You are on page 1of 13

2001

STANDARD for

DESUPERHEATER/
WATER HEATERS

Standard 470

4100 N. FAIRFAX DR., STE. 200 • ARLINGTON, VIRGINIA 22203


IMPORTANT

SAFETY RECOMMENDATIONS

It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements appropriate for products covered by this standard.

ARI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-art and
accepted industry practices. However, ARI does not certify or guarantee safety of any products, components or
systems designed, tested, rated, installed or operated in accordance with these standards or that any tests
conducted under its standards will be non-hazardous or free from risk.

Note:

This standard supersedes ARI Standard 470-1995.

Price $10.00 (M) $20.00 (NM) ©Copyright 2001, by Air-Conditioning and Refrigeration Institute
Printed in U.S.A. Registered United States Patent and Trademark Office
TABLE OF CONTENTS

SECTION PAGE

Section 1. Purpose ...............................................................................................................1

Section 2. Scope ..................................................................................................................1

Section 3. Definitions ............................................................................................................1

Section 4. Test Requirements................................................................................................2

Section 5. Rating Requirements.............................................................................................2

Section 6. Minimum Data Requirements for Published Ratings ...............................................4

Section 7. Marking and Nameplate Data...............................................................................5

Section 8. Conformance Conditions ......................................................................................5

TABLES

Table 1. Standard Rating Conditions ..................................................................................2

APPENDICES

Appendix A. References - Normative........................................................................................6

Appendix B. References - Informative.......................................................................................6

Appendix C. Method of Testing Desuperheater/Water Heaters - Normative ..............................7


ARI STANDARD 470-2001

DESUPERHEATER/WATER HEATERS
Section 1. Purpose 3.3 Net Heating Capacity. The useful heat exchanged
between the refrigerant vapor and the water being heated.
1.1 Purpose. The purpose of this standard is to This value is the product of the mass flow rate of water, the
establish, for Desuperheater/Water Heaters: definitions; test specific heat of water and the water temperature rise, Btu/h
requirements; rating requirements minimum data [W].
requirements for Published Ratings; marking and nameplate
data; and conformance conditions. 3.3.1 Clean Tube Capacity. This is the Net
Heating Capacity of the heat exchanger, Btu/h [W],
1.1.1 Intent. This standard is intended for the with clean tubes at the Rating Conditions chosen per
guidance of the industry, including manufacturers, Table 1.
engineers, installers, contractors and users.
3.4 Published Rating. A statement of assigned values of
1.1.2 Review and Amendment. This standard is those performance characteristics, under stated rating
subject to review and amendment as technology conditions, by which a unit may be chosen to fit its
advances. application. These values apply to all Desuperheater/Water
Heaters of like nominal size and type (identification)
produced by the same manufacturer. As used herein, the
Section 2. Scope term Published Rating includes all performance
characteristics shown on the unit or published in
2.1 Scope. This standard applies to specifications, advertising or other literature controlled by
Desuperheater/Water Heaters supplied as separate the manufacturer, at stated Rating Conditions.
components, as defined in Section 3 and using single
comp onent and azeotropic refrigerants only. 3.4.1 Application Rating. A rating based on tests
performed at Application Rating Conditions.
2.2 Exclusions. This standard does not apply to
Desuperheater/Water Heaters supplied as components of 3.4.2 Standard Rating. A rating based on tests
factory-assembled refrigeration or air conditioning units. performed at Standard Rating Conditions.
This standard does not apply to systems using zeotropic
refrigerants. 3.5 Rating Conditions. Any set of operating conditions
under which a single level of performance results and which
causes only that level of performance to occur.
Section 3. Definitions
3.5.1 Application Rating Conditions. Rating
All terms in this document shall follow the standard industry Conditions other than Standard Rating Conditions.
definitions in the current edition of ASHRAE Terminology of
Heating, Ventilation, Air Conditioning, and Refrigeration 3.5.2 Standard Rating Conditions. Rating
unless otherwise defined in this section. Conditions used as the basis of comparison for
performance characteristics.
3.1 Desuperheater/Water Heater. A factory-made
assembly of elements by which refrigerant vapor flow and 3.6 "Shall" or "Should." "Shall" or "should" shall be
water flow are maintained in such heat transfer relationship interpreted as follows:
that the refrigerant vapor is desuperheated and the water is
heated. 3.6.1 Shall. Where "shall" or "shall not" is used
for a provision specified, that provision is mandatory
3.2 Field Fouling Allowance. Provisions for anticipated if compliance with the standard is claimed.
Fouling Factor during use.
3.6.2 Should. "Should" is used to indicate
3.2.1 Fouling Factor. The thermal resistance due provisions which are not mandatory but which are
to fouling accumulated on the heat transfer surface. desirable as good practice.

