 status of  the 

floor  location  comments 


lighting study 
the ration between the Emin / Emax must be 
MEP WORK SHOP  DISAPPROVED 
equal or heigher than 0.6 
the ration between the Emin / Emax must be 
equal or heigher than 0.6  so rearrange the 
carpentary shop  DISAPPROVED  lighting fixture 
Eng Store  approved 
BMS room  approved 
the ratio between the Emin/Emax equal or 
maintanance work shop drawings  DISAPPROVED  heigher than 0.6 
chemical storage  approved 
general store  approved 
furniture store  approved 
the ratio between the Emin/Emax equal or 
basement floor 

heigher than 0.6 
co‐oridoor  DISAPPROVED 
the distance between luminare and the 
working plan will be 2.5 m 

cctv server  approved 
the ratio between the Emin/Emax equal or 
room 12  DISAPPROVED  heigher than 0.6 
the ratio between the Emin/Emax equal or 
heigher than 0.6 
pump room 
the distance between luminare and the 
DISAPPROVED  working plan will be 3.15 m
we need explanation about this total no of  
lighting fixture and dosnt comply the 
cctv room  DISAPPROVED  unifirmity factor . 
security manager  approved 
office  approved 
chief engineer room  approved 

the distance between luminare and the 
laundry  DISAPPROVED  working plan will be 3.85 m
the ratio between the Emin/Emax equal or 
heigher than 0.6 
chemical store  approved 
the distance between luminare and the 
working plan will be 3.85 m
laundry  2  DISAPPROVED  working plan will be 0.85 m .
the ratio between the Emin/Emax equal or 
heigher than 0.6 
the distance between luminare and the 
working plan will be 3.85 m
co‐oridoor   DISAPPROVED 
the ratio between the Emin/Emax equal or 
ground floor 

heigher than 0.6 
the ratio between the Emin/Emax equal or 
chiller room  DISAPPROVED  heigher than 0.6 
the distance between luminare and the 
working plan will be 4.5 m 
boiler room  DISAPPROVED 
the ratio between the Emin/Emax equal or 
heigher than 0.6 
clean liner strore  approved 
wwtp  approved 
the distance between luminare and the 
working plan will be 4.5 m 
low voltage room  DISAPPROVED 
the ratio between the Emin/Emax equal or 
heigher than 0.6 
laundry manager  approved 
generator room  approved 
TR1 TR2 TR3  approved 
MV SWITHCGEAR ROOM  approved 