FTC Cafeteria

Transmission Heat Gain for Exposed Wall


Q1= Δt/RTOT = UA (to-ti)
Room/Exposed Wall Exposure
W
Office N
S

Canteen
Transmission Heat Gain for Exposed Wall
Q1= 1/RTOT ×UA (to-ti)
Room Room Exposure
SW
Dining Area NW
SE
NE
Kitchen SE
NW

Nursery
Transmission Heat Gain for Exposed Wall
Q1= 1/RTOT ×UA (to-ti)
Room Room Exposure
SW
Dining Area NW
SE
NE
Kitchen SE
NW
nsmission Heat Gain for Exposed Wall
Q1= Δt/RTOT = UA (to-ti)
1/RTot (W/m2- °K) A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
0.519 14.499 11 307.301
0.519 6.806 11 144.250 595.802
0.519 6.806 11 144.250

595.8015414258

Canteen
nsmission Heat Gain for Exposed Wall
Q1= 1/RTOT ×UA (to-ti)
1/RTot (W/m2- °K) A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
1.927 34.523 11 731.784031
1.927 26.663 11 565.175611 1759.054242
1.927 21.8 11 462.0946
1.927 34.182 11 724.555854
1.927 14.592 11 309.306624 1300.520738
1.927 12.58 11 266.65826

Nursery
nsmission Heat Gain for Exposed Wall
Q1= 1/RTOT ×UA (to-ti)
1/RTot (W/m2- °K) A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
1.927 34.523 11 731.784031
1.927 26.663 11 565.175611 1759.054242
1.927 21.8 11 462.0946
1.927 34.182 11 724.555854
1.927 14.592 11 309.306624 1300.520738
1.927 12.58 11 266.65826
Transmission Heat Gain for Exposed Wall (CSB1)
Q1= 1/RTOT ×UA (to-ti)
ROOM Room Exposure 1/RTot (W/m2- °K)
2.78
Registrar's Office 2.78
NE 2.78
2.78
RSTC
NE 2.78
2.78
Supply Office SE 2.78
NE 2.78
SE 2.78
Supply Storage Room 2.78
2.78
SW 2.78
Accounting Office 2.78
SE 2.78
North 2.78
Deans's Office
South 2.78
East 2.78
Conference Room West 2.78
South 2.78
East 2.78
Assistance Dean's Office
West 2.78
2.78
Registrar's Office 2.78
NE 2.78
2.78
RSTC
NE 2.78
SE 2.78
Supply Office
2.78
SE 2.78
Supply Storage Room
2.78
SE 2.78
Accounting Office 2.78
2.78
North 2.78
Deans's Office
South 2.78
East 2.78
Conference Room West 2.78
South 2.78
East 2.78
Assistance Dean's Office
West 2.78
n for Exposed Wall (CSB1)
OT
×UA (to-ti)
A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
11 0
11 0 514.0498
16.81 11 514.0498
11 0 394.482
12.9 11 394.482
11 0
4.57 11 139.7506 524.447
17.15 11 524.447
4.57 11 139.7506
11 0 0
11 0
22.2 11 678.876
11 0 277.3606
9.07 11 277.3606
11 0 0.000
11 0
11 0
11 0 0
11 0
11 0 0.000
11 0
11 0
11 0 322.9248
10.56 11 322.9248
11 0 332.710
10.88 11 332.7104
3.04 11 92.9632 92.963
11 0
11.04 11 337.6032 337.603
11 0
6.24 11 190.8192
11 0 0
11 0
11 0 0.000
11 0
11 0
11 0 0
11 0
11 0 0.000
11 0
Transmission Heat Gain for Exposed Wall (CSB
Q1= 1/RTOT ×UA (to-ti)
ROOM Room Exposure
SE
RSTC Office
SW
SW
Systematic Room (105)
NW
Lecture Room NW
Lecture Hall NW
Biology Department SE
Chemical Department SE
Parasitology Lab (206) SW
Organic and Biochem Lab (205) SW
NW
Analytical Chemistry Lab
SW
NW
Chemical Room
NE
General and Inorganic Chem Lab (203) NE
NE
Analytical Chem Lab (202)
SE
NE
Analytical Chem Lab (201)
SE

Transmission Heat Gain for Exposed Wall (CSB


Q1= 1/RTOT ×UA (to-ti)
ROOM Room Exposure
East
101 South
North
South
102
North
South
103
North
South
104
North
South
105 North
West
East
106 (Lecture Room)
West
South
107 North
West
South
108
NOrth
South
109
NOrth
South
110
North
East
111 South
North
East
Math Dept.
West
East
Phy. Dept
West
Transmission Heat Gain for Exposed Wall (CSB3)
Q1= 1/RTOT ×UA (to-ti)
1/RTot (W/m2- °K) A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
2.78 22.6 11 691.108
1324.114
2.78 20.7 11 633.006
2.78 19.35 11 591.723
1117.699
2.78 17.2 11 525.976
2.78 15 11 458.7 #REF!
2.78 28 11 856.24 #REF!
2.78 12.9 11 394.482 #REF!
2.78 12.9 11 394.482 394.482
2.78 17.5 11 535.15 535.150
2.78 19.35 11 591.723 #REF!
2.78 25.8 11 788.964
1051.952
2.78 8.6 11 262.988
2.78 8.6 11 262.988
546.251
2.78 9.263 11 283.26254
2.78 17.5 11 535.15 535.150
2.78 8.6 11 262.988
1050.423
2.78 25.75 11 787.435
2.78 26.1 11 798.138
1324.114
2.78 17.2 11 525.976

Transmission Heat Gain for Exposed Wall (CSB4)


Q1= 1/RTOT ×UA (to-ti)
1/RTot (W/m2- °K) A (m2) T difference (°C) Q Tht (wall) Q Tht (wall)/Room
2.78 30.3 11 926.574
2.78 22.49 11 687.7442 1978.2202
2.78 11.9 11 363.902
2.78 22.49 11 687.7442
1051.646
2.78 11.9 11 363.902
2.78 22.49 11 687.7442
1051.646
2.78 11.9 11 363.902
2.78 22.49 11 687.7442
1051.646
2.78 11.9 11 363.902
2.78 22.49 11 687.7442
2.78 11.9 11 363.902 1978.2202
2.78 30.3 11 926.574
2.78 28.9 11 883.762
1414.937
2.78 17.37 11 531.1746
2.78 11.9 11 363.902
2.78 22.49 11 687.7442 1978.2202
2.78 30.3 11 926.574
2.78 11.9 11 363.902
1051.646
2.78 22.49 11 687.7442
2.78 11.9 11 363.902
1051.646
2.78 22.49 11 687.7442
2.78 11.9 11 363.902
1051.646
2.78 22.49 11 687.7442
2.78 30.3 11 926.574
2.78 11.9 11 363.902 1978.2202
2.78 22.49 11 687.7442
2.78 5.055 11 154.5819
622.915
2.78 15.315 11 468.3327
2.78 5.055 11 154.5819
622.915
2.78 15.315 11 468.3327
Transmission Heat Gain for Exposed Roof (CSB3)
Room A (m2) 1/RTot (W/m2- °K)
Instrumentation Room 88 0.69
Parasitology Lab (206) 64 0.69
Analytical Chemistry Lab 84 0.69
Chemical Room 16 0.69
General and Inorganic Chem Lab (203) 64 0.69
Analytical Chem Lab (201) 96 0.69

Room A (m2) 1/RTot (W/m2- °K)


Computer Lab (205) 84 0.69
CSC Office 20 0.69
Computer Lab (202) 84 0.69
Computer Lab (201) 84 0.69
Faculty Room 96 0.69

Transmission Heat Gain for Exposed Roof (AMPHITHEATER)


Room A (m2) 1/RTot (W/m2- °K)
Office 1 17.1 0.69

Office 2 20.725 0.69

Vestibule 10.92 0.69


Storage Room 4.866 0.69
Pojector Room 12.125 0.69
Soundlock Room 11.625 0.69
Dressing Room 1 6.27 0.69
Dressing Room 2 7.054 0.69
Theater 1315.26 0.69
d Roof (CSB3)
T difference (°C) Q Tht (roof)
11 667.920
11 485.760
11 637.560
11 121.440
11 485.760
11 728.640

T difference (°C) Q Tht (roof)


11 637.560
11 151.800
11 637.560
11 637.560
11 728.640

f (AMPHITHEATER)
T difference (°C) Q Tht (roof)
11 129.789

11 157.303

11 82.883
11 36.933
11 92.029
11 88.234
11 47.589
11 53.540
11 9982.823
Sensible Heat due to Infiltration (CSB3)
Q = 1.23 Q (to-tI)
ROOM Height (m) Area (m2) Δt (°C) a
RSTC Office 3.5 72 11 0.2
Animal Histology Lab (105) 3.5 64 11 0.2
Systematic Room (105) 3.5 72 11 0.2
Lecture Room 3.5 96 11 0.2
Lecture Hall 3.5 160 11 0.2
Biology Department 3.5 48 11 0.2
Chemical Department 3.5 48 11 0.2
Instrumentation Room 3.5 88 11 0.2
Parasitology Lab (206) 3.5 64 11 0.2
Organic and Biochem Lab (205) 3.5 72 11 0.2
Chemical Room 3.5 16 11 0.2
General and Inorganic Chem Lab (203) 3.5 64 11 0.2
Analytical Chem Lab (202) 3.5 96 11 0.2

