You are on page 1of 16

2009

STANDARD for

COMMERCIAL
AND
INDUSTRIAL
UNITARY
AIR-
CONDITIONING
CONDENSING
UNITS
ISHRAE – RAMA STANDARD
Standard 365

502, DDA Building, Commercial Complex, Laxmi Nagar, Delhi - 110092


IMPORTANT

SAFETY DISCLAIMER

ISHRAE/AHRI does not set safety standards and does not certify or guarantee the safety of any products, components
or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly
recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally
recognized safety standards and code requirements appropriate for products covered by this standard/guideline.

ISHRAE/AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry
practices. ISHRAE/AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will
be non-hazardous or free from risk.

ISHRAE/AHRI CERTIFICATION PROGRAM PROVISIONS

Scope of the Certification Program

The Certification Program includes Commercial and Industrial Unitary Air-Conditioning Condensing Units rated at or above
135,000 Btu/h [39,600 W] but below 250,000 Btu/h [73,200 W] at the ARI Standard Rating Conditions (Cooling).

Certified Ratings

The following Certification Program ratings are verified by test:

1. Single Number Rating Cooling Capacity, Btu/h [W]


2. Single Number Rating Energy Efficiency Ratio, EER, Btu/(W·h)
3. Integrated Part-Load Value, IPLV, Btu/(W·h)

Conformance to the requirements of the Maximum Operating Conditions Tests (Section 8) is also verified by test.

Note:

This standard supersedes AR I Standard 365 - 94


TABLE OF CONTENTS

SECTION PAGE

Section 1. Purpose...............................................................................................................1

Section 2. Scope...................................................................................................................1

Section 3. Definitions ..........................................................................................................1

Section 4. Classifications .....................................................................................................2

Section 5. Test Requirements ..............................................................................................2

Section 6. Rating Requirements ...........................................................................................2

Section 7. M inimum Data Requirements for Published Ratings .........................................4

Section 8. Operating Requirements .....................................................................................4

Section 9. M arking and Nameplate Data.............................................................................6

Section 10. Conformance Conditions ....................................................................................6

TABLES

Table 1. Classifications of Commercial and Industrial Air-Conditioning


Condensing Units................................................................................................2

Table 2. Standard Rating Conditions ................................................................................3

FIGURE

Figure 1. Part-Load Factor Curve ......................................................................................5

APPENDICES

Appendix A. References - Normative.......................................................................................7


Appendix B. References ‫ ـ‬Informative......................................................................................7

Appendix C. M ethod and Example of Calculating Integrated


Part-Load Values (IPLV) - Normative................................................................8
TABLE FOR APPENDICES

Table C1. Example IPLV Calculation................................................................................10

FIGURE FOR APPENDICES

Figure C1. Part-Load Factor Example ..................................................................................9


______________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-
2009

COMMERCIAL AND INDUSTRIAL UNITARY


AIR-CONDITIONING CONDENSING UNITS
Section 1. Purpose 3.2 Cooling Capacity. Cooling capacity is the capacity
in Btu/h [W] obtained at specific conditions. It is equal to
1.1 Purpose. The purpose of this standard is to establish the increase in total enthalpy between the liquid refrigerant
for Commercial and Industrial Unitary Air-Conditioning entering the expansion valve and superheated return gas
Condensing Units: definitions; classifications; test multiplied by the mass flow rate of the refrigerant.
requirements; rating requirements; minimum data
requirements for Published Ratings; operating requirements; 3.3 Dew Point. Refrigerant vapor saturation temperature
marking and nameplate data; and conformance conditions. at a specified pressure.

