You are on page 1of 8

Insulation resistance

testing
Application Note

Introduction
Insulation resistance testers
can be used to determine the
integrity of windings or cables
in motors, transformers, switch-
gear, and electrical installations.
The test method is determined
by the type of equipment being
tested and the reason for test-
ing. For instance, when testing
electrical cabling or switchgear
(low-capacitance equipment)
the time-dependent capacitive
leakage and absorption leakage
currents become insignificant
and decrease to zero almost
instantly. A steady conductive
leakage current flow is reached
almost instantly (a minute or
less) providing perfect condi-
tions for the spot-reading/short-
time resistance test. (For more
detailed information on leakage
currents and resistance tests see
the following sections: What Is
Insulation Resistance & Leak-
age Currents and Predictive
Maintenance Tests).
On the other hand, when
the equipment to be tested is a
long run of cable, large motor,
or generator (high-capacitance Installation testing Maintenance testing
equipment) the time-depen- The most important reason for The second most important rea-
dent currents will last for hours. testing insulation is to insure son for insulation testing is to
These currents will cause the public and personal safety. By protect and prolong the life
meter readings to change con- performing a high dc voltage of electrical systems and mo-
stantly, making it impossible to test between de-energized cur- tors. Over the years, electrical
obtain an accurate steady read- rent-carrying (hot), grounded, systems are exposed to envi-
ing. This condition can be and grounding conductors, you ronmental factors such as dirt,
overcome by using a test that can eliminate the possibility grease, temperature, stress, and
establishes a trend between of having a life-threatening vibration. These conditions can
readings, such as the step volt- short circuit or short to ground. lead to insulation failure, result-
age or dielectric-absorption This test is usually performed ing in loss of production or even
test. These tests do not depend after the initial installation of fires. Periodic maintenance tests
on a single reading but on a the equipment. This process can provide valuable informa-
collection of relative readings. will protect the system against tion about the state of deteriora-
It would be a waste of time to miswired and defective equip- tion and will help in predicting
perform these tests on low-ca- ment, and it will insure a high possible failure of the system.
pacitance equipment since the quality installation, customer Correcting problems will result
time-dependent currents dimin- satisfaction, and protect against not only in a trouble-free sys-
ish quickly, resulting in all the fire or shock. tem, but will also extend the
measurements being the same. operating life for a variety of
equipment.
Before measuring sulation surface, and, in some ture (resistance goes down
cases will be absorbed by the as temperature goes up), the
In order to obtain meaningful material. recorded readings are altered
insulation resistance measure- by changes in the temperature
ments, the electrician should 3. The surface of the conductor
is free of carbon and other of the insulating material.
carefully examine the system It is recommended that tests
under test. The best results are foreign matter that can be-
come conductive in humid be performed at a standard
achieved when: conductor temperature of
conditions.
1. The system or equipment is 20 °C (68 °F). As a rule of
taken out of service and 4. Applied voltage is not too thumb, when comparing read-
disconnected from all other high. When testing low- ings to 20 °C base tempera-
circuits, switches, capacitors, voltage systems; too much ture, double the resistance
brushes, lightning arrestors, voltage can overstress or for every 10 °C (18 °F) above
and circuit breakers. Make damage insulation. 20 °C or halve the resistance
sure that the measurements 5. The system under test has for every 10 °C below 20 °C
are not affected by leakage been completely discharged in temperature. For example,
current through switches to the ground. The ground- a one-megohm resistance at
and overcurrent protective ing discharge time should be 40 °C (104 °F) will translate
devices. about five times the testing to four-megohm resistance at
2. The temperature of the con- charge time. 20 °C (68 °F). To measure the
ductor is above the dew point 6. The effect of temperature is conductor temperature, use
of the ambient air. When this considered. Since insulation a non-contact infrared ther-
is not the case, a moisture resistance is inversely propor- mometer such as the Fluke 65.
coating will form on the in- tional to insulation tempera-

