Professional Documents
Culture Documents
testing
Application Note
Introduction
Insulation resistance testers
can be used to determine the
integrity of windings or cables
in motors, transformers, switch-
gear, and electrical installations.
The test method is determined
by the type of equipment being
tested and the reason for test-
ing. For instance, when testing
electrical cabling or switchgear
(low-capacitance equipment)
the time-dependent capacitive
leakage and absorption leakage
currents become insignificant
and decrease to zero almost
instantly. A steady conductive
leakage current flow is reached
almost instantly (a minute or
less) providing perfect condi-
tions for the spot-reading/short-
time resistance test. (For more
detailed information on leakage
currents and resistance tests see
the following sections: What Is
Insulation Resistance & Leak-
age Currents and Predictive
Maintenance Tests).
On the other hand, when
the equipment to be tested is a
long run of cable, large motor,
or generator (high-capacitance Installation testing Maintenance testing
equipment) the time-depen- The most important reason for The second most important rea-
dent currents will last for hours. testing insulation is to insure son for insulation testing is to
These currents will cause the public and personal safety. By protect and prolong the life
meter readings to change con- performing a high dc voltage of electrical systems and mo-
stantly, making it impossible to test between de-energized cur- tors. Over the years, electrical
obtain an accurate steady read- rent-carrying (hot), grounded, systems are exposed to envi-
ing. This condition can be and grounding conductors, you ronmental factors such as dirt,
overcome by using a test that can eliminate the possibility grease, temperature, stress, and
establishes a trend between of having a life-threatening vibration. These conditions can
readings, such as the step volt- short circuit or short to ground. lead to insulation failure, result-
age or dielectric-absorption This test is usually performed ing in loss of production or even
test. These tests do not depend after the initial installation of fires. Periodic maintenance tests
on a single reading but on a the equipment. This process can provide valuable informa-
collection of relative readings. will protect the system against tion about the state of deteriora-
It would be a waste of time to miswired and defective equip- tion and will help in predicting
perform these tests on low-ca- ment, and it will insure a high possible failure of the system.
pacitance equipment since the quality installation, customer Correcting problems will result
time-dependent currents dimin- satisfaction, and protect against not only in a trouble-free sys-
ish quickly, resulting in all the fire or shock. tem, but will also extend the
measurements being the same. operating life for a variety of
equipment.
Before measuring sulation surface, and, in some ture (resistance goes down
cases will be absorbed by the as temperature goes up), the
In order to obtain meaningful material. recorded readings are altered
insulation resistance measure- by changes in the temperature
ments, the electrician should 3. The surface of the conductor
is free of carbon and other of the insulating material.
carefully examine the system It is recommended that tests
under test. The best results are foreign matter that can be-
come conductive in humid be performed at a standard
achieved when: conductor temperature of
conditions.
1. The system or equipment is 20 °C (68 °F). As a rule of
taken out of service and 4. Applied voltage is not too thumb, when comparing read-
disconnected from all other high. When testing low- ings to 20 °C base tempera-
circuits, switches, capacitors, voltage systems; too much ture, double the resistance
brushes, lightning arrestors, voltage can overstress or for every 10 °C (18 °F) above
and circuit breakers. Make damage insulation. 20 °C or halve the resistance
sure that the measurements 5. The system under test has for every 10 °C below 20 °C
are not affected by leakage been completely discharged in temperature. For example,
current through switches to the ground. The ground- a one-megohm resistance at
and overcurrent protective ing discharge time should be 40 °C (104 °F) will translate
devices. about five times the testing to four-megohm resistance at
2. The temperature of the con- charge time. 20 °C (68 °F). To measure the
ductor is above the dew point 6. The effect of temperature is conductor temperature, use
of the ambient air. When this considered. Since insulation a non-contact infrared ther-
is not the case, a moisture resistance is inversely propor- mometer such as the Fluke 65.
coating will form on the in- tional to insulation tempera-
Work safely
Safety is everyone’s respon- • Hang or rest the meter • Shut down the equipment
sibility, but ultimately it is in if possible. Try to avoid to be tested by opening
your hands. No tool by itself can holding it in your hands to fuses, switches, and circuit
guarantee your safety. It is the minimize personal breakers.
combination of the instrument exposure to the effects of
and safe work practices that transients.