Sensible Heat due to Infiltration (CSB2)


Q = 1.23 Q (to-tI)
Room Height (m) Area (m2) Δt (°C) a
Canteen 3.5 96 11 0.2
Maintenance Department 3.5 28 11 0.2
B.U Multi-purpose Cooperative 3.5 28 11 0.2
Computer Lab (105) 3.5 56 11 0.2
Lecture Room (104) 3.5 56 11 0.2
Computer Lab (102) 3.5 56 11 0.2
Computer Lab (101) 3.5 56 11 0.2
Guidance Office 3.5 35 11 0.2
Computer Lab (206) 3.5 84 11 0.2
Computer Lab (205) 3.5 84 11 0.2
CSC Office 3.5 20 11 0.2
Scientia Office 3.5 20 11 0.2
Computer Lab (202) 3.5 70 11 0.2
Computer Lab (201) 3.5 56 11 0.2

Sensible Heat due to Infiltration (BUCN)


Q = 1.23 Q (to-tI)
ROOM Height (m) Area (m2) Δt (°C) a
Hospital Room 3.3 162 11 0.2
Nutrition Lab Room 3.3 63 11 0.2
Chemistry Room 3.3 63 11 0.2
112 3.3 63 11 0.2
111 3.3 63 11 0.2
Supply Office 3.3 63 11 0.2
Guidance Office 3.3 31.5 11 0.2
Graduate School Program Room 3.3 31.5 11 0.2
Faculty Office 3.3 126 11 0.2
Accreditation Room 3.3 31.5 11 0.2
Registrar's Office 3.3 31.5 11 0.2
Anatomy Room 3.3 63 11 0.2
Research Room 3.3 18.62 11 0.2
Store Room 3.3 6 11 0.2
Dean's Office 3.3 30 11 0.2
Work Area 3.3 20.9 11 0.2
Record Room 3.3 6.12 11 0.2
Cashier Office 3.3 25 11 0.2
CSC Office 3.3 11 0.2
Function Room 3.3 126 11 0.2
Library (Storage room) 3.3 11 0.2
Room 201 (Library) 3.3 198 11 0.2
Room 202 3.3 63 11 0.2
Room 203 3.3 63 11 0.2
Room 205 3.3 63 11 0.2
Room 206 3.3 63 11 0.2
Room 207 3.3 63 11 0.2
Room 208 3.3 63 11 0.2
Room 211 3.3 63 11 0.2
Room 212 3.3 63 11 0.2
Room 213 3.3 63 11 0.2
Room 214 3.3 54 11 0.2
Room 215 3.3 45 11 0.2

Sensible Heat due to Infiltration (CSB4)


Q = 1.23 Q (to-tI)
Room Height (m) Area (m2) Δt (°C) a
101 3.5 63 11 0.2
102 3.5 63 11 0.2
103 3.5 63 11 0.2
104 3.5 63 11 0.2
105 3.5 63 11 0.2
106 3.5 71.2 11 0.2
107 3.5 63 11 0.2
108 3.5 63 11 0.2
109 3.5 63 11 0.2
110 3.5 63 11 0.2
111 3.5 63 11 0.2
Physics Department 3.5 56 11 0.2
Math Department 3.5 72.36 11 0.2
201 3.5 63 11 0.2
202 3.5 63 11 0.2
203 3.5 63 11 0.2
204 3.5 63 11 0.2
205 3.5 63 11 0.2
207 3.5 63 11 0.2
208 3.5 63 11 0.2
2009 3.5 63 11 0.2
210 3.5 63 11 0.2
211 3.5 63 11 0.2
Lecture Room 3.5 71.8 11 0.2
Laboratory 3.5 102.4 11 0.2

Sensible Heat due to Infiltration (CSB1)


Q = 1.23 Q (to-tI)
Room Height (m) Area (m2) Δt (°C) a
Cashier's Office 3.5 12 11 0.2
Registrar's Office 3.5 20 11 0.2
Assistant Deans Office/Staff Area 3.5 28 11 0.2
Dean's Office 3.5 23 11 0.2
Conference Room 3.5 46 11 0.2
Accounting Office/Administrative Staff 3.5 55 11 0.2
Supply Office 3.5 10.5 11 0.2
Supply Storage Room 3.5 10 11 0.2
Office of the Director 3.5 11 0.2
Server Room (Small Room) 3.5 11 0.2
Training Room (Big Room) 3.5 11 0.2
3.5 11 0.2
ration (CSB3)
tI)
b c V Nc Q QIS
0.015 0.014 3.33 0.40395 0.028277 0.382581
0.015 0.014 3.33 0.40395 0.025135 0.340072
0.015 0.014 3.33 0.40395 0.028277 0.382581
0.015 0.014 3.33 0.40395 0.037702 0.510108
0.015 0.014 3.33 0.40395 0.062837 0.85018
0.015 0.014 3.33 0.40395 0.018851 0.255054
0.015 0.014 3.33 0.40395 0.018851 0.255054
0.015 0.014 3.33 0.40395 0.03456 0.467599
0.015 0.014 3.33 0.40395 0.025135 0.340072
0.015 0.014 3.33 0.40395 0.028277 0.382581
0.015 0.014 3.33 0.40395 0.006284 0.085018
0.015 0.014 3.33 0.40395 0.025135 0.340072
0.015 0.014 3.33 0.40395 0.037702 0.510108

ration (CSB2)
tI)
b c V Nc Q QIS
0.015 0.014 3.33 0.40395 0.037702 0.510108
0.015 0.014 3.33 0.40395 0.010996 0.148782
0.015 0.014 3.33 0.40395 0.010996 0.148782
0.015 0.014 3.33 0.40395 0.021993 0.297563
0.015 0.014 3.33 0.40395 0.021993 0.297563
0.015 0.014 3.33 0.40395 0.021993 0.297563
0.015 0.014 3.33 0.40395 0.021993 0.297563
0.015 0.014 3.33 0.40395 0.013746 0.185977
0.015 0.014 3.33 0.40395 0.032989 0.446345
0.015 0.014 3.33 0.40395 0.032989 0.446345
0.015 0.014 3.33 0.40395 0.007855 0.106273
0.015 0.014 3.33 0.40395 0.007855 0.106273
0.015 0.014 3.33 0.40395 0.027491 0.371954
0.015 0.014 3.33 0.40395 0.021993 0.297563

ation (BUCN)
I
)
b c V Nc Q QIS
0.015 0.014 3.33 0.40395 0.0599866 0.8116184
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0116641 0.1578147
0.015 0.014 3.33 0.40395 0.0116641 0.1578147
0.015 0.014 3.33 0.40395 0.0466562 0.6312587
0.015 0.014 3.33 0.40395 0.0116641 0.1578147
0.015 0.014 3.33 0.40395 0.0116641 0.1578147
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0068948 0.093286
0.015 0.014 3.33 0.40395 0.0022217 0.0300599
0.015 0.014 3.33 0.40395 0.0111086 0.1502997
0.015 0.014 3.33 0.40395 0.007739 0.1047088
0.015 0.014 3.33 0.40395 0.0022662 0.0306611
0.015 0.014 3.33 0.40395 0.0092572 0.1252497
0.015 0.014 3.33 0.40395 0 0
0.015 0.014 3.33 0.40395 0.0466562 0.6312587
0.015 0.014 3.33 0.40395 0 0
0.015 0.014 3.33 0.40395 0.0733169 0.991978
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.003014
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0233281 0.3156294
0.015 0.014 3.33 0.40395 0.0199955 0.2705395
0.015 0.014 3.33 0.40395 0.0166629 0.2254495

ration (CSB4)
tI)
b c V Nc Q QIS
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.027962 0.37833
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.021993 0.297563
0.015 0.014 3.33 0.40395 0.028418 0.384494
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.024742 0.334758
0.015 0.014 3.33 0.40395 0.028198 0.381518
0.015 0.014 3.33 0.40395 0.040215 0.544115

ration (CSB1)
tI)
b c V Nc Q QIS
0.015 0.014 3.33 0.40395 0.004713 0.063764
0.015 0.014 3.33 0.40395 0.007855 0.106273
0.015 0.014 3.33 0.40395 0.010996 0.148782
0.015 0.014 3.33 0.40395 0.009033 0.122213
0.015 0.014 3.33 0.40395 0.018066 0.244427
0.015 0.014 3.33 0.40395 0.0216 0.292249
0.015 0.014 3.33 0.40395 0.004124 0.055793
0.015 0.014 3.33 0.40395 0.003927 0.053136
0.015 0.014 3.33 0.40395 0 0
0.015 0.014 3.33 0.40395 0 0
0.015 0.014 3.33 0.40395 0 0
0.015 0.014 3.33 0.40395 0 0
Latent Heat Load due to Infiltration (CSB3)
Q = 3000 Q (Wo-Wi)
ROOM Height (m) Area (m2) Wo Wi ΔW
RSTC Office 3.5 72 0.0158 0.01 0.0058
Animal Histology Lab (105) 3.5 64 0.0158 0.01 0.0058
Systematic Room (105) 3.5 72 0.0158 0.01 0.0058
Lecture Room 3.5 96 0.0158 0.01 0.0058
Lecture Hall 3.5 160 0.0158 0.01 0.0058
Biology Department 3.5 48 0.0158 0.01 0.0058
Chemical Department 3.5 48 0.0158 0.01 0.0058
Instrumentation Room 3.5 88 0.0158 0.01 0.0058
Parasitology Lab (206) 3.5 64 0.0158 0.01 0.0058
Organic and Biochem Lab (205) 3.5 72 0.0158 0.01 0.0058
Chemical Room 3.5 16 0.0158 0.01 0.0058
General and Inorganic Chem Lab (203) 3.5 64 0.0158 0.01 0.0058
Analytical Chem Lab (202) 3.5 96 0.0158 0.01 0.0058