Work safely
Safety is everyone’s respon- • Hang or rest the meter • Shut down the equipment
sibility, but ultimately it is in if possible. Try to avoid to be tested by opening
your hands. No tool by itself can holding it in your hands to fuses, switches, and circuit
guarantee your safety. It is the minimize personal breakers.
combination of the instrument exposure to the effects of
and safe work practices that transients.
• Disconnect the branch cir-
gives you maximum protection. cuit conductors, grounded
Here are a few safety tips you
• Use the three-point test conductors, grounding
method, especially when conductors, and all other
should follow: checking to see if a circuit equipment from the unit
• Work on de-energized circuits is dead. First, test a known under test.
whenever possible. live circuit. Second, test
Use proper lock-out/tag-out the target circuit. Third,
• Discharge conductor
procedures. If these proce- capacitance, both before
test a live circuit again. and after the test. Some
dures are not in place or not This verifies that your me-
enforced, assume the circuit instruments may have
ter worked properly before automatic discharge
is live. and after the measure- functions.
• On live circuits, use protective ment.
• Check for any leakage
gear: • Use the old electricians’ current through fuses,
• Use insulated tools trick of keeping one hand switches, and breakers
• Wear flame resistant in your pocket. This less- on de-energized circuits.
clothing, safety glasses, ens the chance of a closed Leakage current can cause
and insulation gloves circuit across your chest inconsistent and incorrect
and through your heart.
• Remove watches or other readings.
jewelry • When performing insulation • Don’t use an insulation
• Stand on an insulation and resistance tests: tester in a dangerous or
explosive atmosphere
mat • Never connect the insula- since the instrument can
tion tester to energized
• When making voltage mea- conductors or energized generate arcing in dam-
surements on live circuits: aged insulation.
equipment and always
• Hook on the ground clip follow the manufacturer’s • Use insulated rubber
first, then make contact recommendations. gloves when connecting
with the hot lead. Remove the test leads.
the hot lead first and the
ground lead last.

 Fluke Corporation Insulation resistance testing


What are insulation The value of insulation re- Capacitive charging leakage
resistance and sistance read on the meter will current (IC )
leakage currents? be a function of following three When two or more conductors
independent sub-currents. are run together in a raceway,
During the testing procedure, they act as a capacitor. Due to
the high dc voltage generated Conductive leakage
current (I L ) this capacitive effect, a leakage
by pressing the test button will current flows through conduc-
cause a small (micro-amps) cur- Conductive current is a small
(micro-amp) amount of current tor insulation. This current lasts
rent flow through the conductor only for a few seconds as the
and the insulation. The amount that normally flows through
insulation, between conductors dc voltage is applied and drops
of current depends on the out after the insulation has been
amount of voltage applied, the or from a conductor to ground.
This current increases as insula- charged to its full test voltage.
system’s capacitance, the total In low-capacitance equipment,
resistance, and the tempera- tion deteriorates and becomes
predominant after the absorp- the capacitive current is higher
ture of the material. For a fixed than conductive leakage cur-
voltage, the higher the current, tion current (see Figure 1) van-
ishes. Because it is fairly steady rent, but usually disappears
the lower the resistance (E=IR, by the time we start recording
R=E/I). The total resistance is and time independent, this is
the most important current for the data. Because of this, it is
the sum of the internal resis- important to let the reading
tance of the conductor (small measuring insulation resistance.
“settle out” before recording it.
value) plus the insulation resis- On the other hand, when test-
tance in MΩs. ing high capacitance equipment
the capacitive charging leakage
current can last for a very long
time before settling out.
Insulation
Resistance Polarization absorption
(in Megohms) leakage current (IA )
Total Current Absorption current is caused by
(IA + IC + IL ) the polarization of molecules
within dielectric material. In
low-capacitance equipment, the
current is high for the first few
seconds and decreases slowly
to nearly zero. When dealing
IL IC IA
with high capacitance equip-
ment or wet and contaminated
insulation, there will be no de-
Current crease in the absorption current
(in µA) for a long time.

0 Time ∞
(in seconds)

Figure 1. Current components


IL

IC

Dielectric
Insulation Dielectric
Insulation

Conductors Conductors

Figure 2. Conductive leakage current (I L) Figure 3. Capacitive charging leakage current (IC)

