Professional Documents
Culture Documents
Equipment Maintenance
Supervisory Operations
FTView A-P Security Code Configuration
Advanced Production
(non coordinated)
(as of 5/15/2013)
System Access
Disable Alarms
spare
A B C D E F G H I J K L M N O P
Command Equipment in Operator Mode X
Enter Setpoints, Control Variables X
Reset Latched Interlocks, Restart Equipment X
Add Batch to Batch List, Run Batches X
Hold, Restart Batches, clear failures, bind, bind ack X
Acquire/Lock and Release Equipment Operator Mode X
Change Loop Mode (Manual, Auto, Cascade) X
Acquire/Release Equipment Maintenance Mode X
Reset Run Time Accumulators X
Override Inputs X
Bypass Feedback X
Enable/Disable Device X
Configuration (Limits, Constants, Timers) X
Modify Alarm Delay Times X
Tuning X
Change Machine Configuration X
Setup Configuration (Advanced) X
Alarm Configuration (Ack Required, Reset Required) X
Put Device in Simulation X
Edit HMI Application X
Acknowledge Alarms X
Reset Alarms X
Shelve Alarms X
Disable Alarms X
Modify Alarm Limits and Deadbands X
Bypass Permissives and Interlocks X
Respond to Prompt (level 1) X
Respond to Prompt (level 2) X
Exception Processing (Resume, Manual, Auto, Semi-Auto,
X
Pause, Disconnect, Release)
Exception Processing (Step Change, Parameter Change,
X
Step, Acquire, Reorder, Reactivate Step)
Override Downloaded Setpoints X
Override Downloaded Phase Parameters X
Manual Batch Processing (Stop, Abort, Reset Phases) X
Manual Supervisory EP/EM Control X
Force Steps/States X
Change Inflights and Preacts X
Force Queue Indexing X
Navigate to Other Units X
Shutdown HMI Application X
Access Windows Start Menu, Windows Apps X
Change Accounts/Passwords X
Change Security Settings X
Process
HMI Operators X X X X
HMI Operating Supervisor X X X X X X X X X X
HMI Maintenance X X X X X X X X X X X
HMI Maintenance Supervisor X X X X X X X X X X X X X
HMI Manager X X X X X X X X X X X X X
HMI Engineering X X X X X X X X X X X X X X
HMI Admin X X X