NFPA 20 – 2016 and Beyond

Gayle Pennel, P.E. - Aon Fire Protection Engineering

Aon Fire Protection Engineering Corporation


NFPA 20 -2016 Major Changes
Automatic Supervision of Pressure Transducers
Connectivity Annex – Standardized Data Reporting Format
Introduction of Multistage Multiport Pumps
Additional Requirements for Vertical Staging of Fire Pumps
New NFPA Sample Fire Pump Acceptance Test Form
Break Tanks and Refilling Requirements Moved from NFPA
20 to NFPA 22

Aon Fire Protection Engineering 2


Automatic Supervision of Pressure Transducers

10.5.2.1.3* Where an electronic pressure sensor is used to


automatically control fire pump operation, the fire pump
controller shall monitor the transducer during automatic testing.
10.5.2.1.3.1* Where the transducer pressure reading exceeds
10 psi (0.68 bar) during any automatic pump start that was
initiated by the solenoid drain valve, as required by 10.5.2.1.8.3,
the controller shall activate a visual and audible alarm, that can
be silenced.

Aon Fire Protection Engineering 3


Automatic Supervision of Pressure Transducers
(continued)

10.5.2.1.3.2* Where an electronic pressure sensor is used to


control fire pump operation, the fire pump controller shall
monitor for and provide a signal for the following electronic
pressure sensor conditions:
(1) Any time the transducer output is less than 10 percent of
rated span or below its rated zero pressure output
(2) Any time the pressure transducer reading is more than 10
percent above its rated full-scale output

Aon Fire Protection Engineering 4


Introduction of Multistage Multiport Pumps

Single driver with multiple stages and multiple outlets


Similar to fire pumps in series except a single driver, with
multiple impellers in a shared case and no shut off of check
valves between outlets.
Currently being used in Europe

Aon Fire Protection Engineering 5


Introduction of Multistage Multiport Pumps

Aon Fire Protection Engineering 6


Vertical Staged Fire Pumps

4.20.2.1* Except as permitted by 4.20.2.2, all the pumps that are


a part of a series fire pump unit shall be located within the same
fire pump room.
4.20.2.2 Pumps that are a part of a series fire pump unit shall be
permitted to be located in separate pump rooms where all the
following conditions are met:
(1) Each pump shall be arranged so that all pumps operating in
series can be manually stopped or started from all pump rooms
housing the series fire pumps.
(2) The suction and discharge pressures from all pumps
operating in series shall be displayed in all pump rooms housing
the series fire pumps.

Aon Fire Protection Engineering 7


Vertical Staged Fire Pumps (continued)

(3) The alarms and signals shall be annunciated in the other


pump rooms for all pumps that are a part of the series fire pump
unit in accordance with 4.20.2.8 and 4.20.2.9.
(4) The interconnect control wiring between the controllers in
different pump rooms shall comply with 4.20.2.7 and 4.20.2.8.
(5) A pump room communication system that shall comply with
4.20.2.9 and 4.20.2.10.
4.20.2.10.1 A two-way, in-building emergency services
communications system in accordance with NFPA 72 shall be
provided in each pump room where pumps in series are not
located in the same room.
4.20.2.10.1.1 The communication system shall meet the
survivability requirements of NFPA 72

Aon Fire Protection Engineering 8


Break Tanks and Refilling Requirements Moved from
Chapter 4 of NFPA 20 to NFPA 22

Requirements remain the same


Refilling requirements for High Rise retained in NFPA 20

Aon Fire Protection Engineering 9


Auxiliary Power for High Rise

5.5 Auxiliary Power. Where electric motor–driven fire pump(s)


are used, a reliable emergency source of power in accordance
with Section 9.6 or a back-up fire pump in accordance with
Section 9.3 shall be provided for the fire pump installation.

Aon Fire Protection Engineering 10


Definitions Added

3.3.38* No Flow (Churn, Shutoff). The condition of zero flow


when the fire pump is running but the only water passing
through the pump is a small flow that is discharged through the
pump circulation relief valve or supplies the cooling for a diesel
engine driver.
3.3.47 Rated Flow. The capacity of the pump at rated speed
and rated pressure as marked on the manufacturer's nameplate
3.3.42.3 Rated Pressure. The net pressure (differential
pressure) at rated flow and rated speed as marked on the
manufacturer’s nameplate.
3.3.41* Peak Load. As it pertains to acceptance testing in this
standard, the maximum power required to drive the pump at any
flow rate up to 150 percent of rated capacity (flow).

Aon Fire Protection Engineering 11


Definations Added (continued)

3.3.42.1 Discharge Pressure. The total pressure available at


the fire pump discharge flange.
3.3.42.2* Net Pressure (Differential Pressure). For vertical
turbine fire pumps, the total pressure at the fire pump discharge
flange plus the total suction lift. For other fire pumps, the total
pressure at the fire pump discharge flange minus the total
pressure at the fire pump suction flange.
3.3.42.4 Suction Pressure. The total pressure available at the
fire pump suction flange
3.3.67.2 Suction Pressure Regulating Valve. A pilot-operated
valve installed in discharge piping that maintains positive
pressure in the suction piping, while monitoring pressure in the
suction piping through a sensing line.

Aon Fire Protection Engineering 12


NFPA Sample Fire Pump Acceptance Test Form

Aon Fire Protection Engineering 13


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 14


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 15


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 16


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 17


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 18


Fire Pump Acceptance Test Form (continued)

Aon Fire Protection Engineering 19


Test Equipment.

