Professional Documents
Culture Documents
Natural
National Engineering Handbook
Resources
Conservation
Service
Chapter 16 Hydrographs
Rain clouds
Cloud formation
Precipitation
tion
Evaporation
ira
n
ean
tio
Transp
oil
ta
from oc
ge
s
ve
from
m
on
fro
ms
ati
n
tio
ir
a
tre
sp
ra
po
an
ms
va
Tr
Surfa E
fro
ce ru
noff
Infiltration
Soil
Percolation
Rock Ocean
Ground water
Deep percolation
March 2007
Tables Table 16–1 Ratios for dimensionless unit hydrograph and 16–4
mass curve
Table 16–3 Rainfall tabulated in 0.3 hour increments from plot 16–11
of rain gage chart in figure 16–3
Figures Figure 16–1 Dimensionless unit hydrograph and mass curve 16–3
Figure 16–3 Accumulated or mass rainfall and runoff curves for 16–7
CN 85 taken from a recording rain gage
1.0
.9
Mass curve
.8
.7
q=Discharge at time t
.6 qp=Peak discharge
q/qp or Qa/Q
.4
.3
.2
.1
DUH
0
0 1 2 3 4 5
t/Tp
Figure 16–2 Effect of watershed shape on the peaks of unit hydrographs (Equations, definitions, and units for variables are
found in appendix 16A.)
(a)
Area A
Area B
D.A.=4.6 mi2
1,500 Tc=2.3 h
∆D=0.3 h
qp=1455 ft3/s
D.A.=4.6 mi2
Tp=1.53 h
Tc=6.0 h
1,000
∆D=0.8 h
q (ft3/s)
zero at 20 hours
0 0
0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9
Time (h) Time (h)
Figure 16–2 Effect of watershed shape on the peaks of unit hydrographs (Equations, definitions, and units for variables are
found in appendix 16A.)—Continued
(b)
1,000
Area C2 Area C1
D.A.=2.0 mi2 D.A.=2.6 mi2
q, ft3/s
Tc=1.5 h Tc=6.0 h
500 Unit hydrograph
from area C2 ∆D=0.2 h ∆D=0.8 h
Unit hydrograph qp=988 ft3/s qp=315 ft3/s
from area C1 Tp=1.0 h Tp=4.0 h
(C1)
0
0 5 10 15 20
Time (h)
(C2)
1,000
q (ft3/s)
0
0 5 10 15 20
Time (h)
The equations used in this example are found in appendix 16A. It is recommended to read appendix 16A be-
fore reading the example.
Problem: Develop a composite flood hydrograph using the runoff produced by the rainfall taken from a
recording rain gage (fig. 16–3) on watershed (area A) shown in figure 16–2.
Figure 16–3 Accumulated or mass rainfall and runoff curves for CN 85 taken from a recording rain gage
4
Rainfall
3
Volume (in)
Runoff from
2 CN-85
0
0 1 2 3 4 5 6
Time (h)
1.0
0.8
0.6
0.4
0.2
0.0
Solution:
Step 1 Develop and plot unit hydrograph.
Using equation 16A–13 in appendix 16A, compute ∆D:
∆D = 0.133 Tc
∆D = 0.133 × 2.3 = 0.306,use 0.3 hours
Using equation 16A–7 from appendix 16A, compute Tp:
∆D
+L Tp =
2
.30
Tp = + (.6 × 2.3 ) = 1.53 h
2
Using equation 16A–6 from the appendix, compute qp for volume of runoff equal to 1 inch:
484 AQ
qp =
Tp
484 × 4.6 × 1
qp = = 1, 455 ft 3 / s
1.53
The coordinates of the curvilinear unit hydrograph are shown in table 16–2, and the plotted
hydrograph is figure 16–4.
Step 2 Tabulate the ordinates of the unit hydrograph from figure 16–4 in 0.3 hour increments (∆D)
(table 16–4a, column 2).
Step 3
Check the volume under the unit hydrograph by summing the ordinates (table 16–4a, column 2)
and multiplying by ∆D.
9,914 × 0.3 = 2,974 (ft3/s)h
Compare this figure with the computed volume under the unit hydrograph:
645.33 ft 3 /s h ( )
mi 2 × in
× 4.6 mi 2 × 1 in = 2, 969 ft 3 /s h ( )
The difference between the two volumes in this example is less than 1 percent, and can be con-
sidered negligible.
If the volumes fail to check closely, reread the coordinates from figure 16–4 and adjust if neces-
sary until a reasonable balance in volume is attained.
