Professional Documents
Culture Documents
Processing
Processing
Control loops
Example of level control system of a continuous stirred-tank reactor. The flow control
into the tank would be cascaded off the level control
Treatment of emulsions:
Emulsions are mixtures of two or more dissimilar fluids.
They are normally created by the individual components
being subjected to changes in pressure and agitation.
Such conditions arise when oil and water leave the
reservoir and move up the production string through the
choke and other items of equipment, end route – track -
to the separator.
Water is associated with the crude oil as following:
1- Free water:
This water is not intimately mixed in with the crude. It is
basically a volume of water that just happens to be
moving along with the crude, such as in a pipeline.
Free water should settle out the oil in any quiescent zone.
It should settle in separators, knockout separator and
storage tanks.
The rate of settling of an immiscible liquid (water) from
another liquid (oil) can be calculated from the following
equation:
K (ρw - ρo) gd2
Rate of settling =
μ
Where:
K = constant of system involved.
ρw = density of water.
ρo = density of oil.
g = gravity factor.
d = diameter of droplet.
μ = viscosity of oil.
2- Emulsified water:
If the water and crude oil have been intimately mixed
due to turbulent flow together or by the shearing action
when passing through pumps, orifices, valves, etc. Then
an emulsion is formed. Tiny droplets of water are
scattered through the continuous oil phase that called
water-in-oil emulsion.
The electrical, heating and chemical treatment are the
efficient way to separate the emulsified water from the
oil.
On the other hand, we deliberately inject wash water into
the crude to create an emulsion to wash out salts and
solids.
3- Soluble water:
The solubility of water in oil is to a great extent a
function of temperature but is also dependent upon the
type of hydrocarbon.
Soluble water will not settle out with time. In fact
lowering the temperature of the oil is really the only way
to remove at least some of the soluble water. Neither
electrical nor chemical dehydration will remove soluble
water.
API is the American petroleum institute.
API gravity is based on empirical scale gravities in
degrees.
API gravity and normal specific gravity are linked by the
formula:
The (4–20 Ma) convention was born in the 1950s out of the earlier highly
successful( 3–15 psi) pneumatic control signal standard, when electronics
became cheap and reliable enough to emulate the older standard
electrically. The( 3–15 psi) standard had the same features of being able
to power some remote devices, and have a "live" zero.
However the (4–20 Ma) standard was better suited to the electronic
controllers then being developed.
The transition was gradual and has extended into the 21st century, due to the huge
installed base of 3–15 psi devices. As the operation of pneumatic valves over motorised
valves has many cost and reliability advantages, pneumatic actuation is still an industry
standard.
BASIC OF FLAPPER / NOZZLE SYSTEM AS AN PNEUMATIC LOOP
To allow the construction of hybrid systems, where the 4–20 mA is
generated by the controller, but allows the use of pneumatic
valves, a range of current to pressure (I to P) converters are
available from manufacturers. These are usually located locally to
the control valve and convert 4–20 mA to 3–15 psi (or 0.2–
1.0 bar). This signal is then fed to the valve actuator or more
commonly, a pneumatic positioner.
The positioner is a dedicated controller which has a mechanical linkage to the actuator
movement. This ensures that problems of friction are overcome and the valve control
element moves to the desired position. It also allows the use of higher air pressures for
valve actuation.
With the development of cheap industrial micro-processors, "smart" valve positioners
have become available since the mid-1980s and are very popular for new installations.
These include an I to P converter, plus valve position and condition monitoring. These
latter are fed back over the current loop to the controller, using such as
the HART protocol.
Module 7– Piping and Instrumentation Drawings
The P&ID acts as a directory to all field instrumentation and control that will be
installed on a process and thus is a key document to the control engineer.
Since the instrument tag number assigned to field devices is shown on this
document. The instrument tag associated with, for example, a measurement
device or actuator of interest may be quickly found.
Module 8- Controller Tuning
A control loop is a process management system designed to maintain a
process variable at a desired set point. Each step in the loop works in
conjunction with the others to manage the system. Once the set point has
been established, the control loop operates using a four-step process.
Control tuning
with the others to manage the system. Once the set point To tune the
control device then must refer to the set value in manual mode before
transfer to automatic mode.
PID controller theory
Note: Due to the diversity of the field of control theory and application,
many naming conventions for the relevant variables are in common use
This section describes the parallel or non-interacting form of the PID
controller. For other forms please see the Section "Alternative notation
and PID forms".
The PID control scheme is named after its three correcting terms, whose
sum constitutes the manipulated variable (MV). Hence
:
where Pout, Iout, and Dout are the contributions to the output from the PID
controller from each of the three terms, as defined below
Proportional term
Where
• Iout: Integral term of output
• Ki: Integral gain, a tuning parameter
• e: Error = SP − PV
• t: Time or instantaneous time (the present)
• τ: A dummy integration variable
The integral term (when added to the proportional term) accelerates the
movement of the process towards setpoint and eliminates the residual
steady-state error that occurs with a proportional only controller.
However, since the integral term is responding to accumulated errors
from the past, it can cause the present value to overshoot the setpoint
value (cross over the setpoint and then create a deviation in the other
direction). For further notes regarding integral gain tuning and controller
stability, see the section on loop tuning
Derivative term
Where
• Dout: Derivative term of output
• Kd: Derivative gain, a tuning parameter
• e: Error = SP − PV
• t: Time or instantaneous time (the present)
The derivative term slows the rate of change of the controller output and
this effect is most noticeable close to the controller setpoint. Hence,
derivative control is used to reduce the magnitude of the overshoot
produced by the integral component and improve the combined
controller-process stability. However, differentiation of a signal amplifies
noise and thus this term in the controller is highly sensitive to noise in the
error term, and can cause a process to become unstable if the noise and
the derivative gain are sufficiently large
Summary
The proportional, integral, and derivative terms are summed to calculate
the output of the PID controller. Defining u(t) as the controller output, the
final form of the PID algorithm is:
Settling Error at
Parameter Rise time Overshoot
time equilibrium
Small
Kp Decrease Increase Decrease
change
Indefinite (small
Kd decrease or Decrease Decrease None
increase)