If there are no bends, we have still to consider the friction coefficient of the particular cable duct

with the particular cable.

Of course, cable lubricants can be used as long as they do not harm the sheath material or the
duct material.

If we speak about 11kV triplex cables, you will get them only in smaller lengths because of the
diameter - I suppose 350m on a perfectly straight line shouldn't be a problem.

But please take into consideration the maximum pulling force, which is: 30N/mm2 of conductor
cross-section for aluminium conductors and 50N/mm2 of conductor cross-section for copper
conductors