Outdoor Cable

Central Tube Single Jacket Armored Cable

Product Construction Fiber


• 2–12 fibers
• Central tube gel-filled
• Color-coding per TIA/EIA 598 B
Armor
• Corrugated coated steel tape
Outer Jacket
• Black UV- and moisture-resistant polyethylene (PE)
• Sequential footage markings
Features • Compact, user-friendly design
• Central tube armored design provides excellent fiber protection
Performance • Temperature: Storage -40˚C (-40˚F) to +70˚C (+158˚F) Installation
-30˚C (-22˚F) to +60˚C (+140˚F) Operating -40˚C (-40˚F) to +70˚C
(+158˚F) • Minimum Bend Radius: 20 X OD—Installation 10 X
OD—In-Service
• Maximum Crush Resistance: 150 lbs/in (440 N/cm)
Uses in • Interbuilding voice or data communication backbones
• Installed in ducts, underground conduits, aerial/lashed or direct
buried
• FTTX
Image

Cross Section
Loose Tube Dual Jacket Cable

Product Construction Fiber


• 2–144 fibers
• Loose tube gel-filled
• Color-coding per TIA/EIA 598 B
Central Strength Member
• Epoxy/glass rod
Inner Jacket
• Black UV- and moisture-resistant polyethylene (PE)
Outer Jacket
• Black UV- and moisture-resistant polyethylene (PE)
• Sequential footage markings
Features • Loose tube gel-filled construction for superior fiber protection
• UV- and moisture-resistant design
• Added protection of an inner jacket
• Dry Water Block cable core for ease of handling
Performance • Temperature: Storage -40˚C (-40˚F) to +75˚C (+167˚F) Installation -
30˚C (-22˚F) to +60˚C (+140˚F) Operating -40˚C (-40˚F) to +70˚C
(+158˚F) • Minimum Bend Radius: 20 X OD—Installation 10 X OD—
In-Service
• Maximum Crush Resistance: Short - 125 lbs/in (220 N/cm) Long - 63
lbs/in (110 N/cm)
Uses in • Interbuilding voice or data communication backbones
• Installed in ducts, underground conduits, aerial/lashed or direct buried
Image

Cross Section
Loose Tube Dual Jacket Armored Cable

Product Construction Fiber


• 2–312 fibers
• Loose tube gel-filled
• Color-coding per TIA/EIA 598 B Central Strength Member
• Epoxy/glass rod
Inner Jacket
• Black UV- and moisture-resistant polyethylene (PE)
Armor
• Corrugated coated steel tape
Outer Jacket
• Black UV- and moisture-resistant polyethylene (PE)
• Sequential footage markings
Features • Loose tube gel-filled construction for superior fiber protection
• UV- and moisture-resistant design
• Rodent-resistant construction
• Dry Water Block cable core for ease of handling
Performance • Temperature: Storage -40˚C (-40˚F) to +75˚C (+167˚F) Installation -
30˚C (-22˚F) to +60˚C (+140˚F) Operating -40˚C (-40˚F) to +70˚C
(+158˚F) • Minimum Bend Radius: 20 X OD—Installation 10 X
OD—In-Service
• Maximum Crush Resistance: Short - 125 lbs/in (220 N/cm) Long -
63 lbs/in (110 N/cm)
Uses of Fiber Cable • Interbuilding voice or data communication backbones
• Installed in ducts, underground conduits, aerial/lashed or direct
buried
Image

Cross Section
Loose Tube Single Jacket Self-Supporting (Figure-8) Cable

Product Construction Fiber


• 2–216 fibers
• Loose tube gel-filled
• Color-coding per TIA/EIA 598 B
Central Strength Member
• Epoxy/glass rod
Jacket
• Black UV- and moisture-resistant polyethylene (PE)
• Sequential footage markings
Messenger Wire
• 1/4" stranded EHS galvanized steel
• MRCL with messenger = 14,923 N/ 3,350 kF
Features • Loose tube gel-filled construction for superior fiber protection
• UV- and moisture-resistant design
• Self-supporting figure-8 design
Performance • Temperature: Storage -40˚C (-40˚F) to +75˚C (+167˚F) Installation -
30˚C (-22˚F) to +60˚C (+140˚F) Operating -40˚C (-40˚F) to +70˚C
(+158˚F)
• Minimum Bend Radius: 20 X OD—Installation 10 X OD—In-Service
• Maximum Crush Resistance: Short - 125 lbs/in (220 N/cm) Long - 63
lbs/in (110 N/cm)
Uses of Fiber Cable • Interbuilding voice or data communication backbones
• Installed aerially
Image

Cross Section
Toneable Flat Drop Cable

Product Construction Fiber


• 2–12 fibers
• Central tube gel-filled
• Color-coding per TIA/EIA 598 B
Outer Jacket
• Black UV- and moisture-resistant polyethylene (PE)
• Sequential footage markings
Features • Compact, user-friendly design
• Central tube armored design provides excellent fiber
protection
• Easy to install
Performance • Temperature: Storage -40˚C (-40˚F) to +75˚C (+167˚F)
Installation -30˚C (-22˚F) to +60˚C (+140˚F) Operating -40˚C (-
40˚F) to +70˚C (+158˚F) • Minimum Bend Radius: 5.9 X OD—
Installation 3.9 X OD—In-Service
• Highly crush-resistant
Uses of Fiber Cable • Broadband network
• Installed in ducts
• FTTX
Image

