Station Equipment

PUMP COOLING
Pump Cooling & Cooling / Seal Flushing Using an External Source

All entries are clickable


SECTION PAGE
STATION EQUIPMENT STATION
EQUIPMENT 62
SUPERSEDES ISSUED
Pump Cooling & Cooling / Seal Flushing
01/92 01/97

Pump cooling and cooling/seal flushing using an external source.


ITT Flygt C-Pumps, with a cooling jacket, provide heat COOLING/SEAL FLUSHING
dissipation from the motor by means of flow through Only one hose is required for this system. The flushing
internal passages. (See next page for Models with cooling water enters a threaded connection, circulates around the
jackets). These passages allow the pumped media, after motor and exits through the liquid end, it passes across the
filtering out the large particles, to flow around the stator seal housing, thus keeping it clear of any abrasive mate-
housing. rial.
In the event the pumped media is unsuitable for motor When cooling, or Cooling/Seal Flushing is set up in the
cooling (high in temperature, in abrasives, or in fibre pump, it is extremely important that the cooling water is
content), the internal inlet to the cooling jacket must be maintained at the desired minimum rate while the pump is
blocked to prevent the pumped media from entering the running. To protect the pump from damage, ITT Flygt has
cooling jacket. Cooling water must then be supplied to the a system which insures that the pump and the water source
pump internal passages from an external source. are operating simultaneously. This system consists of a
paddle wheel flow switch. By connecting the flow switch
There are two types of systems; pump cooling, and pump
to the pump electrical control panel, the flow switch will
cooling/seal flushing. Pump cooling is usually employed
monitor the coolant flow and will shut down the pump if
in applications where it is not feasible to mix the cooling
that flow is insufficient.
water with the pumped media. Pump cooling/seal flushing
is used when the pumped media is abrasive, to flush the NOTE:
seals continuously with clear water, preventing the en- When the pump is modified for Cooling, or Cooling/Seal
trance of abrasive material to the seal faces. It is of Flushing from an External Source, the pump must be
paramount importance that the type of system desired be supplied with water from that source at all times, even if
specified so that the correct internal modifications to the the pumped media becomes acceptable to cool the motor.
pump can be made at the factory. They are as follows: The external source can only be removed of the pump is
converted back to its original arrangement at the factory.
COOLING
The cooling water enters the motor cooling jacket through
a threaded connection, circulates through the motor cool-
ing jacket, and exits at another threaded connection to
which the return hose is attached.

DIMENSIONS ARE IN mm (INCHES)


SECTION PAGE
STATION EQUIPMENT STATION
EQUIPMENT 63
SUPERSEDES ISSUED
Pump Cooling & Cooling / Seal Flushing 01/97
01/92

Pump cooling and cooling/seal flushing using an external source.


MODEL 3060 3080 3126(SS) 3152 3170 3201 3231 3300 3306 3312 3356 3351-3602

Minimum Flow
Rate (GPM) *5.0 *5.0 *5.0 *5.0 *5.0 *5.0 11.0 5.5 11.0 16.0 11.0 16.0
WITHOUT
SEAL FLUSH

* The minimum flow rates for actual cooling purposes are actually less than the 5 GPM shown.
WITH
However, a minimum of 5 GPM is necessary to activate the monitoring system. Also, with these
SEAL
FLUSH
models, the 5 GPM will combine cooling with seal flushing. For all other models, the cooling flow rate
shown must be doubled if the combination of cooling with seal flushing is required.

IMPORTANT: The purpose of the flow monitoring kit is to provide


It is most important that the inlet pressure of the automatic shut down of the pump should the flow of
coolant liquid be greater than the volute pressure of external coolant be lost during pump operation.
the pumped liquid to permit internal circulation. The
volute pressure of the pumped liquid would be the FLOW
total head plus submergence at duty point converted ARROW

to pounds per square inch.

PADDLE
FLOW
SWITCH

POWER
CABLE

GENERAL PROTECTIVE COOLING CIRCUIT W/FLOW SWITCH

CONTROL VOLTS
RESET
IFS IPB
CR-1
CR-2

Typical electric circuit to insure coolant flow. N.O.


WATER contact CR-2 to be wired in series with other motor
HOSE protective circuitry so that contactor drops out and
pump stops when coolant flow is lost.

NOTES:
1. For all external cooling applications, consult ITT
Flygt Applications Engineering.
2. Two hoses will be needed if it is not acceptable for
spent coolant to mix with pumped media (supply
and return); only one required if spent coolant
empties into pumped media.
3. Pump modifications by Factory.

DIMENSIONS ARE IN mm (INCHES)