 Fluke Corporation Insulation resistance testing


Applications manu-facturer’s factory test Proof test procedure
voltage (higher than the rated To conduct an installation proof
Installation test voltage and is available from test, use the following procedure:
Proof testing
the cable manufacturer). If you • Use a multimeter or the volt-
don’t know the factory test volt- age measurement function on
Electricians and engineers age, test using a voltage about the MegOhmMeter to make
perform proof tests to insure twice the cable’s rated voltage sure there is no power applied
proper installation and integrity plus 1000 volts. Rated voltage is to the tested circuit.
of conductors. The proof test the maximum amount of voltage • Select the appropriate voltage
is a simple, quick test used to that the conductor can be ex- level.
indicate the instantaneous con- posed to for a prolonged amount
dition of insulation. It provides of time, usually printed on the • Plug one end of the black test
no diagnostic data and the test conductor. For single-phase, lead to the common terminal
voltages used are much higher two-phase, or three-phase sys- on the meter and touch the
than the voltages used in pre- tems, the cable is rated phase- test probe to a ground (earth)
dictive maintenance tests. The to-phase. or another conductor. Some-
proof test is sometimes called This previously mentioned times it is helpful to ground all
GO/NO GO TEST because it tests method should only be used conductors that are not part
cable systems for maintenance for testing small and new ap- of the test. Alligator clips can
errors, incorrect installation, paratus because of its ability to make measurements easier
serious degradation, or contami- withstand higher stress volt- and more accurate.
nation. The installation is ages. For larger or older equip- • Plug one end of the red test
declared acceptable if no break- ment or wire use dc test volt- lead to the volt/ohm terminal
down occurs during testing. ages (see table 3). on the meter and connect the
Choosing the test voltage Common proof dc test volt- test probe to the conductor to
A proof test can be performed ages (not the manufacturer’s be tested.
on equipment of any capaci- test voltages) used for testing • Press the test button to ap-
tance. It is performed with a rotating equipment are shown ply the desired voltage and
single voltage, usually between in Table 1.
500 and 5000 V, for about one Rotating Equipment DC Test Voltages Formula Used
minute. It is common to stress
Factory AC Test, VAC (only for reference) 2 x (VAC Nameplate Rating) + 1,000
the insulation above normal
Maximum DC Installation Test, VDC 1.28 x (Factory AC Test)
working voltages in order to
detect subtle weaknesses in Maximum DC After Service Test, VDC 0.96 x (Factory AC Test)
the insulation. For new equip- Table 1. Proof test voltage equations for rotating machines
ment, the test should be done
at about 60% to 80% of the

Metal Conduit

Insulation

Figure 4. Conductor under test

 Fluke Corporation Insulation resistance testing


read the resistance displayed should notice a steady increase shown in Figure 6. The down-
on the meter. It could take a in insulation resistance due ward slope is a normal sign of
few seconds for the reading to decrease in capacitive and insulation aging. A sharp down-
to settle. The higher the resis- absorption currents. Because ward slope would indicate an
tance is the better. temperature and humidity can insulation failure or a warning
• Test each conductor against affect the readings, the mea- of troubles ahead.
ground and against all the surements should preferably be
other conductors present in made above the dew point at DC Test Voltages Formula Used

the conduit. Keep a dated standard temperature, about For phase-to-phase DCt = 0.8165 x Ep-p
voltage rating
record of the measured values 20 °C/68 °F.
For phase-to-ground DCt = 1.414 x Ep-n
in a safe place. For equipment rated at or voltage rating
below 1000 volts, the insulation
• If some of the conductors fail reading should be of a value Table 3. DC test voltage equations
the test, identify the problem of 1 MΩ or greater. For equip-
or re-pull the conductors. DCt - dc test voltage related to
ment rated above 1000 volts, the maximum insulation
Moisture, water, or dirt can the expected resistance should
create low resistance read- stress during normal ac
increase to one megohm per operation
ings. 1000 volts applied. Usually, the
measured insulation resistance Ep-p - Phase-to-phase voltage
Predictive maintenance will be a bit less than the values rating
tests recorded previously, resulting in Ep-n - Phase-to-ground voltage
a gradual downward trend as rating
Maintenance tests can provide
important information about
the present and future state of
conductors, generators, trans-
formers, and motors. The key to
effective maintenance testing is
good data collection. Examin- Recorded Value
ing the collected data will aid in (in Megohms)
scheduling diagnostic and
Resistance
repair work, which will reduce (in Megohms)
downtime from unexpected fail-
ures. The following are the
most commonly applied dc test
voltages and maintenance tests
performed:

Equipment DC Test Voltage


AC Rating (Volts) (Volts) 0 Time 60 sec
0 – 100 100 – 250 (in seconds)
440 – 560 500 – 1,000
Figure 5. Insulation resistance test
2,300 1,000 or higher
4,100 and above 1,000 or higher
Initial Aging
Acceptance of After
Table 2. Maintenance test voltages versus Test Insulation Rewinding
equipment ratings
1000

Spot-reading/short-time 500
resistance test
During the short-time test, the
MegOhmMeter is connected 100
directly across the equipment
being tested and a test voltage Resistance 50
(in Megohms)
is applied for about 60 seconds.
In order to reach a stable in-
sulation reading in about one 10
minute, the test should only be 5 Insulation
performed on low-capacitance Failure
equipment. The basic connec-
tion procedure is the same as
for a proof test and the voltage
applied is calculated from the 1995 1996 1997 1998 1999 000
dc test voltage formulas. When Year
testing good equipment, you Figure 6. Insulation resistance over a period of time