Latent Heat Load due to Infiltration (CSB2)


Q = 3000 Q (Wo-Wi)
Room Height (m) Area (m2) Wo Wi ΔW
Canteen 3.5 96 0.0158 0.01 0.0058
Maintenance Department 3.5 28 0.0158 0.01 0.0058
B.U Multi-purpose Cooperative 3.5 28 0.0158 0.01 0.0058
Computer Lab (105) 3.5 56 0.0158 0.01 0.0058
Lecture Room (104) 3.5 56 0.0158 0.01 0.0058
Computer Lab (102) 3.5 56 0.0158 0.01 0.0058
Computer Lab (101) 3.5 56 0.0158 0.01 0.0058
Guidance Office 3.5 35 0.0158 0.01 0.0058
Computer Lab (206) 3.5 84 0.0158 0.01 0.0058
Computer Lab (205) 3.5 84 0.0158 0.01 0.0058
CSC Office 3.5 20 0.0158 0.01 0.0058
Scientia Office 3.5 20 0.0158 0.01 0.0058
Computer Lab (202) 3.5 70 0.0158 0.01 0.0058
Computer Lab (201) 3.5 56 0.0158 0.01 0.0058

Latent Heat Load due to Infiltration (BUCN)


Q = 3000 Q (Wo-Wi)
ROOM Height (m) Area (m2) Wo Wi ΔW
Hospital Room 3.3 162 0.0158 0.01 0.0058
Nutrition Lab Room 3.3 63 0.0158 0.01 0.0058
Chemistry Room 3.3 63 0.0158 0.01 0.0058
112 3.3 63 0.0158 0.01 0.0058
111 3.3 63 0.0158 0.01 0.0058
Supply Office 3.3 63 0.0158 0.01 0.0058
Guidance Office 3.3 31.5 0.0158 0.01 0.0058
Graduate School Program Room 3.3 31.5 0.0158 0.01 0.0058
Faculty Office 3.3 126 0.0158 0.01 0.0058
Accreditation Room 3.3 31.5 0.0158 0.01 0.0058
Registrar's Office 3.3 31.5 0.0158 0.01 0.0058
Anatomy Room 3.3 63 0.0158 0.01 0.0058
Research Room 3.3 18.62 0.0158 0.01 0.0058
Store Room 3.3 6 0.0158 0.01 0.0058
Dean's Office 3.3 30 0.0158 0.01 0.0058
Work Area 3.3 20.9 0.0158 0.01 0.0058
Record Room 3.3 6.12 0.0158 0.01 0.0058
Cashier Office 3.3 25 0.0158 0.01 0.0058
CSC Office 3.3 0.0158 0.01 0.0058
Function Room 3.3 126 0.0158 0.01 0.0058
Library (Storage room) 3.3 0.0158 0.01 0.0058
Room 201 (Library) 3.3 198 0.0158 0.01 0.0058
Room 202 3.3 63 0.0158 0.01 0.0058
Room 203 3.3 63 0.0158 0.01 0.0058
Room 205 3.3 63 0.0158 0.01 0.0058
Room 206 3.3 63 0.0158 0.01 0.0058
Room 207 3.3 63 0.0158 0.01 0.0058
Room 208 3.3 63 0.0158 0.01 0.0058
Room 211 3.3 63 0.0158 0.01 0.0058
Room 212 3.3 63 0.0158 0.01 0.0058
Room 213 3.3 63 0.0158 0.01 0.0058
Room 214 3.3 54 0.0158 0.01 0.0058
Room 215 3.3 45 0.0158 0.01 0.0058

Latent Heat Load due to Infiltration (CSB4)


Q = 3000 Q (Wo-Wi)
Room Height (m) Area (m2) Wo Wi ΔW
101 3.5 63 0.0158 0.01 0.0058
102 3.5 63 0.0158 0.01 0.0058
103 3.5 63 0.0158 0.01 0.0058
104 3.5 63 0.0158 0.01 0.0058
105 3.5 63 0.0158 0.01 0.0058
106 3.5 71.2 0.0158 0.01 0.0058
107 3.5 63 0.0158 0.01 0.0058
108 3.5 63 0.0158 0.01 0.0058
109 3.5 63 0.0158 0.01 0.0058
110 3.5 63 0.0158 0.01 0.0058
111 3.5 63 0.0158 0.01 0.0058
Physics Department 3.5 56 0.0158 0.01 0.0058
Math Department 3.5 72.36 0.0158 0.01 0.0058
201 3.5 63 0.0158 0.01 0.0058
202 3.5 63 0.0158 0.01 0.0058
203 3.5 63 0.0158 0.01 0.0058
204 3.5 63 0.0158 0.01 0.0058
205 3.5 63 0.0158 0.01 0.0058
207 3.5 63 0.0158 0.01 0.0058
208 3.5 63 0.0158 0.01 0.0058
2009 3.5 63 0.0158 0.01 0.0058
210 3.5 63 0.0158 0.01 0.0058
211 3.5 63 0.0158 0.01 0.0058
Lecture Room 3.5 71.8 0.0158 0.01 0.0058
Lab 3.5 102.4 0.0158 0.01 0.0058

Latent Heat Load due to Infiltration (CSB1)


Q = 3000 Q (Wo-Wi)
Room Height (m) Area (m2) Wo Wi ΔW
Cashier's Office 3.5 12 0.0158 0.01 0.0058
Registrar's Office 3.5 20 0.0158 0.01 0.0058
Assistant Deans Office/Staff Area 3.5 28 0.0158 0.01 0.0058
Dean's Office 3.5 23 0.0158 0.01 0.0058
Conference Room 3.5 46 0.0158 0.01 0.0058
Accounting Office/Administrative Staff/Administra 3.5 55 0.0158 0.01 0.0058
Supply Office 3.5 10.5 0.0158 0.01 0.0058
Supply Storage Room 3.5 10 0.0158 0.01 0.0058
Office of the Director 3.5 0.0158 0.01 0.0058
Server Room (Small Room) 3.5 0.0158 0.01 0.0058
Training Room (Big Room) 3.5 0.0158 0.01 0.0058
3.5 0.0158 0.01 0.0058
nfiltration (CSB3)
Wo-Wi)
a b c V Nc Q Qil
0.2 0.015 0.014 3.33 0.40395 0.028277 0.492011
0.2 0.015 0.014 3.33 0.40395 0.025135 0.437343
0.2 0.015 0.014 3.33 0.40395 0.028277 0.492011
0.2 0.015 0.014 3.33 0.40395 0.037702 0.656015
0.2 0.015 0.014 3.33 0.40395 0.062837 1.093358
0.2 0.015 0.014 3.33 0.40395 0.018851 0.328007
0.2 0.015 0.014 3.33 0.40395 0.018851 0.328007
0.2 0.015 0.014 3.33 0.40395 0.03456 0.601347
0.2 0.015 0.014 3.33 0.40395 0.025135 0.437343
0.2 0.015 0.014 3.33 0.40395 0.028277 0.492011
0.2 0.015 0.014 3.33 0.40395 0.006284 0.109336
0.2 0.015 0.014 3.33 0.40395 0.025135 0.437343
0.2 0.015 0.014 3.33 0.40395 0.037702 0.656015

nfiltration (CSB2)
Wo-Wi)
a b c V Nc Q Qil
0.2 0.015 0.014 3.33 0.40395 0.037702 0.656015
0.2 0.015 0.014 3.33 0.40395 0.010996 0.191338
0.2 0.015 0.014 3.33 0.40395 0.010996 0.191338
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675
0.2 0.015 0.014 3.33 0.40395 0.013746 0.239172
0.2 0.015 0.014 3.33 0.40395 0.032989 0.574013
0.2 0.015 0.014 3.33 0.40395 0.032989 0.574013
0.2 0.015 0.014 3.33 0.40395 0.007855 0.13667
0.2 0.015 0.014 3.33 0.40395 0.007855 0.13667
0.2 0.015 0.014 3.33 0.40395 0.027491 0.478344
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675