1
ARI STANDARD 470-2001

Table 1. Standard Rating Conditions

Type Saturated Temperature Actual Temperature of Temperature of Entering Temperature of


System of Entering Refrigerant Entering Refrigerant Water Leaving Water
Vapor Vapor

°F °C °F °C °F °C °F °C

Air Cooled 125 51.7 220 104 90 and 120 32 and 140 60
48.8

Water 105 40.6 180 82.2 90 and 120 32 and 140 60


Cooled 48.8

Note: Ratings are for single component and azeotropic refrigerants only. Excluded are zeotropic refrigerants.

Section 4. Test Requirements 5.4 *Determination of Ratings. Ratings shall be


determined in accordance with the following:
4.1 Test Requirements. The tests shall be conducted in
accordance with the test procedure contained in Appendix C. 5.4.1 Clean Tube Ratings. Published Ratings shall
be determined by test with initially clean tubes at
conditions specified for the selected system in Table 1
Section 5. Rating Requirements and conducted in accordance with Appendix C. The
results of these tests shall be accepted as including a
5.1 Published Ratings. Published Ratings consist of Fouling Factor of zero.
Standard Ratings and Application Ratings. Such ratings shall
be based on tests of Desuperheater/Water Heaters with the 5.4.2 Fouled Tube Ratings. From the results of the
refrigerant specified in the ratings. clean tube tests, calculate the clean tube overall heat
transfer coefficient, Uc . Then, mathematically add the
5.2 Standard Ratings. Published Ratings shall include the specified Fouling Factor to the reciprocal of the clean
Standard Rating, given for one of the Standard Rating tube Uc and calculate the fouled ratings for
Conditions shown in Table 1 and properly identified as the publication, using the following methods, as
Standard Rating. Standard Ratings shall be based on tests applicable.
with initially clean tubes.
a. Tube-in-tube (counter flow arrangement
5.3 Application Ratings. Application Ratings give shown - parallel flow also covered).
performance data under operating conditions other than
those shown in Table 1. Application Ratings shall contain all
information shown in 6.2. When Application Ratings include
water-side Field Fouling Allowance(s) they shall be calculated
by the method specified in 5.4. Published Ratings shall be
subject to the tolerances of this standard. ingle tube pass shell-in-tube (counter
flow arrangement shown - parallel flow
5.3.1 Either Application Ratings or a method of also covered).
adjusting the clean tube ratings may be presented to
show the effect of various water-side Field Fouling
Allowances. These calculation methods or method of
adjusting these ratings shall be calculated in
accordance with 5.4.

_______________________________________________
*Note: Where steady state operation is in a condensing
mode, this analysis will be in error.

2
ARI STANDARD 470-2001

c. Coil-in-shell, single pass (counter flow The next step in determination of fouled ratings is the
arrangement shown - parallel flow also calculation of the total thermal resistance including
covered). fouling. This is found by adding the specified Fouling
Factor to the clean-tube overall resistance, as
illustrated below.