1.1.1 Intent. This standard is intended for the 3.4 Energy Efficiency Ratio (EER). A ratio of the
guidance of the industry, including manufacturers, Cooling Capacity in Btu/h to the power input values in
engineers, installers, contractors and users. watts at any given set of Rating Conditions expressed in
Btu/(W·h).
1.1.2 Review and Amendment. This standard is
subject to review and amendment as technology 3.5 Integrated Part-Load Value (IPLV). A single
advances. number part-load efficiency figure of merit calculated per the
method described in this standard and expressed in
Btu/(W·h).
Section 2. Scope
3.6 Published Rating. A statement of the assigned
2.1 Scope. This standard applies to factory-made values of those performance characteristics, under stated
Commercial and Industrial Unitary Air-Conditioning Rating Conditions, by which a unit may be chosen to fit its
Condensing Units greater than or equal to 135,000 Btu/h application. These values apply to all units of like nominal
[39.6 kW] as defined in Section 3. size and type (identification) produced by the same
manufacturer. As used herein, the term Published Rating
2.1.1 Energy Source. This standard applies only includes the rating of all performance characteristics shown
to electrically-driven, mechanical compression-type on the unit or published in specifications, advertising, or
condensing units. other literature controlled by the manufacturer, at stated
Rating Conditions.
2.2 Exclusions. This standard does not apply to the
testing and rating of condensing units for refrigeration 3.6.1 Application Rating. A rating based on tests
purposes, as defined in ISHRAE/AHRI Standard 520. performed at Application Rating conditions (other
than Standard Rating Conditions).

Section 3. Definitions 3.6.2 Standard Rating. A rating based on tests


performed at Standard Rating Conditions.
All terms in this document shall follow the standard
industry definitions in the current edition of ASHRAE 3.7 Rating Conditions. Any set of operating conditions
Terminology of Heating, Ventilation, Air-Conditioning and under which a single level of performance results and which
Refrigeration unless otherwise defined in this section. causes only that level of performance to occur.

3.1 Commercial and Industrial Unitary Air- 3.7.1 Standard Rating Conditions. Rating
Conditioning Condensing Unit. A factory-made assembly Conditions used as the basis of comparison for
of refrigerating components designed to compress and performance characteristics.
liquefy a specific refrigerant. It consists of one or more
refrigerant compressors, refrigerant condensers (air-cooled, 3.8 "Shall" or "Should." "Shall" or "should" shall be
evaporative – cooled, and/or water-cooled), condenser fans interpreted as follows:
and motors (where used) and factory-supplied accessories.

1
ISHRAE/RAMA/ARI STANDARD 365-
2009_________________________________________________________

3.8.1 Shall. Where "shall" or "shall not" is used 6.1 Standard Ratings. Published Ratings shall be
for a provision specified, that provision is mandatory obtained at one or more of the Standard Rating Conditions
if compliance with the standard is claimed. as shown in Table 2. Power input shall be the total power
input to the compressor(s), fan(s), controls, and any other
3.8.2 Should. "Should" is used to indicate components included as part of the condensing unit.
provisions which are not mandatory but which are
desirable as good practice. 6.1.1 Values of Standard Cooling Capacity
Ratings. These ratings shall be expressed only in
3.9 Single Number Rating. The Cooling Capacity and terms of thousands of Btu/h [W] in multiples of
EER determined by averaging the results of the tests at 2,000 Btu/h [600 W] for units with Standard Ratings
Rating Conditions No. 1 and No. 2 for air-cooled and of 400,000 Btu/h [117,000 W] and under. For units
evaporative-cooled condensing units and at Rating with Standard Ratings of over 400,000 Btu/h
Conditions No. 5 and No. 6 for water-cooled condensing [117,000 W], the ratings shall be expressed in
units (Section 6). multiples of 5,000 Btu/h [1,500 W].