nfiltration (BUCN)
Wo-Wi)
a b c V Nc Q Qil
0.2 0.015 0.014 3.33 0.40395 0.059987 1.043766
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.011664 0.202955
0.2 0.015 0.014 3.33 0.40395 0.011664 0.202955
0.2 0.015 0.014 3.33 0.40395 0.046656 0.811818
0.2 0.015 0.014 3.33 0.40395 0.011664 0.202955
0.2 0.015 0.014 3.33 0.40395 0.011664 0.202955
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.006895 0.119969
0.2 0.015 0.014 3.33 0.40395 0.002222 0.038658
0.2 0.015 0.014 3.33 0.40395 0.011109 0.19329
0.2 0.015 0.014 3.33 0.40395 0.007739 0.134659
0.2 0.015 0.014 3.33 0.40395 0.002266 0.039431
0.2 0.015 0.014 3.33 0.40395 0.009257 0.161075
0.2 0.015 0.014 3.33 0.40395 0 0
0.2 0.015 0.014 3.33 0.40395 0.046656 0.811818
0.2 0.015 0.014 3.33 0.40395 0 0
0.2 0.015 0.014 3.33 0.40395 0.073317 1.275714
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.023328 0.405909
0.2 0.015 0.014 3.33 0.40395 0.019996 0.347922
0.2 0.015 0.014 3.33 0.40395 0.016663 0.289935

nfiltration (CSB4)
Wo-Wi)
a b c V Nc Q Qil
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.027962 0.486544
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.021993 0.382675
0.2 0.015 0.014 3.33 0.40395 0.028418 0.494471
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.024742 0.43051
0.2 0.015 0.014 3.33 0.40395 0.028198 0.490644
0.2 0.015 0.014 3.33 0.40395 0.040215 0.699749

nfiltration (CSB1)
Wo-Wi)
a b c V Nc Q Qil
0.2 0.015 0.014 3.33 0.40395 0.004713 0.082002
0.2 0.015 0.014 3.33 0.40395 0.007855 0.13667
0.2 0.015 0.014 3.33 0.40395 0.010996 0.191338
0.2 0.015 0.014 3.33 0.40395 0.009033 0.15717
0.2 0.015 0.014 3.33 0.40395 0.018066 0.31434
0.2 0.015 0.014 3.33 0.40395 0.0216 0.375842
0.2 0.015 0.014 3.33 0.40395 0.004124 0.071752
0.2 0.015 0.014 3.33 0.40395 0.003927 0.068335
0.2 0.015 0.014 3.33 0.40395 0 0
0.2 0.015 0.014 3.33 0.40395 0 0
0.2 0.015 0.014 3.33 0.40395 0 0
0.2 0.015 0.014 3.33 0.40395 0 0
INTERNAL HEAT GAIN FROM LAMPS (CSB2)

Room QTY W Fu Fb CLF


Canteen 18 18 1 ---- 0.96
Maintenance Department 18 18 1 ---- 0.96
B.U Multi-purpose Cooperative 18 18 1 ---- 0.96
Computer Lab (105) 8 18 1 ---- 0.96
Lecture Room (104) 8 18 1 ---- 0.96
8 18 1 0.96
Computer Lab (102)
3 36 1 1.2 0.96
8 18 1 ---- 0.96
Computer Lab (101)
3 36 1 1.2 0.96
Guidance Office 5 18 1 ---- 0.96
Computer Lab (206) 20 18 1 ---- 0.96
Computer Lab (205) 20 18 1 ---- 0.96
CSC Office 2 18 1 ---- 0.96
Scientia Office 5 18 1 ---- 0.96
Computer Lab (202) 8 18 1 ---- 0.96
8 18 1 ---- 0.96
Computer Lab (201)
3 36 1 1.2 0.96

INTERNAL HEAT GAIN FROM LAMPS (CSB3)


ROOM QTY W Fu Fb CLF
9 18 1 ---- 0.96
RSTC Office
1 36 1 1.2 0.96
4 18 1 ---- 0.96
Animal Histology Lab (106)
4 36 1 1.2 0.96
8 18 1 ---- 0.96
Systematic Room (105)
8 36 1 1.2 0.96
Lecture Room 9 18 1 ---- 0.96
9 18 1 ---- 0.96
Lecture Hall
3 36 1 1.2 0.96
3 18 1 ---- 0.96
Biology Department
1 36 1 1.2 0.96
3 18 1 ---- 0.96
Chemical Department
1 36 1 1.2 0.96
Instrumentation Room 14 18 1 ---- 0.96
5 18 1 ---- 0.96
Parasitology Lab (206)
2 36 1 1.2 0.96
2 18 1 ---- 0.96
Organic and Biochem Lab (205)
8 36 1 1.2 0.96
Chemical Room 5 18 1 ---- 0.96
7 18 1 ---- 0.96
General and Inorganic Chem Lab (203)
1 36 1 1.2 0.96
2 18 1 ---- 0.96
Analytical Chem Lab (202)
8 36 1 1.2 0.96

INTERNAL HEAT GAIN FROM LAMPS (CN)


ROOM QTY W Fu Fb CLF
4 18 1 ---- 0.96
Hospital Room
52 36 1 1.2 0.96
Nutrition Lab Room 4 18 1 ---- 0.96
Chemistry Room 4 18 1 ---- 0.96
112 4 18 1 ---- 0.96
111 4 18 1 ---- 0.96
Supply Office 3 18 1 ---- 0.96
Guidance Office 3 18 1 ---- 0.96
Graduate School Program Room 6 18 1 ---- 0.96
Faculty Office 30 18 1 ---- 0.96
Accreditation Room 1 36 1 1.2 0.96
1 18 1 ---- 0.96
Registrar's Office
1 36 1 1.2 0.96
Anatomy Room 2 18 1 ---- 0.96
Research Room 6 36 1 1.2 0.96
Store Room 7 18 1 ---- 0.96
Dean's Office 7 18 1 ---- 0.96
Work Area 7 18 1 ---- 0.96
Record Room 7 18 1 ---- 0.96
Cashier Office 7 18 1 ---- 0.96
CSC Office 5 18 1 ---- 0.96
Function Room 5 18 1 ---- 0.96
Library (Storage room) 7 18 1 ---- 0.96
Room 201 (Library) 5 18 1 ---- 0.96
Room 202 5 18 1 ---- 0.96
Room 203 7 18 1 ---- 0.96
Room 205 7 18 1 ---- 0.96
Room 206 7 18 1 ---- 0.96
Room 207 7 18 1 ---- 0.96
Room 208 7 18 1 ---- 0.96
Room 211 7 18 1 ---- 0.96
Room 212 7 18 1 ---- 0.96
Room 213 7 18 1 ---- 0.96
Room 214 7 18 1 ---- 0.96
Room 215 7 18 1 ---- 0.96
INTERNAL HEAT GAIN FROM LAMPS (CSB4)
Room QTY W Fu Fb CLF
CS FUNCTION HALL 12 18 1 ---- 0.96
Dean's Office 5 18 1 ---- 0.96
Main Room 4 18 1 ---- 0.96
Meeting Room 5 18 1 ---- 0.96
204 6 18 1 ---- 0.96
205 7 18 1 ---- 0.96
206 4 18 1 ---- 0.96
Accounting Office 5 18 1 ---- 0.96
Budget Office 4 18 1 ---- 0.96
Administrative Office 5 18 1 ---- 0.96
AVR 10 18 1 ---- 0.96
Math Department 5 18 1 ---- 0.96
Physics Department 5 18 1 ---- 0.96
Physics Department, CR 4 18 1 ---- 0.96

INTERNAL HEAT GAIN FROM LAMPS (CSB1)


Room QTY W Fu Fb CLF
Cashier's Office 5 18 1 ---- 0.96
Registrar's Office 6 18 1 ---- 0.96
Assistant Deans Office/Staff Area 5 18 1 ---- 0.96
Dean's Office 6 18 1 ---- 0.96
Conference Room 4 18 1 ---- 0.96
Accounting Office/Administrative Staff 6 18 1 ---- 0.96
Supply Office 7 18 1 ---- 0.96
Supply Storage Room 6 18 1 ---- 0.96
Conference Room 7 18 1 ---- 0.96
Office of the Director 5 18 1 ---- 0.96
Server Room (Small Room) 6 18 1 ---- 0.96
Training Room (Big Room) 8 18 1 ---- 0.96
OCCUPANT SENSIBLE COOLING LOAD (C
QL QL/room Room
311.04 311.04
Canteen
311.04 311.04
311.04 311.04 Maintenance Department
138.24 138.24 B.U Multi-purpose Cooperative
138.24 138.24 Computer Lab (105)
138.24 138.24
103.68 103.68 Lecture Room (104)
138.24 138.24
103.68 103.68 Computer Lab (102)
86.4 86.4
345.6 345.6 Computer Lab (101)
345.6 345.6
34.56 34.56 Guidance Office
86.4 86.4 Computer Lab (206)
138.24 138.24
138.24 138.24 Computer Lab (205)
103.68 103.24
CSC Office
Scientia Office

Computer Lab (202)

Computer Lab (201)