Table 16–2 Computation of coordinates for unit hydrograph for use in example 16–1
Time ratios Time Discharge ratios Discharges Time ratios Time Discharge ratios Discharges
(table 16–1) (col 1 × 1.53) (table 16–1) (col 3 × 1,455) (table 16–1) (col 1 × 1.53) (table 16–1) (col 3 × 1,455)
(t/Tp) (h) (q/qp) (ft3/s) (t/Tp) (h) (q/qp) (ft3/s)
1,500
1,400
Unit hydrograph
1,300
1,200
1,100
1,000
Discharge (ft3/s)
900
800
700
600
500
400
300
200
100
0
0 1 2 3 4 5 6 7 8
Time (h)
Step 4 Tabulate the accumulated rainfall in 0.3-hour increments (table 16–3, column 2).
Step 5 Compute the accumulated runoff (table 16–3, column 3) using CN of 85 and moisture condition
II.
Step 7 Tabulate the incremental runoff in reverse order (table 16–3, column 5) on a strip of paper hav-
ing the same line spacing as the paper used in step 2. A spreadsheet program may also be used
to develop the composite hydrograph.
Step 8 Place the strip of paper between column 1 and column 2 of table 16–4(a) and slide down until
the first increment of runoff (0.12) on the strip of paper is opposite the first discharge (140) on
the unit hydrograph (column 2). Multiplying 0.12 × 140 = 16.8 (round to 17). Tabulate in column
3 opposite the arrow on the strip of paper.
Step 9 Move the strip of paper down one line (table 16–4(b)) and compute (0.12 × 439) + (.27 × 140)
= 90.48 (round to 90). Tabulate in column 3 opposite the arrow on the strip of paper. Continue
moving the strip of paper containing the runoff down one line at a time and accumulatively
multiply each runoff increment by the unit hydrograph discharge opposite the increment.
Table 16–3 Rainfall tabulated in 0.3 hour increments from plot of rain gage chart in figure 16–3
Time Accum. Accum. Incremental Reversed Time Accum. Accum. Incremental Reversed
rainfall runoff 1/ runoff incremental rainfall runoff 1/ runoff incremental
(h) (in) (in) (in) runoff (h) (in) (in) (in) runoff
(1) (2) (3) (4) (5) (1) (2) (3) (4) (5)
0.0 0.00
0.3 0.37 0.00 0.00 0.09 3.3 2.71 1.35 0.01 0.00
0.6 0.87 0.12 0.12 0.19 3.6 2.77 1.40 0.05 0.00
0.9 1.40 0.39 0.27 0.24 3.9 2.91 1.51 0.11 0.06
1.2 1.89 0.72 0.33 0.31 4.2 3.20 1.76 0.25 0.12
1.5 2.24 0.98 0.26 0.42 4.5 3.62 2.12 0.36 0.18
1.8 2.48 1.16 0.18 0.36 4.8 4.08 2.54 0.42 0.26
2.1 2.63 1.28 0.12 0.25 5.1 4.43 2.85 0.31 0.33
2.4 2.70 1.34 0.06 0.11 5.4 4.70 3.09 0.24 0.27
2.7 2.70 1.34 0.00 0.05 5.7 4.90 3.28 0.19 0.12
3.0 2.70 1.34 0.00 0.01 6.0 5.00 3.37 0.09 0.00
1/ Runoff computed using CN 85 moisture condition II.
Table 16–4(c) shows the position of the strip of paper containing the runoff when the peak
discharge of the flood hydrograph (2,356 ft3/s) is reached. If only the peak discharge of the flood
hydrograph is desired, it can be found by making only a few computations, placing the larger
increments of runoff near the peak discharge of the unit hydrograph.
Table 16–4(d) shows the position of the strip of paper containing the runoff at the completion of
the flood hydrograph. The complete flood hydrograph is shown in column 3. These discharges
are plotted at their proper time sequence on figure 16–5, which is the complete flood hydrograph
for example 16–1.
Step 10 Calculate the volume under the flood hydrograph by summing the ordinates (table 16–4(d), col-
umn 3) and multiplying by ∆D: 33,409 × 0.3 = 10,022.7 ft3/s‑h.
2,500.000
Composite flood
hydrograph
2,000.000
Discharge (ft3/s)
1,500.000
1,000.000
500.000
0
0 4 7 10 15 18 19 22 25 28 31 34 37 40 43 46
Time (h)
0.26 101 Step 3—For storm events with both measured rainfall
and streamflow, develop a cumulative rainfall distribu-
1 238 tion to be entered into the WinTR–20 data file. If the
2 349 watershed is small enough or if rainfall data are lim-
3 433 ited, a single rain gage may be used to represent uni-
3.7 484 form rainfall over the watershed. If more than one rain
gage is available, rainfall isohyets may be drawn over
4 504 the watershed and rainfall varied for each subarea.