6.1.2 Values of Standard Efficiency Ratings.


Section 4. Classifications EER, in Btu/(W·h), and IPLV shall be expressed in
multiples of 0.1.
Equipment covered within the scope of this standard shall
be classified as shown in Table 1: 6.1.3 Single Number Ratings. The reported
values shall be determined by averaging the results
obtained at Rating Conditions No. 1 and No. 2 or at
Table 1. Classifications of Commercial and Rating Conditions No. 5 and No. 6.
Industrial Air-Conditioning Condensing
Units 6.1.4 Electrical Conditions. Standard Rating
tests shall be performed at the nameplate rated
voltage(s) and frequency.
Designatio ARI Condenser Arrangement
n Type Type
For condensing units with dual nameplate voltage
Remote ratings, Standard Rating tests shall be performed at
Condensin RCU-A Air
COMP both voltages, or at the lower of the two voltages, if
g only a single Standard Rating is to be published.
RCU-E Evaporativ
Unit (RCU) COND
e
6.1.5 Condenser Air Quantity. All Standard
RCU-W Water Ratings for condensing units shall be determined at
the condenser air quantity specified by the
manufacturer where the fan drive is adjustable.
Section 5. Test Requirements Where the fan drive is direct-connected, Standard
Ratings shall be determined at the condenser air
5.1 Test Requirements. All Standard Ratings shall be quantity established when the condensing unit is
verified by tests conducted in accordance with operated with all of the associated inlet louvers and
ANSI/ASHRAE Standard 23 and with the test methods and any duct work and attachments considered by the
procedures as described in this standard. manufacturer as normal installation practice. Once
established, the condenser air circulation of the
5.1.1 An alternate method of verification may be condensing unit shall remain unchanged throughout
used by tests conducted in accordance with all tests prescribed herein, except as altered by
ANSI/ASHRAE Standard 37 provided that the automatic controls.
suction Dew Point temperature and the return gas
temperature are determined from the procedures in 6.2 Part-Load Rating. Condensing units which are
this standard. capable of capacity reduction shall be rated at 100% and at
each step of capacity reduction provided by the condensing
unit as published by the manufacturer. These rating points
Section 6. Rating Requirements shall be used to calculate the IPLV (6.2.2).

2
______________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-
2009

6.2.1 Part-Load Rating Conditions. The


conditions of test for part-load ratings are the same as Suction Dew Point temperature……50.0°F [10.0°C]
those for the Standard Ratings (6.1) except for the
following: Return gas temperature…………….65.0°F [18.3°C]

For all units:

Refrigerant Entering Condensing Unit


Table 2. Standard Rating Conditions
Air- and Ev aporativ e-Cooled Condensing Units
1
Rating Air Entering and Surrounding Unit Refrigerant Entering Condensing Unit
Condition
2
Dry-Bulb Wet-Bulb Suction Dew Point Return Gas
°F °C °F °C °F °C °F °C

3
1 95.0 35.0 75.0 23.9 50.0 10.0 65.0 18.3
3
2 95.0 35.0 75.0 23.9 40.0 4.4 55.0 12.8
3 80.0 26.7 67.0 19.4 50.0 10.0 65.0 18.3
4 80.0 26.7 67.0 19.4 40.0 4.4 55.0 12.8

Water-Cooled Condensing Units


1
Rating Water Temperature Refrigerant Entering Condensing Unit
Condition
Entering Leaving Suction Dew Point Return Gas
°F °C °F °C °F °C °F °C

3
5 90.0 32.2 100.0 37.8 50 10.0 65.0 18.3
3
6 90.0 32.2 100.0 37.8 40 4.4 55.0 12.80
7 80.0 26.7 50 10.0 65.0 18.3
8 80.0 26.7 Same water flow rate 40 4.4 55.0 12.8
as established above.

Notes:
1
The liquid temperature and pressure leaving the condensing unit shall be reported by the manufacturer in its ratings.
2
Required for evaporative-cooled condensing units only.
3
The Single Number Rating is determined by averaging the results of the tests at Rating Conditions No. 1 and No. 2
or at Rating Conditions No. 5 and No. 6.