Faculty
Coordinator
QL QL/room
155.52
196.992
41.472
69.12 OCCUPANT SENSIBLE COOLING LOAD (C
207.36
138.24 ROOM
138.24 RSTC Office
470.016
331.776
Animal Histology Lab (106)
155.52
311.04
155.52
Systematic Room (105)
124.416
176.256
51.84
Lecture Room
34.56
86.4
51.84 Lecture Hall
41.472 Biology Department
283.392
241.92 Chemical Department
86.4 Instrumentation Room
169.344
82.944
Parasitology Lab (206)
34.56
311.04
276.48
Organic and Biochem Lab (205)
Organic and Biochem Lab (205)
86.4
207.36
120.96 Chemical Room
34.56
69.12 General and Inorganic Chem Lab (203)
34.56
331.776 331.776
Analytical Chem Lab (202)

OCCUPANT SENSIBLE COOLING LOAD


QL QL/room ROOM
69.12
2225.664 Hospital Room
2156.544
69.12 69.12 Nutrition Lab Room
69.12 69.12
69.12 69.12
Chemistry Room
69.12 69.12
51.84 51.84
112
51.84 51.84
103.68 103.68
111
518.4 518.4
34.56 518.4 Supply Office
17.28 Guidance Office
58.752
41.472 Graduate School Program Room
34.56 34.56 Faculty Office
207.36 207.36 Accreditation Room
120.96 120.96 Registrar's Office
120.96 120.96
Anatomy Room
120.96 120.96
120.96 120.96 Research Room
120.96 120.96 Store Room
86.4 86.4 Dean's Office
86.4 518.4 Work Area
120.96 518.4 Record Room
86.4 518.4 Cashier Office
86.4 691.2 CSC Office
120.96 120.96 Function Room
120.96 120.96 Library (Storage room)
120.96 120.96 Room 201 (Library)
120.96 120.96 Room 202
120.96 120.96 Room 203
120.96 120.96 Room 205
120.96 120.96 Room 206
120.96 120.96 Room 207
120.96 120.96 Room 208
120.96 120.96 Room 211
Room 212
Room 213
Room 214
Room 215

QL QL/room
207.36 207.36 OCCUPANT SENSIBLE COOLING LOAD (C
86.4 86.4 Room
69.12 69.12 101
86.4 86.4 102
103.68 103.68 103
120.96 120.96 104
69.12 69.12 105
86.4 86.4 106
69.12 69.12 107
86.4 86.4 108
172.8 172.8 109
86.4 89.4 110
86.4 86.4 111
69.12 69.12 Physics Department
201
202
203
204
205
207
QL QL/room 208
86.4 2009
103.68 210
86.4 211
103.68 Lecture Room
69.12 Laboratory
103.68
120.96
103.68 OCCUPANT SENSIBLE COOLING LOAD (CSB1)
120.96 Room
86.4 Cashier's Office
103.68 Registrar's Office
138.24 Assistant Deans Office/Staff Area
Dean's Office
Conference Room
Accounting Office/Administrative Staff
Supply Office
Supply Storage Room
Conference Room
Office of the Director
Server Room (Small Room)
Training Room (Big Room)
ANT SENSIBLE COOLING LOAD (CSB2)
(G/P)s Np (CLF)p Qps Qps/room
75 60 2745
0.61 3083.55
92.5 6 338.55
82.5 2 0.72 118.8 118.8
82.5 4 0.72 237.6 653.4
100 26 1586
0.61 1639.375
87.5 1 53.375
100 30 1830
0.61 1883.38
87.5 1 53.375
100 30 1830
0.61 1883.38
87.5 1 53.375
100 30 1830
0.61 1883.38
87.5 1 53.375
82.5 4 0.72 237.6 237.6
100 26 1586
0.61 1639.375
87.5 1 53.375
100 26 1586
0.61 1639.38
87.5 1 53.375
82.5 11 0.72 653.4 653.4
82.5 11 0.72 653.4 653.4
60 26 951.6
0.61 1014.6
87.5 1 63
100 26 1586
0.61 1639.38
87.5 1 53.375
82.5 10 0.72 594 594
82.5 4 0.72 237.6 237.6

ANT SENSIBLE COOLING LOAD (CSB3)


(G/P)s Np (CLF)p Qps Qps/room
82.5 5 0.72 297 297
60 50 1830
0.61 1883.375
87.5 1 53.375
60 50 1830
0.61 1883.375
87.5 1 53.375
60 50 1830
0.61 1883.375
87.5 1 53.375
60 60 0.61 2160 2160
82.5 10 0.72 594 594
82.5 16 0.72 950.4 950.4
82.5 2 0.61 100.65 100.65
60 30 1098
0.61 1151.375
87.5 1 53.375
60 50 1830
0.61 1883.375
0.61 1883.375
87.5 1 53.375
82.5 16 0.61 805.2 805.2
60 50 1830
0.61 1883.375
87.5 1 53.375
60 50 1830
0.61 1883.375
87.5 1 53.375

PANT SENSIBLE COOLING LOAD (CN)


(G/P)s Np (CLF)p Qps Qps/room
60 50 1830
0.61 1883.375
87.5 1 53.375
60 40 1464
0.61 1517.375
87.5 1 53.375
60 45 1647
0.61 1700.375
87.5 1 53.375
60 50 2160
0.72 2223
87.5 1 63
60 50 2160
0.72 2223
87.5 1 63
82.5 4 0.72 237.6 237.6
82.5 4 0.72 237.6 237.6
82.5 2 0.72 118.8 118.8
82.5 35 0.72 2079 2079
82.5 5 0.72 297 297
82.5 2 0.72 118.8 118.8
60 40 1464
0.61 1517.375
87.5 1 53.375
82.5 2 0.72 118.8 118.8
82.5 2 0.72 118.8 118.8
82.5 1 0.72 59.4 59.4
82.5 1 0.72 59.4 59.4
82.5 1 0.72 59.4 59.4
82.5 2 0.72 118.8 118.8
82.5 4 0.72 237.6 118.8
60 25 0.61 915 915
ANT SENSIBLE COOLING LOAD (CSB4)
(G/P)s Np (CLF)p Qps Qps/room

OCCUPANT SENSIBLE COOLING LOAD (CSB1) 211

(G/P)s Np (CLF)p Qps Qps/room


OCCUPANT LATENT COOLING LOAD (CSB2)
ROOM (G/P)L Np QPL QPL/room
95 60 5700
Canteen 6255
92.5 6 555
Maintenance Department 82.5 2 165 165
B.U Multi-purpose Cooperative 82.5 4 330 330
40 26 1040
Computer Lab (105) 1127.5
87.5 1 87.5
40 30 1200
Lecture Room (104) 1287.5
87.5 1 87.5
40 30 1200
Computer Lab (102) 1287.5
87.5 1 87.5
40 30 1200
Computer Lab (101) 1287.5
87.5 1 87.5
Guidance Office 67.5 4 270 270
40 26 1040
Computer Lab (206) 1127.5
87.5 1 87.5
40 26 1040
Computer Lab (205) 1127.5
87.5 1 87.5
CSC Office 67.5 20 1350 1350
Scientia Office 67.5 20 1350 1350
40 26 1040
Computer Lab (202) 1127.5
87.5 1 87.5
40 26 1040
Computer Lab (201) 1127.5
87.5 1 87.5
Faculty 82.5 10 825 825
Coordinator 82.5 4 330 330

OCCUPANT LATENT COOLING LOAD (CSB3)


ROOM (G/P)L Np QPL QPL/room
RSTC Office 67.5 5 337.5 337.5
40 50 2000
Animal Histology Lab (106) 2087.5
87.5 1 87.5
40 50 2000
Systematic Room (105) 2087.5
87.5 1 87.5
40 50 2000
Lecture Room 2087.5
87.5 1 87.5
Lecture Hall 40 60 2400 2400
Biology Department 67.5 10 675 675
Chemical Department 67.5 16 1080 1080
Instrumentation Room 67.5 2 135 135
40 30 1200
Parasitology Lab (206) 1287.5
87.5 1 87.5
40 50 2000
Organic and Biochem Lab (205) 2087.5
87.5 1 87.5
Chemical Room 67.5 16 1080 1080
40 50 2000
General and Inorganic Chem Lab (203) 2087.5
87.5 1 87.5
40 50 2000
Analytical Chem Lab (202) 2087.5
87.5 1 87.5

OCCUPANT LATENT COOLING LOAD (CN)


ROOM (G/P)L Np QPL SSS
Hospital Room 40 50 2000 2087.5
87.5 1 87.5
Nutrition Lab Room 40 40 1600 1687.5
87.5 1 87.5
Chemistry Room 40 45 1800 1887.5
87.5 1 87.5
112 40 50 2000 2087.5
87.5 1 87.5
111 40 50 2000 2087.5
87.5 1 87.5
Supply Office 67.5 4 270 270
Guidance Office 69.75 4 279 279
Graduate School Program Room 67.5 2 135 135
Faculty Office 67.5 2 135 135
Accreditation Room 67.5 5 337.5 337.5
Registrar's Office 67.5 2 135 135
Anatomy Room 40 40 1600 1687.5
87.5 1 87.5
Research Room 67.5 2 135 135
Store Room 67.5 2 135 135
Dean's Office 67.5 1 202.5 202.5
Work Area 67.5 1 202.5 202.5
Record Room 67.5 1 202.5 202.5
Cashier Office 67.5 2 135 135
CSC Office 67.5 2 135 135
Function Room 40 25 1000 1000
Library (Storage room)
Room 201 (Library)
Room 202
Room 203
Room 205
Room 206
Room 207
Room 208
Room 211
Room 212
Room 213
Room 214
Room 215

