Professional Documents
Culture Documents
Substation Operation and Maintenance
Substation Operation and Maintenance
Operation and
Maintenance
i
Table of Contents
C ontents
1 Substations and Switchyards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction to Substations and Switchyards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Basic Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Substations: Protective Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Regulation, Monitoring, and Communication Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Switchyards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Switchyard Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
iii
Substation Operation and Maintenance
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Test Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
iv
Operating Mechanism Maintenance, Part 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Air-Magnetic and Vacuum Breaker Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Oil Circuit Breaker Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
v
Substation Operation and Maintenance
vi
27 Substation Battery Chargers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Charger Functions and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
DC Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 420
Freshening Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Float and Equalizing Charges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Charger Inspection and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426
vii
Substations and Switchyards
C hapter
1
Substations and Switchyards
Electricity is a necessity of modern life. Transmission and distribution (T&D) systems provide electricity
to consumers wherever and whenever it is needed. Two of the major components of a typical T&D system
are substations and switchyards.
This chapter examines the role that substations and switchyards play in a T&D system and discusses some
of the equipment that is commonly used in substations and switchyards. Security and safety precautions
associated with substations and switchyards are also covered when appropriate.
1
Substations and Switchyards
Potential transformers
Potential transformers are devices that reduce line
voltage to a proportionally lower and safer voltage
for metering and relaying. A potential transformer, Shunt reactor
like the one shown in Figure 1-34, normally has a Figure 1-33. Shunt reactor.
large porcelain bushing that insulates the higher
voltage conductor going into the transformer. The
transformer itself is usually enclosed in a metal
housing. The output wires of the transformers are
enclosed in conduit to protect them. These wires Bushing
connect to meters or relaying equipment in a
control house.
Potential transformers come in many shapes
and sizes. They are sometimes difficult to distin-
guish from other devices such as some current
transformers and surge arrestors. For this reason,
potential transformers are often identified in Transformer housing
Current Transformers
In contrast to potential transformers, which Conduit
reduce line voltage, current transformers reduce Figure 1-34. Potential transformer.
line current to a proportionally lower current
for metering or relaying. Current transformers
can look like potential transformers or surge arrestors. One identifying feature on the current
transformer shown in Figure 1-36 is a large canister on top of the bushing with a conductor
11
Power Transformers, Part 1
49
Power Transformers, Part 2
Next, both selector switch A and selector switch B are rotated clockwise, so that selector switch
B slides over to tap 2, and selector switch A slides across tap N to the opposite end of the tap.
(Selector switch A remains on tap N.) Since current is not flowing through selector switch B,
there is no arcing as the switch changes taps.
Then, transfer switch B is closed, so that current flows across the reversing switch and the raise
tap, labeled R, from left to right through a portion of the tapped winding, across tap 2 and
selector switch B, across transfer switch B, and out lead X0. Current continues to flow across the
neutral tap, across selector switch A, across transfer switch A, and out lead X0.
Transfer switch A is then opened to interrupt current flow through selector switch A. Both
selector switch A and selector switch B are rotated clockwise, so that selector switch A slides over
to tap 2, and selector switch B slides across tap 2 to the opposite end of the tap.
Once selector switch A is on tap 2, transfer switch A is closed, so that current again flows across
selector switch A and transfer switch A and out lead X0. This completes the tap change. The
new tap position is shown in Figure 4-18. With
the reversing switch in the Raise position and the
selector switches on tap 2, a portion of the tapped
winding is added to the secondary winding. This
changes the ratio of secondary turns to primary
turns and effectively raises the secondary voltage.
The first tap position that adds turns to the
secondary winding is called one-raise.
As the selector switches are moved clockwise to
the other taps, turns are added to the secondary to
raise the secondary voltage. When all of the tapped Figure 4-18. Tap changer at one-raise position.
windings are added, the tap changer is at the full-
raise position.
Figure 4-19 shows the tap changer at full-raise.
To lower the secondary voltage, the selector
switches are rotated counterclockwise back to the
neutral tap. Then, the reversing switch slides from
the Raise position (R) to the Lower position (L),
and the selector switches rotate counterclockwise
from tap N to tap 4.
Figure 4-20 shows the new tap position called:
on-lower. Figure 4-19. Tap changer at full-raise position.