For air-cooled units: Surrounding unit...................80.0°F [26.7°C] dry-


bulb 67.0°F [19.4°C]
Air temperature entering and wet-bulb
Surrounding unit....................80.0°F [26.7°C]
dry-bulb (and 67.0 °F For water-cooled units:
[19.4°C] wet-bulb
when condensate is Water temperature entering
rejected into the air condenser...............................80.0°F [26.7°C]
stream)
Water flow rate…………….Same as Standard
For evaporative-cooled units: Rating Conditions

Air temperature entering and

3
ISHRAE/RAMA/AHRI STANDARD 365-
2009________________________________________________________

(
IPLV = PLF 1− PLF 2 × ) (EER 1 +2 EER 2 )
Capacity reduction means may be adjusted to obtain (EER 2 + EER 3 )
the specified step of unloading. No manual
adjustment of condenser air quantities from those of
(
+ PLF 2 − PLF 3 × ) 2
the Standard Rating Conditions shall be made. (EER n −1+ EER n )
However, automatic adjustment of condenser air + (PLF n − 1 − PLF n ) ×
2
quantities by condensing unit function is
+ (PLF n ) × (EER n )
permissible.
7.1 Minimum Data Requirements for Published Ratings.
6.2.2 Integrated Part-Load Value (IPLV). For As a minimum, Published Ratings shall consist of the
equipment covered by this standard, the IPLV shall following information:
be calculated as follows:
a. Single Number Rating Cooling Capacity, Btu/h
a. Determine the capacity and EER at the [W]
conditions specified in 6.2 b. Single Number Rating Energy Efficiency Ratio,
EER, Btu/(W·h)
b. Determine the Part-Load Factor (PLF) c. Integrated Part-Load Value, IPLV, Btu/(W·h)
from Figure 1, at each capacity step
(see Appendix C) All claims to ratings within the scope of this standard shall
include the statement “ Rated in accordance with ARI
c. Use the following equation to calculate Standard 365”. All claims to ratings outside the scope of
IPLV: this standard shall include the statement “ Outside the scope
of ARI Standard 365”. Wherever Application Ratings are
published or printed, they shall include a statement of the
conditions at which the ratings apply.

where: Section 8. Operating Requirements

PLF = Part-Load Factor 8.1 Operating Requirements. To comply with this


determined from standard, any production Commercial and Industrial Unitary
Figure 1 Air-Conditioning Condensing Unit shall meet the
requirements detailed herein.
n = Total number of
capacity steps 8.2 Maximum Operating Conditions Test. Commercial
and Industrial Unitary Air-Conditioning Condensing Units
Superscript 1 = 100% shall be designed and produced to pass the following
capacity and EER maximum operating conditions tests. For multi-capacity
at part-load Rating units, this test shall be conducted with the unit’s controls
Conditions set for maximum capacity.

Subscript 2, 3 etc. = Specific capacity 8.2.1 Temperature Conditions.


and EER at part-
load steps per 6.2 For all units:

6.3 Tolerances. To comply with this standard, measured Air temperature surrounding
test results shall not be less than 95% of Published Ratings unit..........................115.0 °F [46.1°C]
for Cooling Capacity, Energy Efficiency Ratio (EER) and dry-bulb (For units or
Integrated Part-Load Value (IPLV). portions thereof
intended to be installed
only indoors, this
Section 7. Minimum Data Requirements temperature may be
for Published Ratings reduced to 95.0 °F
[35.0 °C] dry-bulb.)

4
______________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-
2009

Refrigerant Entering Condensing Unit

Suction Dew Point


temperature.............50°F [10°C]

Return gas
temperature.............65.0°F [18.3°C]

For water-cooled units:

Water temperature entering


condenser.................90°F [32.2°C]

Water temperature leaving


condenser................100°F [37.8°C]

For air-cooled units:

Outside air
temperature.............115.0 °F [46.1°C]
dry-bulb (and 75.0 °F
[23.9 °C] wet-bulb
when condensate is
rejected to the
condenser air stream) at
the standard condenser
air quantity specified
and stated by the
manufacturer.

5
ISHRAE/AHRI/RAMA STANDARD 365-
2009________________________________________________________

6
______________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-
2009

7
ISHRAE/AHRI/RAMA STANDARD 365-
2009________________________________________________________

For evaporative-cooled units:

Outside air Section 9. Marking and Nameplate Data


temperature.............100.0 °F [37.8°C]
dry-bulb 9.1 Marking and Nameplate Data. As a minimum, the
80.0 °F [26.7°C] wet- nameplate shall include the manufacturer's name, model
bulb designation, and electrical characteristics.