OCCUPANT LATENT COOLING LOAD (CSB4)


Room (G/P)L Np QPL QPL/room
101
102
103
104
105
106
107
108
109
110
111
Physics Department
Math Department
201
202
203
204
205
207
208
2009
210

Lecture Room
Laboratory

OCCUPANT LATENT COOLING LOAD (CSB1)


s (G/P)L Np QPL QPL/room
Cashier's Office
Registrar's Office
Assistant Deans Office/Staff Area
Dean's Office
Conference Room
Accounting Office/Administrative Staff
Supply Office
Supply Storage Room
Conference Room
Office of the Director
Server Room (Small Room)
Training Room (Big Room)
Sensible Heat Gain For Window (CN)
ROOM Window Facing Awindow(m2) Utot(W/m2 K) (to-ti)
SE 15.75 5.9 11
Hospital Room NE 11.25 5.9 11
NW 0.34 5.9 11
SE 9 5.9 11
Nutrition Lab
NW 2.18 5.9 11
SE 9 5.9 11
Chemistry Room
NW 2.18 5.9 11
SE 9 5.9 11
112
NW 2.18 5.9 11
SE 9 5.9 11
111
NW 2.18 5.9 11
SE 9 5.9 11
Supply Office
NW 2.18 5.9 11
NW 4.5 5.9 11
Guidance Office
SE 1.09 5.9 11
NW 4.5 5.9 11
Graduate School Program Room
SE 1.09 5.9 11
NW 18 5.9 11
Faculty Office
SE 4.36 5.9 11
NW 4.5 5.9 11
Accreditation Room
SE 1.09 5.9 11
NW 4.5 5.9 11
Registrar's Office
SE 1.09 5.9 11
NW 9 5.9 11
Anatomy Room
SE 2.18 5.9 11
Research Office SW 5.76 5.9 11
Store Room
Dean's Office NE 8.96 5.9 11
Work Area NE 8.96 5.9 11
Record Room NE 2.56 5.9 11
Cashier's Office NE 5.28 5.9 11
Sensible Heat Gain For Window Glass- CSB2
QTht QTht/Room Room Window Facing Awindow(m2)
1022.175 Canteen NW 2.7
741.125 1785.366 Maitenance SW 5.76
22.066 Cooperative SW 5.76
584.1 Computer Lab (105) SW 11.52
725.582
141.482 Lecture Lab (104) SW 11.52
584.1 Coordinator NE 11.52
725.582
141.482 Computer Lab (102) NE 11.52
584.1 Computer Lab (101) NE 11.52
725.582
141.482 Guidance SW 5.76
584.1 Computer Lab (206) SW 17.28
725.582
141.482 Computer Lab (205) SW 11.52
584.1 CSC Office NW 4
725.582
141.482 Scientia Office NW 4
292.05 Computer Lab (202) NE 11.52
362.791
70.741 Computer Lab (201) NE 11.52
292.05
362.791
70.741
1168.2
1451.164
282.964
292.05
362.791
70.741
292.05
362.791
70.741
584.1
725.582
141.482
373.824 24261.1776

581.504 581.504
581.504 581.504
166.144 166.144
342.672 342.672
For Window Glass- CSB2 Sensible Heat Gain F
Utot(W/m K)
2
(to-ti) QTht QTht/Room Room
5.9 11 175.23 175.23
RSTC Office
5.9 11 373.824 373.824
5.9 11 373.824 373.824 Animal Histology(106)
5.9 11 747.648 747.648
Systematic(105)
5.9 11 747.648 747.648
5.9 11 747.648 747.648
Lecture Room(104)
5.9 11 747.648 747.648
5.9 11 747.648 747.648
Lecture Hall
5.9 11 373.824 373.824
5.9 11 1121.472 1121.472
Biology Department
5.9 11 747.648 747.648
5.9 11 259.6 259.6 Chemical Department
5.9 11 259.6 259.6
Insrumentation Room
5.9 11 747.648 747.648
5.9 11 747.648 747.648 Parasitology Lab(206)
Organic Biochem Lab(205)

Analytical Lab(204)

Chemical Room

General Organic Chem Lab(203)


Analytical Chem Lab(202)

Analytical Chem Lab(202)


Sensible Heat Gain For Window Glass- CSB3
Window Facing Awindow(m ) Utot(W/m K) QTht QTht/Room
2 2
(to-ti)
SE 5.4 5.9 11 350.46
1051.38
SW 10.8 5.9 11 700.92
SW 10.5 5.9 11 681.45 681.45
SW 12.15 5.9 11 788.535
1489.455
NW 10.8 5.9 11 700.92
NW 16.2 5.9 11 1051.38
1401.84
SW 5.4 5.9 11 350.46
SE 10.8 5.9 11 700.92
2083.29
NE 21.3 5.9 11 1382.37
NE 5.4 5.9 11 350.46
876.15
SE 8.1 5.9 11 525.69
SE 8.1 5.9 11 525.69 525.69
SE 16.2 5.9 11 1051.38
2190.375
SW 17.55 5.9 11 1138.995
SW 10.5 5.9 11 681.45 681.45
SW 12.15 5.9 11 788.535
1489.455
NW 10.8 5.9 11 700.92
NW 16.2 5.9 11 1051.38
1401.84
SW 5.4 5.9 11 350.46
NW 5.4 5.9 11 350.46
537.372
NE 2.88 5.9 11 186.912
NE 10.5 5.9 11 681.45 681.45
NE 15.9 5.9 11 1031.91
1732.83
SE 10.8 5.9 11 700.92
NE 5.4 5.9 11 350.46
1405.085
SE 16.25 5.9 11 1054.625
Sensible Heat Gain For Window Glass- Amphitheater
Room Window Facing Awindow(m2) Utot(W/m2 K) (to-ti) QTht QTht/Room
Vestibule
Office 1 SE 3.2 5.9 11 207.68 207.68
Office 2 SE 4 5.9 11 259.6 259.6
Storage Room
Projector Room
Soundlock Room
Dressing Room 1 NW 2.4 5.9 11 155.76 155.76
Dressing Room 2 NW 1.5 5.9 11 97.35 97.35
Part of Theater SE 4 5.9 11 259.6
519.2
NW 4 5.9 11 259.6
Solar Heat Gain for Opaque Wall (CN)
ROOM Room Exposure 1/RTot (W/m2- °K)
NE 2.78
Hospital Room SE 2.78
NW 2.78
SE 2.78
Nutrition Lab
NW 2.78
SE 2.78
Chemistry Room NW 2.78
SW 2.78
SE 2.78
112 SW 2.78
NW 2.78
SE 2.78
111
NW 2.78
SE 2.78
Supply Office SW 2.78
NW 2.78
SE 2.78
Guidance Office SW 2.78
NW 2.78
SE 2.78
Graduate Program Room
NW 2.78
SE 2.78
Faculty Office NW 2.78
SW 2.78
SE 2.78
Accreditation Room NW 2.78
SW 2.78
SE 2.78
Registrar's Office
NW 2.78
SE 2.78
Anatomy Room NE 2.78
NW 2.78
NE 2.78
SW 2.78
Research Room
NW 2.78
SE 2.78
SW 2.78
Store Room
NE 2.78
NE 2.78
Dean's Office
SW 2.78
NE 2.78
Work Area NW 2.78
SW 2.78
NE 2.78
Record Room NW 2.78
SW 2.78
NE 2.78
Cashier Office SW 2.78
NW 2.78

Solar Heat Gain for Opaque Wall (CN Amphitheat


Room Room Exposure 1/RTot (W/m2- °K)
Office 1 NE 2.78
NW 2.78
SE 2.78
SW 2.78
Office 2 NW 2.78
SE 2.78
SW 2.78
Vestibule NW 2.78
Storage Room NE 2.78
Pojector Room SW 2.78
NW 2.78
Soundlock Room NE 2.78
NW 2.78
Dressing Room 1 NE 2.78
SE 2.78
NW 2.78
Dressing Room 2 SE 2.78
SW 2.78
NW 2.78
or Opaque Wall (CN)
A (m2) CLTD QW QW/Room
18.45 11 564.201
43.65 13 1577.511 3064.88328
55.346 6 923.17128
14.1 13 509.574
796.57008
17.206 6 286.99608
14.1 13 509.574
17.206 6 286.99608 1374.53208
29.7 7 577.962
14.1 13 509.574
29.7 7 577.962 1374.53208
17.206 6 286.99608
14.1 13 509.574
796.57008
17.206 6 286.99608
14.1 13 509.574
29.7 7 577.962 1374.53208
17.206 6 286.99608
8.603 13 310.91242
29.7 7 577.962 1006.46842
7.05 6 117.594
8.603 13 310.91242
428.50642
7.05 6 117.594
34.412 13 1243.64968
28.2 6 470.376 2291.98768
29.7 7 577.962
8.603 13 310.91242
7.05 6 117.594 1006.46842
29.7 7 577.962
8.603 13 310.91242
428.50642
7.05 6 117.594
17.206 13 621.82484
29.7 11 908.226 1765.23884
14.1 6 235.188
8.826 11 269.89908
28.23 7 549.3558
1454.52936
9.486 6 158.22648
13.2 13 477.048
19.8 7 385.308
934.00494
17.943 11 548.69694
9.84 11 300.9072
556.66998
13.143 7 255.76278
9.84 11 300.9072
3.918 6 65.35224 689.29544
16.6 7 323.036
2.72 11 83.1776
9.693 6 161.67924 347.60564
5.28 7 102.7488
5.61 11 171.5538
10.643 7 207.11278 653.88658
16.5 6 275.22

ue Wall (CN Amphitheater)