1. Refrigerant outside tubes (fouling


inside):

A. Basing calculations on outside


surface area:
 Ao 
R fo = Rco + r fi   4a
 Ai 
B. Basing calculations on inside
surface area:

R fi = Rci + r fi 4b
Obtain Uc from the following equation:
2. Refrigerant inside tubes (fouling
q
Uc = 1 outside):
A ⋅ (LMTD)c
A. Basing calculations on outside
surface area:
where (LMTD) c is defined by:
R fo = R co + r fo 5a

B. Basing calculations on inside


surface area:
 Ai 
R fi = R ci + r fo   5b
 Ao 
Now calculate the following:

Chot = ( m& ⋅ cp)r = Hot fluid (refrigerant)


capacity rate at Rating Conditions,
Btu/(h " °F) [W/°C]
for counterflow:
( t re − t wl ) − ( t rl − t wl ) Ccold = ( m& ⋅ cp)w = Cold fluid (water)
( LMTD ) c = capacity rate at Rating Conditions,
 t re − t wl 
ln   Btu/ (h " °F) [W/°C]
 t rl − t we 
2a Cmin = The smaller of Chot or Ccold
for parallel flow:
( t re − t we ) − ( t rl − t wl ) Cmax = The larger of Chot or Ccold
( LMTD ) c = 2b
 t re − t we  q max = Cmin (t re - twe), Btu/h [W]
ln  
 t rl − t wl  A
6
NTU = , dimensionl ess
The total thermal resistance is equal to the reciprocal R f ⋅ C min
of the overall coefficient of heat transfer: where Rf is based on area A.
1 A ⋅ ( LMTD )c
Rc= = 3
Uc q

3
ARI STANDARD 470-2001

The actual heat transfer under fouled conditions, q f, is NTU = Number of exchanger heat transfer
calculated from units
q = Total heat transfer rate, Btu/h [W]
q f = ε qmax 7 R = Total thermal resistance, hAft 2A°F/Btu
[m2@°C/W]
where ε is determined for either counterflow or parallel r = Individual thermal resistance term,
flow arrangements of the exchanger types shown in hAft 2A°F/Btu [m2@°C/W]
4.4.2, items a, b and c. t = Temperature, °F [°C]
U = Overall heat transfer coefficient,
Counterflow, where Cmin ≠ Cmax.: Btu/(hAft 2A°F) [W/(m2@°C)]

− NTU  1 − Cmin / C max  Subscripts:


1 − EXP  
c = Clean
ε= 8a
− NTU  1 − Cmin / Cmax  e = Entering
1 − (C min / Cmax ) EXP  
f = Fouled or fouling
i = Inside
where Cmin = Cmax: l = Leaving
o = Outside
NTU r = Refrigerant
ε= 8b
(1 + NTU ) w = Water

5.6 Tolerances. To comply with this standard, published


Parallel flow: Net Heating Capacity shall be based on data obtained in
− NTU ( 1 + C min / C max )
accordance with the provisions of this standard, and shall be
1 − EXP such that any production unit selected at random and tested
ε= 8c
1+ ( C min / C max ) in accordance with this standard shall have a Net Heating
Capacity not less than 95% of the Published Rating, a water
Now having the actual heat transfer under fouled pressure drop not more than 110% of the published water
conditions, the leaving water and refrigerant pressure drop and a refrigerant pressure drop not more than
temperatures can be calculated from: 110% of the published refrigerant pressure drop.

qf
t wl = t we + 9a
Section 6. Minimum Data Requirements for
Ccold
Published Ratings
qf
t rl = t re − 9b 6.1 Minimum Data Requirements for Published Ratings.
C hot As a minimum, Published Ratings shall include all Standard
Ratings. All claims to ratings within the scope of this
standard shall include the statement “Rated in accordance
The combination of q f, twe and tre define the fouled
with ARI Standard 470.” All claims to ratings outside the
ratings at the given operating conditions.
scope of this standard shall include the statement “Outside
the scope of ARI Standard 470.” Wherever Application
5.5 Symbols and Subscripts. The symbols and subscripts
Ratings are published or printed, they shall include a
used in Equations 1 through 9 are as follows:
statement of the conditions at which the ratings apply.
Symbols:
6.2 Published Ratings. Published Ratings shall state all
2 2 the pertinent operating conditions and shall include the
A = Total heat transfer area, ft [m ]
& A cp), following:
C = Flow-stream capacity rate (m
Btu/ (h A °F) [W/°C]
a. Refrigerant designation(s) per ANSI/ASHRAE
cp = Specific heat at constant pressure,
Standard 34 with Addenda
Btu/ (lb@°F) [kJ/ (kg@°C)]
b. Entering refrigerant temperature, °F [°C]
e = Exchanger heat transfer effectiveness
c. Entering refrigerant pressure, psig [kPa gage]
EXP = Base of natural logarithm, e
d. Net Heating Capacity, Btu/h [W]
LMTD = Log mean temperature difference, °F
e. Water flow rate, gpm [L/s]
[°C]
f. Water pressure drop, psi or ft H2O [kPa]
m& = Fluid mass flow rate, lb/h [kg/s]
g. Refrigerant side pressure drop, psi [kPa]
4
ARI STANDARD 470-2001