• Disconnect the branch cir-
gives you maximum protection. cuit conductors, grounded
Here are a few safety tips you
• Use the three-point test conductors, grounding
method, especially when conductors, and all other
should follow: checking to see if a circuit equipment from the unit
• Work on de-energized circuits is dead. First, test a known under test.
whenever possible. live circuit. Second, test
Use proper lock-out/tag-out the target circuit. Third,
• Discharge conductor
procedures. If these proce- capacitance, both before
test a live circuit again. and after the test. Some
dures are not in place or not This verifies that your me-
enforced, assume the circuit instruments may have
ter worked properly before automatic discharge
is live. and after the measure- functions.
• On live circuits, use protective ment.
• Check for any leakage
gear: • Use the old electricians’ current through fuses,
• Use insulated tools trick of keeping one hand switches, and breakers
• Wear flame resistant in your pocket. This less- on de-energized circuits.
clothing, safety glasses, ens the chance of a closed Leakage current can cause
and insulation gloves circuit across your chest inconsistent and incorrect
and through your heart.
• Remove watches or other readings.
jewelry • When performing insulation • Don’t use an insulation
• Stand on an insulation and resistance tests: tester in a dangerous or
explosive atmosphere
mat • Never connect the insula- since the instrument can
tion tester to energized
• When making voltage mea- conductors or energized generate arcing in dam-
surements on live circuits: aged insulation.
equipment and always
• Hook on the ground clip follow the manufacturer’s • Use insulated rubber
first, then make contact recommendations. gloves when connecting
with the hot lead. Remove the test leads.
the hot lead first and the
ground lead last.
0 Time ∞
(in seconds)
IC
Dielectric
Insulation Dielectric
Insulation
Conductors Conductors
Figure 2. Conductive leakage current (I L) Figure 3. Capacitive charging leakage current (IC)
Metal Conduit
Insulation
the conduit. Keep a dated standard temperature, about For phase-to-phase DCt = 0.8165 x Ep-p
voltage rating
record of the measured values 20 °C/68 °F.
For phase-to-ground DCt = 1.414 x Ep-n
in a safe place. For equipment rated at or voltage rating
below 1000 volts, the insulation
• If some of the conductors fail reading should be of a value Table 3. DC test voltage equations
the test, identify the problem of 1 MΩ or greater. For equip-
or re-pull the conductors. DCt - dc test voltage related to
ment rated above 1000 volts, the maximum insulation
Moisture, water, or dirt can the expected resistance should
create low resistance read- stress during normal ac
increase to one megohm per operation
ings. 1000 volts applied. Usually, the
measured insulation resistance Ep-p - Phase-to-phase voltage
Predictive maintenance will be a bit less than the values rating
tests recorded previously, resulting in Ep-n - Phase-to-ground voltage
a gradual downward trend as rating
Maintenance tests can provide
important information about
the present and future state of
conductors, generators, trans-
formers, and motors. The key to
effective maintenance testing is
good data collection. Examin- Recorded Value
ing the collected data will aid in (in Megohms)
scheduling diagnostic and
Resistance
repair work, which will reduce (in Megohms)
downtime from unexpected fail-
ures. The following are the
most commonly applied dc test
voltages and maintenance tests
performed:
Spot-reading/short-time 500
resistance test
During the short-time test, the
MegOhmMeter is connected 100
directly across the equipment
being tested and a test voltage Resistance 50
(in Megohms)
is applied for about 60 seconds.
In order to reach a stable in-
sulation reading in about one 10
minute, the test should only be 5 Insulation
performed on low-capacitance Failure
equipment. The basic connec-
tion procedure is the same as
for a proof test and the voltage
applied is calculated from the 1995 1996 1997 1998 1999 000
dc test voltage formulas. When Year
testing good equipment, you Figure 6. Insulation resistance over a period of time
is also tested.
0.5
Temperature correction for
testing rotating machines
For testing armature and field
winding insulation resistance at
various temperatures, the IEEE
recommends the following insu- 0.1
Rm = Kt x (kV + 1)
-10 0 10 0 30 40 50 60 70 80 90 100
Table 6. Insulation resistance equation for ac
and dc rotating machinery Winding Temperature, Degrees Celsius