5 566
Step 4—Runoff volume may be determined for the Problems inevitably occur when working with rainfall
streamflow hydrograph and is recommended to be and runoff data. Problems indicating that a particu-
the first parameter calibrated. Runoff volume is the lar event should not be included in the analysis may
volume of the hydrograph above the baseflow. Several include:
baseflow separation methods are described in stan-
• a significant flood event with minor rainfall and
dard hydrology texts, but in many small watersheds,
vice versa
baseflow is relatively small and a constant baseflow
can generally be assumed. The runoff curve number • more runoff volume than rainfall (such as may
for the watershed (or its subareas if so divided) should happen with snowmelt events,) see NEH 630,
be adjusted such that the storm event rainfall produc- chapter 11, Snowmelt
es the storm event runoff.
• timing of rainfall and runoff measurements may
be out of synchronization (for example, the
Step 5—If the hydrograph at the gage has significant
hydrograph may begin rising before there is any
baseflow, the value may be entered in the appropri-
rainfall)
ate location in the WinTR–20 input file. Consideration
should also be given to prorating the baseflow value
If more than one storm event is analyzed, a wide range
(based on drainage area) at other locations along the
of event peak rate factors may result. The causes of
stream network.
these kinds of problems include:
Step 6—Timing of the peak discharge at the gage is • poor data quality
dependent primarily upon the time of concentration
• nonuniform rainfall over the watershed
and stream cross section rating tables. The value of
Manning's n used for overland flow, concentrated flow, • rainfall (magnitude and/or distribution) at the
and channel flow is not known precisely. Using gage gage not representing rainfall over the watershed
data may help in refining these estimates. If the times
• partial area hydrology
to peak of the measured and computed hydrographs
are not similar, the timing factors of the watershed • runoff curve number procedure not representing
should be adjusted to bring the times to peak into the distribution of runoff over time
closer agreement.
• frozen soil, snowmelt runoff, transmission loss,
or physical changes in the watershed over time
Step 7—After the runoff volume and timing have
(urbanization, reservoir construction, channel
been adjusted, the DUH may be calibrated by entering
modification)
different DUHs in WinTR–20 with various peak rate
factors. The objective is to match the peak discharge • the DUH may even be sensitive to the magnitude
and shape of the measured hydrograph as closely as of the storm and resulting flood
possible.
If the range of PRFs for the various storm events is
Considerations to be made in selecting events to wide, the data and watershed characteristics should be
analyze should include single versus multiple peak investigated to determine the reason. Judgment needs
hydrographs, long versus short duration rainfalls, high to be exercised in determining what DUH best repre-
versus low event runoff curve numbers, and large sents the watershed. Example 16–2 shows the proce-
versus small flood events. Rainfall events separated by dure to determine the dimensionless unit hydrograph
a relatively short time span may not allow the stream- for a gaged watershed.
flow hydrograph to return to baseflow. Use of a com-
plete hydrograph that begins and ends at baseflow is
recommended.
Watershed and storm event description: The watershed selected for this example is Alligator Creek
near Clearwater, Florida. Hourly discharge and rainfall data
were provided by the U.S. Geological Survey. The watershed
has a drainage area of 6.73 square miles. For simplicity,
the watershed is treated as a single watershed and is not
divided into subareas. The date of the storm event being
analyzed is February 2, 1996. The storm had a duration of 15
hours and a total rainfall of 3.69 inches. The peak discharge
at the stream gage was 436 cubic feet per second.
Rainfall and runoff data: Columns 1 to 3 in table 16–6 show the time series of
measured rainfall and stream discharge. The rainfall
distribution for the storm event is plotted in figure 16–6.
The baseflow of the hydrograph is 4.7 cubic feet per second.
After subtracting the constant baseflow from the measured
hydrograph, the runoff volume was computed to be 1.45
inches. The runoff curve number corresponding to 3.69
inches of rainfall and 1.45 inches of runoff is 75, which was
used in WinTR–20 for the watershed runoff curve number.
Dimensionless Unit Hydrograph: A DUH for any desired peak rate factor may be developed
from the gamma equation (16–1) described in this section.
Appendix 16B has standard tables that have been developed
for a DUH based on the gamma equation for peak rate fac-
tors ranging from 100 to 600 (at increments of 50). The PRF
for this individual storm event was between 200 and 250.
The sum of the DUH coordinates in table 16–7 is 13.5361.
Using the given nondimensional time step 0.2 and equation
16–2 results in a calculated PRF of 238.37, and is rounded
to 238. The final peak rate factor of 238 was selected (which
gave a good fit of hydrograph shape and peak discharge).