h. Refrigerant mass flow rate, lb/h [kg/s] Section 7. Marking and Nameplate Data
i. Fouling Factor (water-side), ft 2AhA°F/Btu [m2A°C/W]
7.1 Marking and Nameplate Data. As a minimum, each
Plus at least one of the following: Desuperheater/Water Heater shall have the following
information shown in a conspicuous place:
j. Entering Water Temperature, °F [°C]
k. Leaving Water Temperature, °F [°C] a. Name of manufacturer
b. Manufacturer's model number
6.3 Published Ratings shall be accompanied by the c. Design working pressure for the water side
following information: d. Design working pressure for the refrigerant side

a. Design pressures for water-side and refrigerant-


side, psig [kPa gage] Section 8. Conformance Conditions
b. Minimum water flow rate, gpm [L/s], at minimum
entering water temperature, °F [°C] 8.1 Conformance. While conformance with this standard
c. Maximum recommended flow rate, gpm [L/s] is voluntary, conformance shall not be claimed or implied for
d. If only clean tube ratings are published, a products or equipment within its Purpose (Section 1) and
statement shall be included to contact the Scope (Section 2) unless such claims meet all of the
manufacturer if fouled tube ratings are required requirements of the standard.

5
ARI STANDARD 470-2001

APPENDIX A. REFERENCES - NORMATIVE


A1 Listed here are all standards, handbooks and other A1.3 ASHRAE Handbook – Fundamentals, 2001,
publications essential to the formation and implementation American Society of Heating, Refrigerating and Air-
of the standard. All references in this appendix are Conditioning Engineers, Inc., 1791 Tullie Circle N.E.,
considered as part of the standard. Atlanta, GA 30329, U.S.A.

A1.1 ANSI/ASHRAE Standard 34-1997 with A1.4 ASHRAE Terminology of Heating,


Addenda, Designation and Safety Classification of Ventilation, Air Conditioning and Refrigeration,
Refrigerants, 1997, American Society of Heating, Second Edition, 1991, American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc., Refrigerating and Air-Conditioning Engineers, Inc.,
1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. 1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A.

A1.2 ANSI/ASHRAE Standard 41.1-1986 (RA 91), A1.5 ASME Standard PTC 19.5-1972, Application
Standard Method for Temperature Measurement, Part II of Fluid Meters, 1972, American Society of
1991, American Society of Heating, Refrigerating and Mechanical Engineers, 345 East 47th Street, New
Air-Conditioning Engineers, Inc., 1791 Tullie Circle York, NY 10017, U.S.A.
N.E., Atlanta, GA 30329, U.S.A.

APPENDIX B. REFERENCES - INFORMATIVE

B1 Listed here are standards, handbooks and other B1.1 ANSI/ASHRAE Standard 41.2-1987 (RA 92),
publications which may provide useful information and Standard Methods for Laboratory Air Flow
background but are not considered essential. References in Measurement, 1987, American Society of Heating,
this appendix are not considered part of the standard. Refrigerating and Air-Conditioning Engineers, Inc.,
1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A.

