Professional Documents
Culture Documents
September 2002
The September 2002 Addendum to ARI Standard 880-98, Air Terminals, is comprised of only
the shaded portions shown, which has been incorporated into the already published 1998 version
of ARI Standard 880 to avoid confusion.
The Addendum addresses a new type of unit, modulating diffuser units, for inclusion in the ARI
Standard 880-98. There are no changes to any of the other type of units in this Addendum.
AIR
TERMINALS
Standard 880
SAFETY RECOMMENDATIONS
It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements, appropriate for products covered by this standard.
ARI, as a manufacturers' trade association, uses its best efforts to develop standards, employing state-of-the-art
and accepted industry practices. However, ARI does not certify or guarantee safety of any products, components
or systems designed, tested, rated, installed or operated in accordance with these standards or that any test
conducted under its standards will be non-hazardous or free from risk.
Exclusion: This certification program does not apply to the rating and testing of retrofit units.
Certified Ratings
The following certification program ratings are verified by test at the standard rating conditions (see Section 6.2):
Sound power level data generated by use of this standard with air terminals are directly applicable to ARI
Standard 885, a procedure for using published sound ratings in the estimating of sound levels in occupied spaces.
Note:
Price $15.00 (M) $30.00 (NM) ©Copyright 1998, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A. Registered United States Patent and Trademark Office
TABLE OF CONTENTS
SECTION PAGE
Section 2. Scope.....................................................................................................................1
TABLES
FIGURES
Figure 4. Discharge Sound Test for Integral Diffuser Air Terminal - Alternative
Method.................................................................................................................11
APPENDICES
AIR TERMINALS
Section 1. Purpose 3.1 Definitions. All terms in this document will follow the
standard industry definitions in the current edition of
1.1 Purpose. The purpose of this standard is to establish ASHRAE Terminology of Heating, Ventilation, Air
for air terminals : definitions and symbols; classifications; Conditioning, and Refrigeration unless otherwise defined in
requirements for testing and rating; minimum data this section.
requirements for Published Ratings; marking and nameplate
data; and conformance conditions. 3.2 Acoustically Isolated. The specimen under test shall
have a sound pressure level at least 10 dB higher than any
1.1.1 Intent. This standard is intended for the extraneous sound sources, such as sound generated from the
guidance of the industry, including manufacturers, air supply or duct walls, to insure that the test specimen is the
engineers, installers, contractors and users. sole contributor to the sound level being measured (see
Figure 1).
1.1.2 Review and Amendment. This standard is
subject to review and amendment as technology 3.3 Air.
advances.
3.3.1 Primary Air. Air supplied to an air terminal
inlet under positive static gage pressure, normally from
Section 2. Scope an air handling unit.
2.1 Scope. This standard applies to air control and 3.3.2 Secondary Air. Air drawn into an air terminal
distribution devices used in commercial air distribution by means of induction and discharged through the air
systems which are ducted air devices and provide control of terminal outlet.
air volume and/or air temperature by one or more of the
following means: 3.3.3 Standard Air. As defined in ASHRAE
Terminology of Heating, Ventilation, Air
a. Fixed or adjustable directional vanes. Conditioning and Refrigeration, dry air at 70EF
b. Pressure dependent volume dampers or shutoff [20EC] and 14.696 psia [101.325 kPa]. Under these
valves (including air induction nozzles and conditions, dry air has a mass density of 0.075 lb/ft 3
dampers). [1.204 kg/m3].
c. Pressure compensated volume dampers or
shutoff valves (including air induction nozzles 3.4 Airflow. Unit volume displacement of standard air per
and dampers). unit time. Normally measured in cubic feet per minute (cfm) or
d. Heat exchange. cubic meters per second (m3/s). The various types of airflow
e. On/off fan control. are defined as follows:
f. Variable speed fan control.
3.4.1 Design Airflow. The flow of conditioned air
These devices may or may not have a fan to deliver air into a through an air terminal required to meet a given
space. heating or cooling design load.
2.2 Exclusions. This standard does not apply to registers, 3.4.2 Rated Airflow. The flow of air through an air
diffusers and grilles or to products specifically covered by: terminal at which test or performance data is generated.
a. The Air Heating and Cooling Coils Sub-Section 3.4.3 Standard Airflow. Airflow corrected for
of the Air Conditioning Heat Transfer Products standard air density. Qs = Qa (ñ a /ñ s).