When the reversing switch is in the Lower position, and the selector switches are on tap 4,
current flows from left to right across the secondary winding, across the reversing switch and the
Lower tap, from right to left through part of the tapped winding, across tap 4 and the selector
switches, across the transfer switches, and out lead X0.
65
Power Transformer Insulation Resistance Testing
between the high voltage winding and ground to be tested. Although the low voltage winding
is not included in this test, current leakage to the low voltage winding could affect the resis-
tance measurement. To avoid this problem, a lead is connected to the guard (G) terminal of the
megohmmeter and the low voltage (X) terminal of the transformer. The guard diverts current
that leaks to the low voltage windings so that this leakage current is not included in the test
measurement.
Connections for Testing the Resistance Between the Low Voltage Winding and Ground
The connections for testing the insulation resis-
tance between the low voltage winding and
ground are illustrated in Figure 8-18. One test
lead is connected to the earth (-) terminal of the
megohmmeter and to a transformer case ground.
Another test lead is connected to the line (+)
terminal of the megohmmeter and to the low
voltage (X) terminal of the transformer. A lead is
also connected between the guard (G) terminal
of the megohmmeter and the high voltage (H)
terminal of the transformer to divert current Figure 8-18. Connections for testing insulation
that leaks to the high voltage winding so that this resistance between the low voltage winding
leakage current is not measured. and ground.
121
Circuit Breaker Operation
161
Circuit Breaker Operation
As the moving contact assembly moves away Figure 11-22. Gas-puffer breaker interruptor –
from the stationary assembly, the SF6 gas in the closed.
compression chamber is compressed. Compressing
Main contacts
the gas increases its dielectric strength. Eventually, separate
Gas
the moving contact assembly moves so far that the comnpressing
arcing contact fingers separate, and an arc forms in chamber
(Figure 11-24).
When the arcing fingers separate, the compres-
sion chamber opens, and thehigh-pressure gas Arcing contacts
still meet
flows through the arc to the low pressure areas
of the interruptor. The dielectric strength of the
high-pressure gas weakens the arc. As the gas flows
Figure 11-23. Gas-puffer breaker interruptor –
through the arc, the arc is lengthened and cooled, main contacts open.
until it eventually extinguishes at a current zero.
Arc
167
New Circuit Breaker Inspections and Tests
211
Substation Operation and Maintenance
294
Voltage Regulators
333
Protective Relays, Transmission Systems
Zoned Protection
To prevent undesirable operations, a distance relay Figure 23-38. Zone 1 protection.
is generally set to protect approximately 90% of
Unprotected line
a line section. This protected section is typically sections
referred to as Zone 1 (Figure 23-38).
To protect line sections between substations,
additional Zone 1 sections can be set up (Figure
23-39). However, with this type of protection,
approximately 10% of each line section is left
unprotected. Figure 23-39. Multiple Zone 1 protection.
365
Substation Operation and Maintenance
Sensing Equipment
Sensing equipment is equipment that changes a condition such as voltage or current to a value
or signal that can be measured. For example, potential transformers (Figure 24-1) change, or
transform, line voltage to a proportionally lower voltage for measurement.
Another example of sensing equipment is a current transformer. Current transformers (Figure
24-2) transform line current to a proportionally lower current for measurement.
Measuring Equipment
The signals from sensing equipment are typically sent to measuring equipment and control-
ling equipment. Measuring equipment measures the signal provided by sensing equipment and
indicates the value of the condition being sensed. For example, a meter such as the ammeter
shown in Figure 24-3 indicates the value of current it receives from a current transformer.
Another example of measuring equipment is a recording meter, such as the one shown in Figure
24-4. A recording meter measures signals from sensing equipment and records the values of the
signals over a period of time.
Controlling Equipment
Controlling equipment detects the signals it gets from sensing equipment, and, if a signal is
different from a preset value, provides a signal that operates various other equipment. An
example of controlling equipment is an overcurrent relay, such as the one shown in Figure 24-5.
An over current relay detects current that it receives from a current transformer. If the current
376
Substation Operation and Maintenance
If alternating current to the charger is interrupted for any reason, the battery will instantly
provide direct current to the steady, continuous loads and, as required, to the intermittent loads.
It will continue to supply the loads until alternating current is restored or until the battery is
fully discharged.
396
Substation Operation and Maintenance
432