Substation
Design Analysis:
Calculated Current Primary: 7500/1.732(69) = 62.75A
Equipment Specification:
A. Private Pole
3.0 Lightning Arrester or Surge Arrester:
Minimum Arrester: 1.25 x L-N = 1.25 ( 69/1.732) = 49.8 KV
Use Industrial Standard ---------------- 48KV
Refer to Meralco Std.
Type: Station
Connection: Grounded Wye, 3 Phase, 4 Wire Primary Voltage
Rating: 48 KV
General Specification (Meralco)
Type: Station Type rated @ 48KV
Ur: 27 KV
MOOV: 22 KV
Discharge Level : Class I