Section of ARI. ARI Standard 410.
b. The Room Fan-Coil and Air-Induction Units 3.4.4 Induced Airflow. The flow of secondary air
Sub-Section of the Air Conditioning Heat into an air terminal resulting from a pressure differential
Transfer Products Section of ARI. ARI created by the velocity of the flow of primary air
Standard 440. through the terminal.
1
____________________________________________________________________ARI STANDARD 880-1998
3.5 Air Terminal (Terminal). A device that modulates the 3.9 Octave Band. Frequency band with an upper band
volume of air delivered to a conditioned space in response to limit that is twice the frequency of the lower band limit. The
a given load (see Figures 2 and 3). The various types of air center frequency of an Octave Band is the geometric mean of
terminals are: its upper and lower band limits. The octave band center
frequencies of interest are listed in Table 1:
3.5.1 Bypass Terminal. Air terminal that diverts Table 1. Octave Band Center Frequencies
excess primary air to the return. Octave Band Center Frequency (Hz)
3.5.8 Modulating Diffuser Terminal. A diffuser 3.11.2 Pressure Compensated Control System.
with an integral air terminal. Airflow through the air terminal is independent of
system pressure.
3.6 Damper. A device used to regulate or modulate the
flow of air. 3.11.3 Pressure Dependent Control System. Airflow
through the air terminal varies in response with system
3.6.1 Inlet Damper. Controls all air flowing into an pressure.
integral diffuser terminal.
3.12 Published Ratings. A statement of the assigned
3.6.2 Outlet Damper. Controls only the air being values of those performance characteristics, under stated
discharged through the diffuser part of an integral rating conditions, by which a unit may be chosen to fit its
diffuser terminal. application. These values apply to all units of like nominal
size and type (identification) produced by the same
3.7 Equivalent Diameter. Diameter of a circular equivalent manufacturer. As used herein, the term Published Rating"
of any duct for equal cross-sectional areas. includes the rating of all performance characteristics shown
on the unit or published in specifications, advertising or other
3.8 Model. An air terminal of the same type with similar literature controlled by the manufacturer, at stated rating
characteristics available in a progression of sizes. For fan- conditions.
powered air terminals, a model is defined by a progression of
various inlet dimensions and fan volume capacities. For non- 3.12.1 Standard Rating. A rating based on tests
fan-powered air terminals, it is an air terminal of various inlet performed at Standard Rating Conditions.
dimensions.
2
ARI STANDARD 880-1998
3.12.2 Application Rating. A rating based on tests 3.17 Size. Air terminal characteristics related to the
performed at application rating conditions (other than dimensions of the unit.
Standard Rating Conditions).
3.18 Sound Power. In a specified frequency band, the rate
3.13 Quiet Air Supply. Condition in which the sound power at which sound energy is radiated by a noise source,
level introduced in the frequency band of interest by the air measured in watts.
supply alone is at least 10 dB lower than the measured sound
power level generated by the air supply and the air terminal 3.19 Sound Power Level. In a specified frequency band,
under test. ten times the common logarithm of the ratio of the sound
power radiated by the noise source under test to the standard
3.14 Rating Conditions. Any set of operating conditions reference sound power of 10-12 watt.
under which a single level of performance results, and which
causes only that level of performance to occur. 3.20 Sound Power-Radiated. Sound power transmitted
from an air terminal casing (plus induction port for fan-
3.14.1 Standard Rating Conditions. Rating powered air terminals).
conditions used as the basis of comparison for
performance characteristics. 3.21 Sound Power - Discharge. Sound power transmitted
from an air terminal outlet.
3.15 Retrofit Unit. Air terminal intended for installation into
existing air distribution systems, and containing little or no 3.22 Sound Pressure. In a specified frequency band, a
sound attenuating materials. fluctuating pressure superimposed on the static pressure by
the presence of sound.
3.16 "Shall," "Should," "Recommended" or "It Is
Recommended." "Shall," "should," "recommended" or "it is 3.23 Sound Pressure Level. In a specified frequency band,
recommended" shall be interpreted as follows: 20 times the common logarithm of the ratio of the sound
pressure radiated by the noise source under test to the
3.16.1 Shall. Where "shall" or "shall not" is used standard reference pressure of 20 micropascals.
for a provision, that provision is mandatory if
compliance with the standard is claimed. 3.24 Symbols and Abbreviations. The nomenclature used
throughout this standard is shown in Table 2.