6
ARI STANDARD 470-2001

APPENDIX C. METHOD OF TESTING


DESUPERHEATER/WATER HEATERS – NORMATIVE
C1 Purpose. This appendix prescribes methods of testing d. Water-side pressure drop, psi
for rating Desuperheater/Water Heaters. or ft H2O [kPa]
e. Refrigerant-side pressure drop,
C2 Scope. This appendix applies to Desuperheater/Water psi [kPa]
Heaters supplied as a separate component. f. Water flow rate, gpm [L/s]
g. Refrigerant mass flow rate, lb/h
C3 Definitions. [kg/s]
h. Ambient temperature, °F [°C]
C3.1 Definitions. Definitions of this appendix are
identical with those in Section 3 of this standard. C5.1.2 The heat balance shall be calculated
by the following:
C4 Test Results.
a. Multiply the mass flow rate of
C4.1 Test results shall be expressed in the water by the specific heat and
following terms: temperature difference between
entering and leaving water (Net
a. Net Heating Capacity, Btu/h [W] Heating Capacity, Equation C4)
b. Entering water temperature, °F [°C] and adding to this the heat lost
c. Leaving water temperature, °F [°C] by the refrigerant through the
d. Entering refrigerant temperature, °F [°C] external surfaces of the heat
e. Water flow rate, gpm [L/s] exchanger (Equation C1)
f. Refrigerant mass flow rate, lb/h [kg/s]
g. Water-side pressure drop through heat b. Multiply the refrigerant mass
exchanger, psi or ft H2O [kPa] flow rate by the enthalpy
h. Refrigerant-side pressure drop through differences between entering
heat exchanger, psi [kPa] and leaving refrigerant
i. Pressure of refrigerant entering heat (Equation C3).
exchanger, psig [kPa gage]
j. Refrigerant designation(s), per A heat balance calculated between C5.1.2a
ANSI/ASHRAE Standard 34 with and C5.1.2b shall be within 5%.
Addenda
C5.1.3 The water flow rate shall be
C4.2 The test record shall include the date, determined in accordance with C6.4.1.
observers' names, essential identifying physical data
of the Desuperheater/Water Heater tested, refrigerant C5.1.4 Refrigerant flow rate shall be
used, all test readings, reference to instrument determined in accordance with C6.4.2.
calibrations and computations, and the determined
results. C5.1.5 The enthalpy difference between
the entering and leaving refrigerant shall be
C5 Test Methods. determined from temperature and pressure
measurements and the applicable
C5.1 Standard Test Methods. thermodynamic properties of the refrigerant.

C5.1.1 Tests shall consist of measurement C5.1.6 The heat lost through the external
of the following at specified conditions: surfaces of the heat exchanger to the ambient
air shall be determined by:
a. Entering and leaving water
temperatures, °F [°C] A ⋅ LMTD
b. Entering and leaving refrigerant qo = C1
R
temperatures, °F [°C] and
c. Entering refrigerant pressure,
psig [kPa gage] x 1
R= + C2
k hs
7
ARI STANDARD 470-2001