Cross Section
Indoor Cable

Tight Buffer Distribution Low-Smoke, Zero-Halogen Cable

Product Construction Fiber


• 2–72 fibers
• 900 µm tight buffer
• Color-coding per TIA/EIA 598 B
Central Strength Member
• Epoxy/glass rod (above 12 fibers)
Overall Strength Member
• Aramid fiber yarn
Jacket
• Flame-retardant LSZH compound
• Sequential footage markings
• Orange jacket—multimode fibers (except 10 Gbps)
• Aqua jacket—10 Gbps multimode fibers
• Yellow jacket—singlemode fibers
Features • Lightweight, flexible design simplifies installation
• Tight buffer provides individual fiber protection
• Tight buffered fibers are easy to handle and strip for field
connectorization
• Sub-units are numbered for identification
Performance • Temperature: Storage -40˚C (-40˚F) to +70˚C (+158˚F) Installation 0˚C
(+32˚F) to +50˚C (+122˚F) Operating -20˚C (-4˚F) to +70˚C (+158˚F)
• Minimum Bend Radius: 20 X OD—Installation 10 X OD—In-Service
• Maximum Crush Resistance: 850 lbs/in (1485 N/cm)
• Maximum Vertical Rise—1,640 ft (500 m)
Uses of Fiber Cable • Intrabuilding voice or data communication backbones
• ETL Listed Type OFNR for installation in vertical riser and general
horizontal applications when installed in accordance with NEC article
770.154 and 770.179
Image

Cross Section
Tight Buffer Distribution Riser Cable

Product Construction Fiber


• 2–144 fibers
• 900 µm tight buffer
• Color-coding per TIA/EIA 598 B
Central Strength Member
• Epoxy/glass rod (P1R)
Overall Strength Member
• Aramid fiber yarn
Jacket
• Flame-retardant compound
• Sequential footage markings
• Orange jacket—multimode fibers (except 10 Gbps)
• Aqua jacket—10 Gbps multimode fibers
• Yellow jacket—singlemode fibers
Features • Lightweight, flexible design simplifies installation • Tight buffer
provides individual fiber protection
• Tight buffered fibers are easy to handle and strip for field
connectorization
• Sub-units are numbered for identification
Performance • Temperature: Storage -40˚C (-40˚F) to +70˚C (+158˚F) Installation
0˚C (+32˚F) to +50˚C (+122˚F) Operating -20˚C (-4˚F) to +70˚C
(+158˚F)
• Minimum Bend Radius: 20 X OD—Installation 10 X OD—In-Service
• Maximum Crush Resistance: 850 lbs/in (1485 N/cm)
• Maximum Vertical Rise—1,640 ft (500 m)
Uses of Fiber Cable • Intrabuilding voice or data communication backbones
• ETL Listed Type OFNR for installation in vertical riser and general
horizontal applications when installed in accordance with NEC article
770.154 and 770.179
Image

Cross Section
Tight buffer Breakout Riser Cable

Product Construction Fiber


• 2–24 fibers
• 900 µm white tight buffer
• 2.4 mm jacketed sub-units, with overall jacket color coding
Central Strength Member
• Aramid fiber yarn
• Optional epoxy glass rod (BIR)
Overall Strength Member
• Aramid fiber yarn
Jacket
• Flame-retardant compound
• Sequential footage markings
• Orange jacket—multimode fibers (except 10 Gbps)
• Aqua jacket—10 Gbps multimode fibers
• Yellow jacket—singlemode fibers
Features • Rugged individual fiber protection
• Easily terminated with fiber sub-units
• Heavy-duty premises applications
• Sub-units are numbered for identification
Performance • Temperature: Storage -40˚C (-40˚F) to +70˚C (+158˚F)
Installation 0˚C (+32˚F) to +50˚C (+122˚F) Operating -20˚C
(-4˚F) to +70˚C (+158˚F)
• Minimum Bend Radius: 20 X OD—Installation 10 X OD—
In-Service
• Maximum Crush Resistance: 1000 lbs/in (1750 N/cm)
• Maximum Vertical Rise—1,640 ft (500 m)
Uses of Fiber Cable • Intrabuilding voice or data communication backbones
• ETL Listed Type OFNR for installation in vertical riser and
general horizontal applications when installed in accordance
with NEC article 770.154 and 770.179
Image

Cross Section
Tight Buffer Distribution Interlock Armored Riser Cable

Product Construction Fiber


• 2–144 fibers
• 900 µm tight buffer
• Color-coding per TIA/EIA 598 B
Overall Strength Member
• Aramid fiber yarn
Inner Jacket
• Flame-retardant compound
Armor
• Interlock aluminum (-ILRA)
Outer Jacket
• Flame-retardant compound
• Sequential footage markings*
• Orange jacket—multimode fibers (except 10 Gbps)
• Aqua jacket—10 Gbps multimode fibers
• Yellow jacket—singlemode fibers
Features • Interlock armor provides outstanding mechanical protection
• Interlock armor is flexible and easy to use
• Tight buffer provides individual fiber protection
• Sub-units are numbered for identification
Performance • Temperature: Storage -40˚C (-40˚F) to +70˚C (+158˚F) Installation 0˚C
(+32˚F) to +50˚C (+122˚F) Operating -20˚C (-4˚F) to +70˚C (+158˚F)
• Minimum Bend Radius: 20 X OD—Installation 10 X OD—In-Service
• Maximum Crush Resistance: 1,500 lbs/in (2,627 N/cm)
Uses of Fiber Cable • Harsh premises environments requiring heavy-duty protection
• ETL Type OFCR for installation in any premises location when
installed in accordance with NEC article 770.154 and 770.179
Image

Cross Section