A (m2) CLTD Q Tht (wall) Q Tht (wall)/Room
22.1925 11 678.64665
18.15 6 302.742
1600.27503
9.24 13 333.9336
14.643 7 284.95278
14.85 6 247.698
12.993 13 469.56702 961.29342
12.54 7 244.0284
1.152 6 19.21536
4.95 11 151.371
16.5 7 321.09
548.82204
13.653 6 227.73204
16.5 11 504.57
580.93104
4.578 6 76.36104
11.55 11 353.199
10.89 13 393.5646 821.913672
4.5054 6 75.150072
7.26 13 262.3764
9.9 7 192.654 545.15244
5.403 6 90.12204
Solar Heat Gain for Opaque Wall (CSB2)
ROOM Room Exposure 1/RTot (W/m2- °K) A (m2) CLTD
SE 2.78 14.25 13
SW 2.78 25.956 7
Canteen
NE 2.78 25.956 11
NW 2.78 25.3 6
SE 2.78 24.5 13
Maintenance Department SW 2.78 8.24 7
NE 2.78 8.943 11
NE 2.78 8.943 11
B.U Multi-purpose Cooperative
SW 2.78 8.24 7
NE 2.78 19.743 11
Computer Lab (105) NW 2.78 24.5 6
SW 2.78 16.48 7
NE 2.78 22.994 11
NW 2.78 24.5 6
Lecture Room
SE 2.78 24.5 13
SW 2.78 16.48 7
SW 2.78 22.994 7
Coordinator NE 2.78 16.48 11
NW 2.78 24.5 6
SW 2.78 24.5 7
Computer Lab (102) NE 2.78 16.48 11
SW 2.78 19.743 7
SE 2.78 24.5 13
Computer Lab (101) NE 2.78 16.48 11
SW 2.78 19.743 7
SW 2.78 11.74 7
Guidance Office NE 2.78 14.643 11
SE 2.78 24.5 13
NE 2.78 38.143 11
Computer Lab (206) NW 2.78 24.5 6
SW 2.78 11.74 7
NW 2.78 24.5 13
Computer Lab (205) NE 2.78 38.286 11
SW 2.78 30.48 7
SE 2.78 15.643 13
CSC Office
NW 2.78 13.5 6
SE 2.78 15.643 13
Scientia Office
NW 2.78 13.5 6
SW 2.78 31.286 7
Computer Lab (202) NE 2.78 23.48 11
NW 2.78 24.5 6
SW 2.78 24.286 7
Computer Lab (201) NE 2.78 16.48 11
Computer Lab (201)
SE 2.78 24.5 13
SE 2.78 14.25 13
SW 2.78 25.956 7
Faculty Room
NE 2.78 25.956 11
NW 2.78 25.3 6
QW QW/Room
514.995
505.1038
2235.8372
793.7345
422.004
885.43
160.3504 1319.2573
273.4769
273.4769
433.82734
160.3504
603.7409
408.66 1333.1017
320.7008
703.1565
408.66
2317.9473
885.43
320.7008
447.4632
503.9584 1360.0816
408.66
476.77
503.9584 1364.9272
384.1988
885.43
503.9584 1773.5872
384.1988
228.4604
447.7829 1561.6733
885.43
1166.413
408.66 1803.5333
228.4604
885.43
1170.786 2649.3567
593.1408
565.338
790.51802
225.18
565.338
790.51802
225.18
608.8256
718.0184 1735.504
408.66
472.6056
503.9584 1861.994
1861.994
885.43
514.995
505.1038
2235.8372
793.7345
422.004
Solar Heat Gain for Opaque Wall (CSB3)
ROOM Room Exposure 1/RTot (W/m2- °K) A (m2)
SE 2.78 22.6
SW 2.78 20.7
RSTC Office
NE 2.78 15.643
NW 2.78 28
SW 2.78 17.5
Animal Histology Lab (105) SE 2.78 28
NE 2.78 24.286
SW 2.78 19.35
Systematic Room (105) NW 2.78 17.2
NE 2.78 29.643
SE 2.78 38.286
SW 2.78 8.6
Lecture Room
NE 2.78 28
NW 2.78 25.8
SE 2.78 17.2
SW 2.78 52.286
Lecture Hall
NE 2.78 48.7
NW 2.78 28
NE 2.78 8.6
Biology Department NW 2.78 19.143
SE 2.78 12.9
NW 2.78 19.143
Chemical Department SE 2.78 12.9
SW 2.78 28
SE 2.78 25.8
SW 2.78 27.95
Instrumentation Room
NE 2.78 17.5
NW 2.78 38.286
NE 2.78 24.286
Parasitology Lab (206) SW 2.78 17.5
SE 2.78 28
SW 2.78 19.35
Organic and Biochem Lab (205) NE 2.78 13.786
NW 2.78 17.2
NW 2.78 25.8
Analytical Chemistry Lab SE 2.78 38.286
SW 2.78 8.6
NW 2.78 8.6
Chemical Room NE 2.78 9.263
SE 2.78 12.143
SW 2.78 26.143
General and Inorganic Chem Lab (203) NE 2.78 17.5
NW 2.78 28
NE 2.78 8.6
Analytical Chem Lab (202) SE 2.78 25.75
NW 2.78 38.286
NE 2.78 26.1
Analytical Chem Lab (201) SE 2.78 17.2
SW 2.78 24.286
CLTD QW QW/Room
13 816.764
7 402.822
2164.989
11 478.363
6 467.040
7 340.550
13 1011.920 2095.136
11 742.666
7 376.551
6 286.896 1569.930
11 906.483
13 1383.656
7 167.356
2837.596
11 856.240
6 430.344
13 621.608
7 1017.486
3595.380
11 1489.246
6 467.040
11 262.988
6 319.305 1048.499
13 466.206
6 319.305
13 466.206 1330.391
7 544.880
13 932.412
7 543.907
2650.079
11 535.150
6 638.610
11 742.666
7 340.550 2095.136
13 1011.920
7 376.551
11 421.576 1085.023
6 286.896
6 430.344
13 1383.656 1981.356
7 167.356
6 143.448
11 283.263 865.559
13 438.848
7 508.743
11 535.150 1510.933
6 467.040
11 262.988
13 930.605 1832.203
6 638.610
11 798.138
13 621.608 1892.352
7 472.606
Solar Load Calculation Thru Transparent Surfaces (BUCN)
ROOM Window Facing SHGFmax(W/m2) SC
SE 630 0.55
Hospital Room NE 435 0.55
NW 435 0.55
SE 630 0.55
Nutrition Lab
NW 435 0.55
SE 630 0.55
Chemistry Room
NW 435 0.55
SE 630 0.95
112
NW 435 0.95
SE 630 0.95
111
NW 435 0.95
SE 630 0.55
Supply Office
NW 435 0.55
NW 435 0.55
Guidance Office
SE 630 0.55
NW 435 0.55
Graduate School Program Room
SE 630 0.55
NW 435 0.55
Faculty Office
SE 630 0.55
NW 435 0.55
Accreditation Room
SE 630 0.55
NW 435 0.55
Registrar's Office
SE 630 0.55
NW 435 0.55
Anatomy Room
SE 630 0.55
Research Office SW 630 0.55
Store Room
Dean's Office NE 435 0.55
Work Area NE 435 0.55
Record Room NE 435 0.55
Cashier's Office NE 435 0.55
Total
nsparent Surfaces (BUCN)
Awindow(m2) CLF Qsg(W) Qsg(W)/ room
15.75 0.79 4311.32625
11.25 0.37 995.878125 5331.607875
0.34 0.3 24.4035
9 0.79 2463.615
2620.0845
2.18 0.3 156.4695
9 0.79 2463.615
2620.0845
2.18 0.3 156.4695
9 0.79 4255.335
4525.6005
2.18 0.3 270.2655
9 0.79 4255.335
4525.6005
2.18 0.3 270.2655
9 0.79 2463.615
2620.0845
2.18 0.3 156.4695
4.5 0.3 322.9875
621.35865
1.09 0.79 298.37115
4.5 0.3 322.9875
621.35865
1.09 0.79 298.37115
18 0.3 1291.95
2485.4346
4.36 0.79 1193.4846
4.5 0.3 322.9875
621.35865
1.09 0.79 298.37115
4.5 0.3 322.9875
621.35865
1.09 0.79 298.37115
9 0.3 645.975
1242.7173
2.18 0.79 596.7423
5.76 0.75 1496.88 1496.88