Make-up water Nameplate voltages for 60 Hertz systems shall include one
temperature.............90.0 °F [32.2 °C] or more of the equipment nameplate voltage ratings shown
in Table 1 of ARI Standard 110. Nameplate voltages for 50
8.2.2 Voltages. Tests shall be conducted at the Hertz systems shall include one or more of the utilization
range B minimum and maximum utilization voltages voltages shown in Table 1 of IEC Standard Publication
from ARI Standard 110, Table 1, based on the unit’s 60038.
nameplate rated voltage(s). These voltages shall be
supplied at the unit’s service connection and at rated
frequency. A lower minimum or a higher maximum Section 10. Conformance Conditions
voltage shall be used, if listed, on the nameplate.
10.1 Conformance. While conformance with this standard
8.2.3 Procedure. is voluntary, conformance shall not be claimed or implied
for products or equipment within its Purpose (Section 1)
8.2.3.1 The condensing unit shall be and Scope (Section 2) unless such claims meet all of the
operated continuously for two hours at the requirements of the standard.
temperature conditions and voltage(s)
specified.

8.2.3.2 All power to the condensing unit


shall be shut off for a period sufficient to
cause the compressor to stop (not to exceed
five seconds) and then be restored.

8.2.4 Requirements.

8.2.4.1 During both tests, the condensing


unit shall operate without failure of any of
its parts.

8.2.4.2 The unit shall resume continuous


operation within one hour of restoration of
power and shall then operate continuously
for one hour. Operation and resetting of
safety devices prior to establishment of
continuous operation is permitted.

8.2.4.3 Units with water-cooled condensers


shall operate at maximum conditions with a
water-pressure drop not to exceed 15.0 psi
[103 kPa], measured across the unit.

8.3 Tolerances. The conditions for the tests outlined in


8.2 are average values subject to tolerances of ± 1.0°F [±
0.6°C] for air wet-bulb and dry-bulb temperatures, ± 0.5°F
[± 0.3°C] for water temperatures, and ± 1.0% of the readings
for specified voltages.

8
______________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-
2009

APPENDIX A. REFERENCES – NORMATIVE


A1 Listed here are all standards, handbooks, and other A1.4 ARI Standard 520-1997, Positive
publications essential to the formation and implementation Displacement Condensing Units, 1997, Air-
of the standard. All references in this appendix are Conditioning and Refrigeration Institute, 4100 North
considered as part of the standard. Fairfax Drive, Suite 200, Arlington, VA 22203,
U.S.A.
A1.1 ANSI/ASHRAE Standard 23-1993, Methods
of Testing for Rating Positive Displacement A1.5 ASHRAE Terminology of Heating,
Refrigerant Compressors and Condensing Units, Ventilation, Air-Conditioning and Refrigeration,
1993, American Society of Heating, Refrigerating and Second Edition, 1991, American Society of Heating,
Air-Conditioning Engineers, Inc., 1791 Tullie Circle, Refrigerating and Air-Conditioning Engineers, Inc.,
N.E., Atlanta, GA 30329, U.S.A. 1791 Tullie Circle, N.E., Atlanta, GA 30329,
U.S.A.
A1.2 ANSI/ASHRAE Standard 37-1988, Methods
of Testing for Rating Unitary Air-Conditioning and A1.6 IEC Standard Publication 60038, IEC
Heat Pump Equipment, 1988, American Society of Standard Voltages, 1983, International
Heating, Refrigerating and Air-Conditioning Electrotechnical Commission, 3, rue de Varembe,
Engineers, Inc., 1791 Tullie Circle, N.E., Atlanta, P.O. Box 131, 1211 Geneva 20, Switzerland.
GA 30329, U.S.A.