 Fluke Corporation Insulation resistance testing


Step voltage test
The step voltage test involves
Test Made
resistance testing at various with 50V
voltage settings. In this test,
you apply each test voltage for Test Made
with 500V
the same period of time (usu-
ally 60 seconds), graphing the
recorded insulation resistance. Direction of
By applying increasing volt- Resistance Insulation
(in Megohms)
ages in steps, the insulation is Failure
exposed to increased electrical Test Made
with 1000V
stress that can reveal informa-
tion about flaws in the insula-
tion such as pinholes, physical
damage, or brittleness. Good
insulation should withstand an
increase in over-voltage stress
and its resistance should remain 0 Time 60 sec
(in seconds)
approximately the same dur-
ing testing with different volt-
Figure 7. Step voltage test
age levels. On the other hand,
especially at higher voltage
levels, deteriorated, cracked or
contaminated insulation will
experience an increased current 1000
flow, resulting in a decrease in
500
insulation resistance. This test is
independent of insulation ma-
terial, equipment capacitance, Good
Insulation
and temperature effect. Because 100 Condition
it takes a longer time to run, it 50
should be performed only after Resistance
(in Megohms)
Poor
Insulation
an insulation spot test has been Condition
inconclusive. A spot test deals
10
with absolute resistance change
(single reading) with respect to 5
time, while the step voltage test
looks for trends in resistance,
with respect to varying test
voltages.
Voltage
(in kV)
Dielectric-absorption/
time-resistance test
Figure 8. Good and poor test curves
The time resistance test is
independent of equipment size
and temperature. It compares
the absorption characteristics of Good
contaminated insulation with the Insulation
absorption characteristics of good
insulation. The test voltage is
applied over a 10 minute period,
with the data recorded every 10
seconds for the first minute and Resistance
then every minute thereafter. (in Megohms)
The interpretation of the slope of
the plotted graph will determine Cracked
the condition of the insulation. A Insulation

continuous increase in graphed


resistance indicates good insula-
tion. A flat or downward curve
indicates cracked or contami- 0 Time 10 min
nated insulation. (in minutes)

Figure 9. Dielectric absorption test for good and contaminated curves

 Fluke Corporation Insulation resistance testing


Another method for deter- Insulation Resistance 60/30 Second Ratio 10/1 Minute Ratio
mining the quality of insulation Condition (Polarization Index)
is to use the polarization index Dangerous 0 -1.0 0 - 1
(PI) test. It is particularly valu- Poor 1.0 – 1.3 1 – 2
able for uncovering moisture Good 1.3 – 1.6 2 – 4
and oil ingress that have a flat- Excellent 1.6 and above 4 and above
tening effect on the PI curve,
causing leakage current and Table 4. Approximate dielectric absorption ratios
eventually shorted windings.
Proof Test Spot- Test Step Test Dielectric- Polarization
The polarization index is the Reading Voltage Absorption Index Test
ratio of two time-resistance Test
readings: one is taken after 1 Single reading • •
minute and the other is taken High test voltage •
after 10 minutes. With good
insulation, the insulation re-
Performed • • • •
periodically
sistance will start low and get Various test •
higher as the capacitive leakage voltages
current and absorption current Timed test • •
get smaller. Results are obtained intervals
by dividing the 10 minute test Diagnostic • • • •
information
value by the one-minute test
value. A low polarization index Table 5. Various insulation tests
usually indicates problems with
the insulation. When test time Rm - Minimum insulation resis- For a three phase system tested
is constrained, a shortcut to the tance corrected to 40 °C with the other two phases
polarization index test is the (104 °F) in MΩ grounded, the resistance re-
dielectric absorption ratio corded for each phase should
(60/30) second test. Kt - Insulation resistance
temperature coefficient at be divided by two. Then, the
winding temperature, resulting value can be compared
Testing connections obtained from Figure 10 with the recommended mini-
in generators, mum insulation resistance (Rm).
transformers, kV - Rated machine terminal
to terminal voltage in
motors, and wiring kilovolts
To test the insulation resistance
in generators, transformers, 100

motors, and wiring installa-


tions, we can employ any of the 50

previously mentioned predictive


maintenance tests. Whether we
choose the spot-reading, step
voltage, or time-resistance tests
depends on the reason for test- 10
ing and the validity of the data
Insulation Resistance Temperature Coefficient, K t

obtained. When testing gen- 5


erators, motors, or transformers
each winding/phase should be
tested in sequence and sepa-
rately while all the other wind-
ings are grounded. In this way,
the insulation between phases 1.0

is also tested.
0.5
Temperature correction for
testing rotating machines
For testing armature and field
winding insulation resistance at
various temperatures, the IEEE
recommends the following insu- 0.1

lation resistance formula.


