ETAP Page: 1
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
Static
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual
Load @ T=0¯
Bus Initial Voltage Constant kVA Constant Z Constant I Generic
Total Number of Buses: 11 1.553 0.962 0.938 0.582 0.000 0.000 0.000 0.000
0.000 0.000
Project:
ETAP Page: 4
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
BOP-SUS-1A 2.500 4.160 0.480 5.75 10.67 0 0 7.5 0 0 6.1813 Dyn 0.000
BOP-SUS-1B 2.500 4.160 0.480 5.75 10.67 0 0 7.5 0 0 6.1813 Dyn 0.000
LIQUEFACTION-SUS-1A 1.000 4.160 0.480 5.75 5.79 0 0 7.5 0 0 6.1813 Dyn 0.000
LIQUEFACTION-SUS-1B 1.000 4.160 0.480 5.75 5.79 0 0 7.5 0 0 6.1813 Dyn 0.000
Branch Connections
% Impedance
Machine Connected Bus Rating (Machine Base)
ID Type ID MVA kV R X" X' *
Switching Motors
Amine Circulation Pump1 Ind. 1 MTR BUS 500.0 4.160 1800 60.3 92.1 93.2 650.00 18.89 0.00 0.00
Project:
ETAP Page: 8
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
Sequence of Events
Load Change
Time Event Switching Load % Loading Time Motor Load Static Load
Name Time ID Type Action Category Start Final Begin End MW Mvar MW Mvar
MS 0.200 Amine Circulation Pump1 Ind. Motor Start Normal 100.0 100.0 0.00 0.00
Project:
ETAP Page: 9
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
BOP MAIN A BUS 0.480 98.697 -1.0 0 0 0 0 MVSG-1A -0.724 -0.449 1037.9 85.0
BOP MAIN B BUS 0.480 98.263 -1.3 0 0 0 0 MVSG-1A -0.957 -0.593 1378.8 85.0
ESS-MCC 0.480 98.263 -1.3 0 0 0.270 0.167 LVSG-1B -0.270 -0.167 388.4 85.0
LIQUEFACTION MAIN A 0.480 98.050 -1.2 0 0 0 0 MVSG-1A -0.391 -0.243 564.9 85.0
BUS
LIQUEFACTION-SWG-1A 0.391 0.243 564.9 85.0
LIQUEFACTION MAIN B 0.480 98.063 -1.2 0 0 0 0 MVSG-1A -0.389 -0.241 561.1 85.0
BUS
LIQUEFACTION-SWG-1B 0.389 0.241 561.1 85.0
LIQUEFACTION-SWG-1A 0.480 98.050 -1.2 0 0 0.391 0.243 LIQUEFACTION MAIN A -0.391 -0.243 564.9 85.0
BUS
LIQUEFACTION-SWG-1B 0.480 98.063 -1.2 0 0 0.389 0.241 LIQUEFACTION MAIN B -0.389 -0.241 561.1 85.0
BUS
LVSG-1A 0.480 98.697 -1.0 0 0 0.724 0.449 BOP MAIN A BUS -0.724 -0.449 1037.9 85.0
LVSG-1B 0.480 98.263 -1.3 0 0 0.688 0.426 BOP MAIN B BUS -0.957 -0.593 1378.8 85.0
MTR BUS 4.160 100.000 0.0 0 0 0 0 MVSG-1A 0.000 0.000 0.0 0.0
* MVSG-1A 4.160 100.000 0.0 0 0 0 0 BOP MAIN A BUS 0.726 0.467 119.8 84.1
* Gen1 4.160 112.701 8.4 1.246 1.096 0 0 MVSG-1A 1.246 1.096 204.4 75.1
* Gen2 4.160 112.701 8.4 1.246 1.096 0 0 MVSG-1A 1.246 1.096 204.4 75.1
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
Project:
ETAP Page: 10
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
BOP MAIN A BUS 0.480 81.402 -3.1 0 0 0 0 MVSG-1A -0.628 -0.389 1091.7 85.0
BOP MAIN B BUS 0.480 81.079 -3.3 0 0 0 0 MVSG-1A -0.770 -0.477 1343.9 85.0
ESS-MCC 0.480 81.079 -3.3 0 0 0.188 0.117 LVSG-1B -0.188 -0.117 328.2 85.0
LIQUEFACTION MAIN A 0.480 80.408 -3.6 0 0 0 0 MVSG-1A -0.388 -0.240 682.2 85.0
BUS
LIQUEFACTION-SWG-1A 0.388 0.240 682.2 85.0
LIQUEFACTION MAIN B 0.480 80.424 -3.6 0 0 0 0 MVSG-1A -0.385 -0.239 677.6 85.0
BUS
LIQUEFACTION-SWG-1B 0.385 0.239 677.6 85.0
LIQUEFACTION-SWG-1A 0.480 80.408 -3.6 0 0 0.388 0.240 LIQUEFACTION MAIN A -0.388 -0.240 682.2 85.0
BUS
LIQUEFACTION-SWG-1B 0.480 80.424 -3.6 0 0 0.385 0.239 LIQUEFACTION MAIN B -0.385 -0.239 677.6 85.0
BUS
LVSG-1A 0.480 81.402 -3.1 0 0 0.628 0.389 BOP MAIN A BUS -0.628 -0.389 1091.7 85.0
LVSG-1B 0.480 81.079 -3.3 0 0 0.582 0.361 BOP MAIN B BUS -0.770 -0.477 1343.9 85.0
MTR BUS 4.160 82.776 -1.8 0 0 0.365 1.900 MVSG-1A -0.365 -1.900 324.4 18.9
* MVSG-1A 4.160 82.776 -1.8 0 0 0 0 BOP MAIN A BUS 0.630 0.409 126.0 83.8