3.16.2 Should, Recommended or It Is Recommended.
"Should," "recommended" or "it is recommended" is
used to indicate provisions which are not mandatory
but are desirable as good practice.
Table 2. Nomenclature
Symbol Quantity I - P Units SI Units
3
____________________________________________________________________ARI STANDARD 880-1998
4.1 Classifications (Types). Terminal units falling within 5.1 Test Requirements. Air terminals shall be tested in
the scope of this standard shall be classified as one accordance with ASHRAE Standard 130, except as noted
of the following eight types: below.
4
ARI STANDARD 880-1998
5.1.4.5 Dual Duct Air Terminal Test Watts shall be expressed to the nearest 1 watt.
Configuration. Dual duct terminals shall be
tested with one valve controlling air flow 6.2 Standard Rating Conditions.
and one valve fully closed.
6.2.1 Air Flow Rate and Minimum Operating
5.1.5 Radiated Sound Power Tests - Series Pressure.
Flow Fan Terminals. The total air flow
discharging the test unit shall be measured using 6.2.1.1 Primary Damper. The standard
an acoustically isolated flow measuring device rated air flow and minimum operating
installed as shown in Figure 6 of ASHRAE pressure shall be established and published
Standard 130 (3.5 De distance to discharge flow in accordance with Table 4.
measuring device is a minimum value.)
6.2.1.2 Integral Fan. Fan air flow rating
5.1.6 Induced Airflow. Induced airflow is shall be established and published at 0.25 in.
calculated by subtracting the primary airflow from the H2O [0.062 kPa] discharge static pressure or
discharge (total) airflow. Primary airflow is measured minimum recommended pressure (whichever
in accordance with Section 4.4 and discharge (total) is greater) with any fan volume dampers at
airflow is measured in accordance with Section 5.1 of wide open position, and primary air valve
ASHRAE Standard 130. closed.
5
____________________________________________________________________ARI STANDARD 880-1998
standard rated airflow and 1.5 in. H2O [0.37 Octave Band Center Rating Tolerance
kPa] inlet static pressure. The induction Frequencies, Hz dB
damper(s) shall be set in the full open 125 6
position. 250 4
500 3
6.2.2 Sound Power Rating. The sound power 1000 3
level, dB, for both discharge and radiated shall be 2000 3
established and published at the Standard Rating 4000 3
Conditions (see Table 5).
6.3 Application Ratings. Data at conditions other than Section 7. Minimum Data Requirements
those specified in 6.2 may be published as application for Published Ratings
ratings, and shall be determined in accordance with the
method of testing described in Section 5. 7.1 Minimum Data Requirements for Published Ratings.
Published ratings shall include Standard Ratings and may
6.4 Appurtenance Ratings. The terminal data referred to also include application ratings. The following information
in 6.2 represent the performance of the base terminal without shall be published for all Standard Ratings.
appurtenances. Thus, as appurtenances such as reheat coils,
filters, multiple outlet connectors, etc. are added to the a. A listing of all applicable rating conditions
terminal, their effects must be taken into account in order to specified.
establish the overall performance of the combined terminal. b. Primary air flow rate, cfm [m3/s]
c. Induced or fan air flow rate, cfm [m3/s]
6.5 Publication of Ratings. Wherever application ratings d. Minimum operating pressure, in. H2O [kPa]
are published or printed, they shall include or be e. Octave band sound power level, dB (125 to
accompanied by the Standard Rating, clearly designated as 4000 Hz)
such, including a statement of the conditions at which the f. Electrical power input at fan rating point, W
ratings apply. (fan-powered terminals only)
6
ARI STANDARD 880-1998
For Series Flow Fan-Powered Terminals, the rated air flow cfm [m3/s] for the primary air valve shall be the lower of the fan
rating flow or the rated air flow according to the above table.
Integral Diffuser Terminals and Bypass Terminals shall be rated at the manufacturer's recommended air flow.
Modulating Diffuser Terminals shall be rated at 750 fpm [3.8 m/s] and 400 fpm [2.0 m/s] neck velocity.
7
____________________________________________________________________ARI STANDARD 880-1998
8
ARI STANDARD 880-1998
9
____________________________________________________________________ARI STANDARD 880-1998
10
ARI STANDARD 880-1998
Figure 4. Discharge Sound Test for Integral Diffuser Air Terminal - Alternative Method
11
____________________________________________________________________ARI STANDARD 880-1998
12
ARI STANDARD 880-1998
13