0.05

Rm = Kt x (kV + 1)

-10 0 10 0 30 40 50 60 70 80 90 100
Table 6. Insulation resistance equation for ac
and dc rotating machinery Winding Temperature, Degrees Celsius

Figure 10. Approximate temperature coefficient for rotating machines

 Fluke Corporation Insulation resistance testing


Testing generators and
motors Transformer Type 60-Hertz
When testing the resistance Tanked oil-filled type 1.5
of the stator coils make sure
the stator winding and phases Untanked oil-filled type 30.0
are disconnected. Measure the Dry or compound-filled type 30.0
insulation resistance between Table 9. Constant C values at 20°C (68°)
Insulation
Resistance
windings and windings to Tester

ground. Also, when dc genera- Testing wiring and cable


tors or motors are being tested installations
To Different
Windings
the brushes should be raised
so the coils can be tested sepa- When testing wires or cables,
rately from the armature. The they should be disconnected
following table lists recom- from panels and machinery to
mended minimum resistance keep them isolated. The wires To Ground

readings for various motor volt- and cables should be tested


age ratings. against each other and against
ground (see Figure 4 on page 4).
Motor Nameplate Minimum Acceptable The Insulated Power Cable
Voltage Rating Resistance Engineers Association (IPCEA)
0-208 100,000 Ω provides the following formula
208-240 200,000 Ω that suggests minimum insula-
240-600 300,000 Ω tion resistance values. Figure 11. Testing the insulation resistance of a motor
600-1000 1 MΩ
R = K x Log10 (D/d)
1000-2400 2 MΩ
2400-5000 3 MΩ Table 10. Cable insulation resistance

Table 7. Recommended minimum resistance at R - MΩs per 1000 feet (305


40°C (104°F) meters) of cable. Based on
dc test potential of 500
Testing transformers volts, applied for one min-
When testing single-phase ute at 15.6 °C (60 °F) tem-
transformers, test winding to perature)
winding, winding to ground, or K - Insulation material constant.
test one winding at a time with (For example: Impregnated
all others grounded. For three- Paper-2640, Varnished
phase transformers, substitute E Cambric-2460, Thermo-
with EP-P (for delta transformers) plastic Polyethlene-50000,
or Ep-n (for wye transformers) Composite Polyethylene-
and kVA with kVA3Ø rating of the 30000)
winding under test.
For determining minimum D - Outside diameter of con-
insulation resistance use the fol- ductor insulation for single
lowing formula. conductor wire and cable
D = d + 2c + 2b diameter
Transformer Type Formula Used of single conductor cable
Single phase R = C x E ÷ √kVA d - Diameter of conductor
Three phase wye R = C x Ep-n ÷ √kVA c - Thickness of conductor
Three phase delta R = C x Ep-p ÷ √kVA insulation Fluke. Keeping your world
Table 8. Transformers insulation resistance b - Thickness of jacket up and running.®
equations insulation
R - One minute 500 volt dc For example, one thousand Fluke Corporation
minimum insulation feet of number 6 A.W.G. Heat PO Box 9090, Everett, WA USA 98206

resistance in megohms Resistant Natural Rubber insula- Fluke Europe B.V.


PO Box 1186, 5602 BD
C - Constant for 20 °C (68 °F) tion type stranded conductor Eindhoven, The Netherlands
measurements with 0.125 insulation thickness
For more information call:
(see below) will have K = 10,560 and Log10 In the U.S.A. (800) 443-5853 or
(D/d) = 0.373 inches. According Fax (425) 446-5116
E - Winding voltage rating. to the formula (R = K x Log10 In Europe/M-East/Africa +31 (0) 40 2675 200 or
KVA - Rated capacity of wind- (D/d), R = 10,560 x 0.373 = Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
ing under test. For three 3,939 MΩ per 1000 feet) the Fax (905) 890-6866
phase units kVA3Ø = expected minimum insulation From other countries +1 (425) 446-5500 or
√3 x kVA1Ø resistance for single conductor Fax +1 (425) 446-5116
per thousand feet at tempera- Web access: http://www.fluke.com
ture of 60 °F will be 3,939 MΩ. ©2003, 2007 Fluke Corporation. All rights reserved.
Specifications subject to change without notice.
Printed in U.S.A. 4/2007 1579160 A-EN-N Rev C

 Fluke Corporation Insulation resistance testing

You might also like