The DUH is listed in table 16–7 and plotted in figure 16–7.
The computed hydrograph for this PRF is in column 4 of
table 16–6. The comparison of the measured and computed
hydrographs is shown in figure 16–8.
Table 16–6 Storm event of February 2, 1996, at Alligator Creek near Clearwater, FL
4.00
3.00
2.50
Rainfall (in)
2.00
1.50
1.00
0.50
0.00
0 2 4 6 8 10 12 14 16
Time (h)
Table 16–7 Dimensionless unit hydrograph for Alligator Creek at Clearwater, FL, used in example 16–2
Time Discharge Time Discharge Time Discharge Time Discharge Time Discharge
non-dim non-dim non-dim non-dim non-dim non-dim non-dim non-dim non-dim non-dim
0.0 0 2.0 0.736 4.0 0.199 6.0 0.04 8.0 0.007
0.2 0.445 2.2 0.663 4.2 0.172 6.2 0.034 8.2 0.006
0.4 0.729 2.4 0.592 4.4 0.147 6.4 0.029 8.4 0.005
0.6 0.895 2.6 0.525 4.6 0.126 6.6 0.024 8.6 0.004
0.8 0.977 2.8 0.463 4.8 0.107 6.8 0.021 8.8 0.0036
1.0 1 3.0 0.406 5.0 0.092 7.0 0.017 9.0 0.003
1.2 0.983 3.2 0.355 5.2 0.078 7.2 0.015 9.2 0.0025
1.4 0.938 3.4 0.308 5.4 0.066 7.4 0.012 9.4 0.002
1.6 0.878 3.6 0.267 5.6 0.056 7.6 0.01 9.6 0.001
1.8 0.809 3.8 0.231 5.8 0.048 7.8 0.009 9.8 0
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Time (non-dim)
450.0
350.0
300.0
Discharge (ft3/s)
250.0
200.0
150.0
100.0
50.0
0.0
-5 5 15 25 35 45 55
Time (h)
The dimensionless curvilinear unit hydrograph (fig. These relationships are useful in developing the peak
16–1) has 37.5 percent of the total volume in the rising rate equation for use with the dimensionless unit
side, which is represented by one unit of time and one hydrograph.
unit of discharge. This dimensionless unit hydrograph
also can be represented by an equivalent triangular Peak rate equation
hydrograph having the same units of time and dis-
charge, thus having the same percent of volume in the From figure 16A–1 the total volume under the triangu-
rising side of the triangle (fig. 16A–1). This allows the lar unit hydrograph is:
base of the triangle to be solved in relation to the time
to peak using the geometry of triangles. Solving for the q p Tp q p Tr qp
base length of the triangle, if one unit of time Tp equals Q=
2
+
2
=
2
(Tp + Tr )
[16A–1]
0.375 per cent of volume:
1.00 With Q in inches and T in hours, solve for peak rate qP
Tb = = 2.67 units of time
.375 in inches per hour:
Figure 16A–1 Dimensionless curvilinear unit hydrograph and equivalent triangular hydrograph
Excess rainfall
Lag
1.0
∆D
.9
Mass curve
of runoff
.8
.7
q/qp or Qa/Q
.6
qp
.5
Tc Point of inflection
.4
.3
.2
.1
0
0 1 2 3 4 5
Tp Tr
Tb
t/Tp
∆D
Tc + ∆D = 1.7 + 0.6 Tc [16A–12]
2
0.15 ∆D = 0.02Tc
∆D = 0.133 Tc [16A–13]
This appendix has standard dimensionless unit hydrographs developed using the gamma equation. For each peak
rate factor from 100 to 600, in increments of 50, a table has been prepared in the format for the NRCS WinTR–20
computer program (see tables 16B–1 through 16B–11). A plot of each dimensionless unit hydrograph is included
as figures 16B–1 through 16B–11. Refer to section 630.1604 for information on the development and use of these
standard tables.
1.0
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6
Time (non-dim)
1.0
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4
Time (non-dim)
1.0
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.25 0.5 .075 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 3.25 3.5 3.75 4 4.25 4.5 4.75 5 5.25 5.5 5.75 6
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.25 0.5 .075 1 1.25 1.5 1.75 2 2.25 2.5 2.75 3 3.25 3.5 3.75 4 4.25 4.5 4.75 5 5.25 5.5 5.75 6
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5
Time (non-dim)
1.0
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Time (non-dim)
1.0
0.9
Dim hyd
0.8
0.7
Discharge (non-dim)
0.6
0.5
0.4
0.3
0.2
0.1
0.0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Time (non-dim)