8.96 0.37 793.1616 793.1616


8.96 0.37 793.1616 793.1616
2.56 0.37 226.6176 226.6176
5.28 0.37 467.3988 467.3988
32233.868475
Solar Load Calculation Thru Transparent Surfaces (BUCN)
Window Facing SHGFmax(W/m ) Awindow(m2)
2
Room SC CLF
Canteen NW 435 1 2.7 0.3
Maitenance SW 630 0.55 5.76 0.75
Cooperative SW 630 0.55 5.76 0.75
Computer Lab (105) SW 630 0.55 11.52 0.75
Lecture Lab (104) SW 630 0.55 11.52 0.75
Coordinator NE 435 0.55 11.52 0.37
Computer Lab (102) NE 435 0.55 11.52 0.37
Computer Lab (101) NE 435 0.55 11.52 0.37
Guidance SW 630 0.55 5.76 0.75
Computer Lab (206) SW 630 0.55 17.28 0.75
Computer Lab (205) SW 630 0.55 11.52 0.75
CSC Office NW 435 0.55 4 0.3
Scientia Office NW 435 0.55 4 0.3
Computer Lab (202) NE 435 0.55 11.52 0.37
Computer Lab (201) NE 435 0.55 11.52 0.37
Total
N) Solar Load Calcula
Qsg(W) Room
352.35
RSTC Office
1496.88
1496.88 Animal Histology(106)
2993.76
Systematic(105)
2993.76
1019.7792
Lecture Room(104)
1019.7792
1019.7792
Lecture Hall
1496.88
4490.64
Biology Department
2993.76
287.1 Chemical Department
287.1
Insrumentation Room
1019.7792
1019.7792 Parasitology Lab(206)
23988.006
Organic Biochem Lab(205)

Analytical Lab(204)

Chemical Room

General Organic Chem Lab(203)

Analytical Chem Lab(202)

Analytical Chem Lab(202)

Total
Solar Load Calculation Thru Transparent Surfaces (CSB3)
Window Facing SHGFmax(W/m2) SC Awindow(m2) CLF Qsg(W) Qsg(W)/ room
SE 630 0.55 5.4 0.79 1478.17
4284.82
SW 630 0.55 10.8 0.75 2806.65
SW 630 0.55 10.5 0.75 2728.69 2728.69
SW 630 0.55 12.15 0.75 3157.481
3932.65125
NW 435 0.55 10.8 0.3 775.17
NW 435 0.95 16.2 0.3 2008.395
4432.32
SW 630 0.95 5.4 0.75 2423.925
SE 630 0.55 10.8 0.79 2956.338
4841.86725
NE 435 0.55 21.3 0.37 1885.529
NE 435 0.55 5.4 0.37 478.0215
2695.275
SE 630 0.55 8.1 0.79 2217.254
SE 630 0.55 8.1 0.79 2217.254 2217.25
SE 630 0.55 16.2 0.79 4434.507
8995.31325
SW 630 0.55 17.55 0.75 4560.806
SW 630 0.55 10.5 0.75 2728.688 2728.69
SW 630 0.55 12.15 0.75 3157.481
3932.65125
NW 435 0.55 10.8 0.3 775.17
NW 435 0.55 16.2 0.75 2906.888
4310.2125
SW 630 0.55 5.4 0.75 1403.325
NW 435 0.55 5.4 0.3 387.585
642.5298
NE 435 0.55 2.88 0.37 254.9448
NE 435 0.55 10.5 0.37 929.4863 929.486
NE 435 0.55 15.9 0.37 1407.508
4363.84575
SE 630 0.55 10.8 0.79 2956.338
NE 435 0.55 5.4 0.37 478.0215
4926.21525
SE 630 0.55 16.25 0.79 4448.194
55961.82
Solar Load Calculation Thru Transparent Surfaces (AMPHITHEATER)
Window FacingSHGFmax(W/m ) SC Awindow(m2)
2
Room
Vestibule
Office 1 SE 630 0.55 3.2
Office 2 SE 630 0.55 4
Storage Room
Projector Room
Soundlock Room
Dressing Room 1 NW 435 0.55 2.4
Dressing Room 2 NW 435 0.55 1.5
Part of Theater SE 630 0.55 4
NW 435 0.55 4
Total
AMPHITHEATER)
CLF Qsg(W)

0.79 875.952
0.79 1094.94

0.3 172.26
0.3 107.6625
0.79 1094.94
0.3 287.1
3632.855
INTERNAL HEAT GAIN FROM LAMPS (AMPHITHEATER)
ROOM QTY W Fu Fb
Vestibule 7 18 1 ----
Office 1 6 18 1 ----
Office 2 6 18 1 ----
Storage Room 5 18 1 ----
Projector Room 5 18 1 ----
Soundlock Room 6 18 1 ----
Dressing Room 1 4 18 1 ----
Dressing Room 2 4 18 1 ----
Theater 4 18 1 ----

OCCUPANT SENSIBLE COOLING LOAD (AMPHITHEATER)


ROOM (G/P)s Np (CLF)p Qps
Vestibule 75 5 0.72 270
Office 1 75 3 0.72 162
Office 2 106.75 15 0.61 976.7625
Storage Room 60 2 0.61 73.2
Projector Room 60 2 0.61 73.2
Soundlock Room 60 2 0.61 73.2
Dressing Room 1 75 4 0.61 183
Dressing Room 2 75 4 0.61 183
Theater 75 4 0.61 183

OCCUPANT LATENT COOLING LOAD (AMPHITHEATER)


ROOM (G/P)L Np QPL
Vestibule 75 5 375
Office 1 67.5 3 202.5
Office 2 106.75 15 320.25
Storage Room 40 2 80
Projector Room 40 2 80
Soundlock Room 40 2 80
Dressing Room 1 75 4 300
Dressing Room 2 75 4 300
Theater 75 4 300

Sensible Heat due to Infiltration (AMPHITHEATER)


Q = 1.23 Q (to-tI)
ROOM Height (m) Area (m2) Δt (°C) a
Vestibule 3.3 10.92 11 0.2
Office 1 3.3 17.1 11 0.2
Office 2 3.3 20.725 11 0.2
Storage Room 3.3 4.866 11 0.2
Projector Room 3.3 12.125 11 0.2
Soundlock Room 3.3 11.625 11 0.2
Dressing Room 1 3.3 6.27 11 0.2
Dressing Room 2 3.3 7.054 11 0.2
Theater 3.3 1315.26 11 0.2

Latent Heat Load due to Infiltration (CSB3)


Q = 3000 Q (Wo-Wi)
ROOM Height (m) Area (m2) Wo Wi
Vestibule 3.3 10.92 0.0158 0.01
Office 1 3.3 17.1 0.0158 0.01
Office 2 3.3 20.725 0.0158 0.01
Storage Room 3.3 4.866 0.0158 0.01
Projector Room 3.3 12.125 0.0158 0.01
Soundlock Room 3.3 11.625 0.0158 0.01
Dressing Room 1 3.3 6.27 0.0158 0.01
Dressing Room 2 3.3 7.054 0.0158 0.01
Theater 3.3 1315.26 0.0158 0.01
CLF QL
0.96 120.96
0.96 103.68
0.96 103.68
0.96 86.4
0.96 86.4
0.96 103.68
0.96 69.12
0.96 69.12
0.96 69.12

n (AMPHITHEATER)
-tI)
b c V Nc Q QIS
0.015 0.014 3.33 0.404 0.00404404 0.054716
0.015 0.014 3.33 0.404 0.0063327 0.085681
0.015 0.014 3.33 0.404 0.00767516 0.103845
0.015 0.014 3.33 0.404 0.00180204 0.024382
0.015 0.014 3.33 0.404 0.00449029 0.060754
0.015 0.014 3.33 0.404 0.00430513 0.058248
0.015 0.014 3.33 0.404 0.00246271 0.03332
0.015 0.014 3.33 0.404 0.00277065 0.037487
0.015 0.014 3.33 0.404 0.48708462 6.590255

to Infiltration (CSB3)
Q (Wo-Wi)
ΔW a c V Nc Q Qil
0.0058 0.2 0.014 3.33 0.404 0.004044 0.070366
0.0058 0.2 0.014 3.33 0.404 0.006333 0.110189
0.0058 0.2 0.014 3.33 0.404 0.007675 0.133548
0.0058 0.2 0.014 3.33 0.404 0.001802 0.031356
0.0058 0.2 0.014 3.33 0.404 0.00449 0.078131
0.0058 0.2 0.014 3.33 0.404 0.004305 0.074909
0.0058 0.2 0.014 3.33 0.404 0.002463 0.042856
0.0058 0.2 0.014 3.33 0.404 0.002771 0.048215
0.0058 0.2 0.014 3.33 0.404 0.51066 8.885484