* Gen1 4.160 112.701 8.4 1.305 2.542 0 0 MVSG-1A 1.305 2.542 351.8 45.7
* Gen2 4.160 112.701 8.4 1.305 2.542 0 0 MVSG-1A 1.305 2.542 351.8 45.7
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
Project:
ETAP Page: 11
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
BOP MAIN A BUS 0.480 96.905 -2.4 0 0 0 0 MVSG-1A -0.713 -0.442 1041.3 85.0
BOP MAIN B BUS 0.480 96.482 -2.8 0 0 0 0 MVSG-1A -0.936 -0.580 1373.3 85.0
ESS-MCC 0.480 96.482 -2.8 0 0 0.260 0.161 LVSG-1B -0.260 -0.161 382.1 85.0
LIQUEFACTION MAIN A 0.480 96.226 -2.7 0 0 0 0 MVSG-1A -0.391 -0.242 575.0 85.0
BUS
LIQUEFACTION-SWG-1A 0.391 0.242 575.0 85.0
LIQUEFACTION MAIN B 0.480 96.239 -2.7 0 0 0 0 MVSG-1A -0.388 -0.241 571.1 85.0
BUS
LIQUEFACTION-SWG-1B 0.388 0.241 571.1 85.0
LIQUEFACTION-SWG-1A 0.480 96.226 -2.7 0 0 0.391 0.242 LIQUEFACTION MAIN A -0.391 -0.242 575.0 85.0
BUS
LIQUEFACTION-SWG-1B 0.480 96.239 -2.7 0 0 0.388 0.241 LIQUEFACTION MAIN B -0.388 -0.241 571.1 85.0
BUS
LVSG-1A 0.480 96.905 -2.4 0 0 0.713 0.442 BOP MAIN A BUS -0.713 -0.442 1041.3 85.0
LVSG-1B 0.480 96.482 -2.8 0 0 0.676 0.419 BOP MAIN B BUS -0.936 -0.580 1373.3 85.0
MTR BUS 4.160 98.212 -1.4 0 0 0.400 0.169 MVSG-1A -0.400 -0.169 61.4 92.1
* MVSG-1A 4.160 98.212 -1.4 0 0 0 0 BOP MAIN A BUS 0.715 0.460 120.2 84.1
* Gen1 4.160 112.701 8.4 1.433 1.269 0 0 MVSG-1A 1.433 1.269 235.7 74.9
* Gen2 4.160 112.701 8.4 1.433 1.269 0 0 MVSG-1A 1.433 1.269 235.7 74.9
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
Project:
ETAP Page: 12
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
% Alert Settings
Critical Marginal
Starting Motors/MOV
Critical Report
DeviceID Type Alert Condition Rating/Limit Unit Operating % Operating T Begin Duration
Gen1 Generator Generator Rating Over Rating 2.059 MVA 2.098 101.9 0.200 0.000
Gen2 Generator Generator Rating Over Rating 2.059 MVA 2.098 101.9 0.200 0.000
BOP MAIN A BUS LV Bus Bus Voltage Under Voltage 0.480 kV 0.391 81.4 0.200 0.000
BOP MAIN B BUS LV Bus Bus Voltage Under Voltage 0.480 kV 0.389 81.1 0.200 0.000
ESS-MCC LV Bus Bus Voltage Under Voltage 0.480 kV 0.389 81.1 0.200 0.000
LIQUEFACTION MAIN A BUS LV Bus Bus Voltage Under Voltage 0.480 kV 0.386 80.4 0.200 0.000
LIQUEFACTION MAIN B BUS LV Bus Bus Voltage Under Voltage 0.480 kV 0.386 80.4 0.200 0.000
LIQUEFACTION-SWG-1A LV Bus Bus Voltage Under Voltage 0.480 kV 0.386 80.4 0.200 0.000
LIQUEFACTION-SWG-1B LV Bus Bus Voltage Under Voltage 0.480 kV 0.386 80.4 0.200 0.000
LVSG-1A LV Bus Bus Voltage Under Voltage 0.480 kV 0.391 81.4 0.200 0.000
LVSG-1B LV Bus Bus Voltage Under Voltage 0.480 kV 0.389 81.1 0.200 0.000
MTR BUS MV Bus Bus Voltage Under Voltage 4.160 kV 3.443 82.8 0.200 0.000
MVSG-1A Generator Bus Bus Voltage Under Voltage 4.160 kV 3.443 82.8 0.200 0.000
MVSG-1A MV Bus Bus Voltage Under Voltage 4.160 kV 3.443 82.8 0.200 0.000
Project:
ETAP Page: 13
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
Marginal Report
DeviceID Type Alert Condition Rating/Limit Unit Operating % Operating T Begin Duration
Amine Circulation Pump1 Motor Motor Voltage Under Voltage 4.160 kV 3.443 82.8 0.200 0.000
MTR BUS Motor Bus Bus Voltage Under Voltage 4.160 kV 3.443 82.8 0.200 0.000
Project:
ETAP Page: 14
12.5.0C
Location: Date: 05-05-2015
Contract: SN: KIEWIT-ENG
Engineer: Revision: Base
Study Case: MS
Filename: Alaska LNG Rev B Config.: MS - Normal
The tabulated plots were not generated because the option of 'Skip Tabulated Plots' in the study case was checked.
To generate tabulated plots, you need to uncheck this option in the Info page of Motor Starting Study Case.