A1.3 ARI Standard 110-2002, Air-Conditioning


and Refrigerating Equipment Nameplate Voltages,
2002, Air-Conditioning and Refrigeration Institute,
4100 North Fairfax Drive, Suite 200, Arlington,
VA 22203, U.S.A.

APPENDIX B. REFERENCES – INFORMATIVE


None.

9
ISHRAE/AHRI/RAMA STANDARD 365-
2009________________________________________________________

APPENDIX C. EXAMPLE OF CALCULATING


INTEGRATED PART-LOAD VALUES (IPLV) - NORMATIVE
C1 Purpose and Scope. C3 Calculation Example for a Four Capacity Step System.

C1.1 Purpose. This appendix shows example C3.1 Assume equipment has four capacity steps as
calculations for determining Integrated Part-Load follows:
Values (IPLV).
1 100% (full load)
C1.2 Scope. This appendix is for equipment 2 75% of full load
covered by this standard. 3 50% of full load

) ( )
EER 1 + EER 2 4 25% of full load
(
IPLV = PLF 1− PLF 2 ×
2
C2
C3.2 Obtain Part-Load Factors from Figure C1.
(
+ PLF 2 − PLF 3 ) × (EER 2 + EER 3 )
2 C3.3 Obtain EER at each capacity step per 6.2 of
(EER n −1+ EER n ) this standard.
(
+ PLF n −1 − PLF n × ) 2 C3.4 Calculate IPLV using the general equation
+ (PLF n ) × (EER n ) General with:
Equation and Definitions of Terms.
n = 4
PLF 1 = 1.0 EER 1 = 8.9
C1 PLF 2 = 0.9 EER 2 = 7.7
PLF 3 = 0.4 EER 3 = 7.1
PLF 4 = 0.1 EER 4 = 5.0

Enter the above values in Equation C1:

 8.9 + 7.7 
IPLV = (1.0 - 0.9)  
 2 
where:
 7.7 + 7.1 
+ (0.9 - 0.4)  
PLF = Part-Load Factor  2 
determined from Figure
C1  7.1 + 5.0 
+ (0.4 - 0.1)  
 2 
n = Total number of capacity
steps + 0.1 x 5.0

Subscript 1 = 100% capacity and EER = (0.1 x 8.3) + (0.5 x 7.4)


at part-load Rating
Conditions + (0.3 x 6.0) + 0.5

Subscript 2, 3, etc. = Specific capacity = 0.83 + 3.70 + 1.80 + 0.5


and EER at part-load
steps per 6.2 of this IPLV = 6.8 Btu/(W·h)
standard
To further illustrate the calculation process,
see the example in Table C1.

10
____________________________________________________ISHRAE/RAMA/AHRI STANDARD 365-2009

11
ISHRAE/RAMA/AHRI STANDARD 365-2009________________________________________________________
_
I-P Units

Using information from C3:

Table C1. Exam ple IPLV Calculation

3
Capacit % Full PLF Mfrs. Avg. PLF Diff. Avg. EER x Weighted
y Step Load Part- Part- PLF Diff. = Avg.
Cap. 2 Load Load
EER EER
2
1 100% 1.0 8.9 (1.0 - 0.9) = 8.3 x 0.1 = 0.83
= 8.3 0.1
2 75% 0.9 7.7 7.4 x 0.5 = 3.70
= 7.4 (0.9 - 0.4) =
3 50% 0.4 7.1 0.5 6.0 x 0.3 = 1.80
= 6.0
4 25% 0.1 5.0 (0.4 - 0.1) = 5.0 1 x 0.1 = 0.50
1
= 5.0 0.3
0% 0.0 ----- Single number 6.83 4
(0.1 - 0.0) = IPLV
0.1

Notes:
1
For the range between 0% capacity and the last capacity step, use EER of the last capacity step for the
average EER.
2
The 100% capacity and EER are to be determined at the part-load Rating Conditions.
3
Part-Load Factor from Figure C1.
4
Rounded to 6.8 Btu/(W·h).

12

You might also like