systems utilizing tions. The results did not favor DOAS w/ Heat Ratio of Air Conditioning Equip-
PDHCs. The modeled airflow rate per ton EW+DX for the 350-sq-ft hotel room with ment with the Building Load SHR,” 2003:
of cooling ranged from 300 to 400 cfm/ton respect to room humidity control; other- http://doas-radiant.psu.edu/TIAX_FR_
of cooling, corresponding to saturated SA wise, it did well. The poor humidity control SHR_PKG_AC_&_TER.pdf.
temperatures of 48° and 52°, respectively. is a reflection of improper system sizing for 3. GARD Analytics, 2006. “ASHRAE 1254-
The terminology used in Tables 2 through 4, the analysis, rather than an innate inability RP Evaluating The Ability Of Unitary
DOAS w/ADesW + DX and DOAS w/ EW+DX of the DOAS to control humidity. Where Equipment To Maintain Adequate Space
recognizes that the DOAS is not capable of high latent generation is present relative to Humidity Levels, Phase II,” 2006: http://
providing all of the space cooling due to the low occupancy, either the rate of ventilation air doas-radiant.psu.edu/ASHRAE_1254RP_
ventilation airflow rates, and requires a parallel must be increased or the SA DPT dropped. FR.pdf.
cooling system — DX in the research project.
The base DX and the DX w/ADesW were each CONCLUSIONS AND
sized to satisfy the entire space loads. RECOMMENDATIONS
Clearly, humidity control, annual oper- Providing the correct ventilation and
ating costs, and LCC for DOAS w/ EW+DX space % rh for the purpose of achieving
w w w. esmag a zin e. co m 49