C5.1.7 The heat absorbed by the water is C6.4.2.2 A refrigerant calorimeter


the product of the mass flow, the specific may also be used to calculate the
heat and the temperature difference between refrigerant mass flow rate. In this
entering and leaving water (Equation C4). approach, the calorimeter is used to
accurately measure the amount of
C5.1.8 The heat rejected from the heat required to evaporate and
refrigerant is the product of the refrigerant superheat the refrigerant flowing
mass flow rate and the enthalpy difference through it. The refrigerant mass
between the refrigerant entering and leaving flow rate is determined by dividing
the Desuperheater. the heat input, including leakage
losses, by the enthalpy difference
q = m& r (H e − H l ) C3 between the entering and leaving
refrigerant.
C6 Instruments, Test Apparatus, and Thermodynamic
C6.4.2.3 Accuracy of either the
Properties.
direct or indirect refrigerant mass
flow rate measurement shall be
C6.1 General.
within 2% of the range of mass
flows calculated.
C6.1.1 Instruments, whose types and
accuracies are listed below, shall be
C6.4.2.4 Instruments shall be
calibrated against standards before and after
applied and used in accordance
each test.
with ASME PTC 19.5.
C6.2 Temperature Measuring Instruments.
C6.4.3 Thermodynamic Properties of
Refrigerants. Thermodynamic Properties of
C6.2.1 Temperature measurements shall be
Refrigerants shall be obtained from the
made in accordance with ANSI/ASHRAE
current issue of the ASHRAE Handbook -
Standard 41.1.
Fundamentals.
C6.3 Pressure Measuring Instruments.
C7 Test Procedure
C6.3.1 All pressure measuring instruments
C7.1 General
shall have accuracy within the limits of "1%
of the absolute pressure readings or "2% of
C7.1.1 The Desuperheater/Water Heater,
the differential pressure readings.
the selected instruments, and test apparatus
are assembled, connected, tested,
C6.4 Flow Measuring Instruments.
dehydrated, evacuated, and charged with
refrigerant. If necessary, a refrigerant
C6.4.1 Water Flow Measuring Instruments.
superheater may be used, to assure accuracy
of measurements and to obtain specified
C6.4.1.1 Accuracy of flow meter
conditions.
shall be within 2% over the range of
flows measured.
C7.1.2 The water-side surfaces of the
heat exchangers should be cleaned
C6.4.2 Refrigerant Flow Measuring
immediately prior to the test. This method
Instruments.
gives clean tube test results.
C6.4.2.1 Refrigerant flow rate
C7.1.3 The refrigerant system should be
measurements shall be made with
checked for non-condensables. Non-
one or more of the following
condensables present for a test intended for
instruments.
rating should not exceed that amount which
increases the condenser pressure more than
a. Liquid refrigerant flow meter
the equivalent of 0.5 °F [0.3 °C].
b. Gaseous refrigerant flow meter

8
ARI STANDARD 470-2001

C7.2 Operation and Limits. C8 Computation of Results.

C7.2.1 Start the system and maintain the C8.1 The Net Heating Capacity, q, is given as
specified conditions in accordance with the follows:
following tolerances:
q =(m
& ⋅ c p ⋅ ∆ t )w C4a
a. The arithmetic average of
pressure readings used to
[ q = 1000( m
& ⋅ c p ⋅ ∆ t )w ] C4b
determine refrigerant enthalpies
and refrigerant saturated
temperatures shall not vary C9 Symbols and Subscripts. The symbols and subscripts
from the required values, by used in Equations C1 through C4 are as follows:
more than 2% of their absolute
values, nor shall the individual Symbols:
pressure readings vary by more
than this amount from the A = External surface area, ft 2 [m2]
average value. Pressure cp = Specific heat at constant pressure, Btu/(lb ⋅ °F)
readings shall be converted to [kJ/(kg ⋅ °C)]
absolute values to determine ? t = Temperature difference between the entering
refrigerant saturated and leaving water, °F [°C]
temperatures. H = Enthalpy of refrigerant, Btu/lb [J/kg]
h = Film coefficient, defined as 2 Btu/(h ⋅ ft 2 ⋅ °F)
b. The arithmetic average of [11W/(m ⋅ °C)]
temperature readings of water k = Thermal conductivity of insulation,
and refrigerant entering and Btu/(hAftA°F) [W/(m@°C)]
leaving the Desuperheater/ LMTD = Log mean temperature difference, °F [°C]
Water Heater shall not vary m& = Mass flow rate, lb/h [kg/s]
from the specified value by q = Heat transfer rate, Btu/h [W]
more than 1.0°F [0.6°C] nor R = Total thermal resistance, h ⋅ ft 2 ⋅ °F/Btu
shall the individual readings [m2 ⋅ °C/W]
vary by more than this amount x = Insulation thickness, ft [m]
from the average value.
Subscripts:
C7.2.2 After establishment of steady flow
conditions, all required readings shall be e = Entering
taken at intervals of not less than fifteen l = Leaving
minutes, and the test shall be continued until o = External surfaces
two consecutive sets of readings are within r = Refrigerant
the specified limits. s = Surface
w = Water

You might also like