You are on page 1of 1

INERTIA BASE LOAD CALCULATION

For primary pumps

Operating Weight of the Pump 358 Kg


Size of Inertia Base 1650 * 900* 200 mm
Density of RCC 2450 Kg /M3

Weight of RCC 705.6 Kg


Weight of inertia base (Approx.) 100 Kg
Steel Wight (10% of RCC Weight) 70.56 Kg

Total Weight 1234.16 Kg


With Safety Factor ( 25%) 1542.7 Kg
Load Acting Points 4 Nos

Point Load 385.675 Kg


Spring Selection Load 390 Kg

Design Summary

1650mm * 900mm* 200mm inertia base with 4 point load each point having 390 kg
vibration spring isolators

For Secondary Pumps

Operating Weight of the Pump 736 Kg


Size of Inertia Base 2050 * 1100* 250 mm

Density of RCC 2450 Kg /M3


Weight of RCC 1360.975 Kg
Weight of inertia base (Approx.) 200 Kg
Steel Wight (10% of RCC Weight) 136.0975 Kg
Total Weight 2433.0725 Kg
With Safety Factor ( 25%) 3041.340625 Kg

Load Acting Points 4 Nos


Point Load 760.33515625 Kg
Spring Selection Load 765 Kg

Design Summary

2050mm * 1100mm* 250mm inertia base with 4 point load each point having 765 kg
vibration spring isolators