14.2.6.1.1 Calibrated test equipment shall be provided to


determine net pump pressures, rate of flow through the pump,
volts and amperes, and speed.
14.2.6.1.2 Calibrated test gauges, transducers, and other
devices used for measurements required in 14.2.6.1.1 during
the test shall be used and shall bear a label with the latest date
of calibration.
14.2.6.1.2.1 Gauges, transducers, and other devices used for
measurements required in 14.2.6.1.1 during the test shall be
calibrated annually at minimum.
14.2.6.1.2.2 Calibration of gauges, transducers, and other
devices used for measurements required in 14.2.6.1.1 during
the test shall be maintained at an accuracy level of }1 percent.

Aon Fire Protection Engineering 20


Test Equipment (continued)

14.2.6.1.2.3 Fire pump controller voltage and current readings


on controllers that are factory calibrated and adjusted to } 3
percent shall be permitted to be used in lieu of calibrated
volt/amp meters for the acceptance test.
14.2.6.1.2.4 Fixed outlet flow devices shall be inspected for
damage, but they shall not require calibration.
14.2.6.1.3 Discharge and sensing orifices that can be visually
observed without disassembling equipment, piping, or valves
shall be visually inspected and shall be free of damage and
obstructions that could affect the accuracy of the measurement.
14.2.6.1.4 Discharge orifices shall be listed or constructed to a
recognized standard with a known discharge coefficient.

Aon Fire Protection Engineering 21


Test Equipment (continued)

14.2.6.1.5 Requirements for personal protective equipment and


procedures in accordance with NFPA 70E shall be followed
when working near energized electrical or rotating equipment

Aon Fire Protection Engineering 22


Test Equipment (continued)

14.2.6.1.5 Requirements for personal protective equipment and


procedures in accordance with NFPA 70E shall be followed
when working near energized electrical or rotating equipment

Aon Fire Protection Engineering 23


Packaged Fire Pump Assemblies.

4.30.1 A packaged fire pump assembly, with or without an


enclosure, shall meet all of the following requirements:
...
(3) The assembly shall be listed for fire pump service.
(4) The total assembly shall be engineered and designed by a
system designer as referenced in 4.3.2.
A

Aon Fire Protection Engineering 24


Minimum Pump Suction Pressure from Tank

4.15.3.2* The requirements of 4.15.3.1 shall not apply where the


supply is a suction tank with its base at or above the same
elevation as the pump, and the gauge pressure at the pump
suction flange shall be permitted to drop to -3 psi (-0.2 bar) with
the lowest water level after the maximum system demand and
duration have been supplied.

Aon Fire Protection Engineering 25


Automatic Shutdown After Automatic Start

10.5.4.2. Automatic shutdown shall not be permitted if starting


and running causes are present.
10.5.4.2.1 Automatic shutdown shall be permitted only in the
following circumstances:
(1)* During automatic testing in accordance with 10.5.2.7
(2) Where approved by the authority having jurisdiction
10.5.4.2.2 Where automatic shutdown after automatic start is
permitted, a minimum run timer set for at least 10 minutes shall
be used.

Aon Fire Protection Engineering 26


Limited Service Controllers.

10.7
10.7.1 Limitations. Limited service controllers consisting of
automatic controllers for across-the-line starting of squirrelcage
motors of 30 hp or less, 600 V or less, shall be permitted to be
installed where such use is acceptable to the authority having
jurisdiction.

10.7.2.3 The manually operated isolating switch specified in


10.4.2 shall not be required.

Aon Fire Protection Engineering 27


Automatic Fuel Maintenance Systems

11.6.4.4* An active fuel maintenance system listed for fire pump


service shall be permitted to be installed for the maintenance of
the fuel in the supply tank.
11.6.4.4.1 Where provided, the active fuel maintenance system
shall be equipped with a visible indicator to indicate when the
system is in need of maintenance.
11.6.4.4.2 Where provided, the active fuel maintenance system
shall be equipped with a contact closure for signaling to the
controller when the system is in need of maintenance.

Aon Fire Protection Engineering 28


Automatic Fuel Maintenance Systems (continued)

11.6.4.4.3 Where provided, the active fuel maintenance systems


shall be permanently connected to the fuel tank as follows:
(1) All connections shall be made directly to the tank.
(2) The supply from the tank to the active fuel maintenance
system shall include a manual shutoff valve and a connection to
the drain located between the bottom of the tank and the drain
valve of the fuel storage tank.
(3) The return from the active fuel maintenance system to the
fuel storage tank shall be connected to the dedicated connection
on the top of the tank with a drop tube down to the 50 percent
level, and shall include a manual shutoff valve for servicing the
system.

Aon Fire Protection Engineering 29


Emergency-Run Mechanical Control at Controller

10.5.3.2*.
10.5.3.2.1 The controller shall be equipped with an emergency-run
handle or lever that operates to mechanically close the motor-circuit
switching mechanism.
10.5.3.2.1.1 This handle or lever shall provide for nonautomatic
continuous running operation of the motor(s), independent of any electric
control circuits, magnets, or equivalent devices and independent of the
pressure-activated control switch.

Aon Fire Protection Engineering 30


Automatic Testing

12.7.2.7.1 The controller equipment shall be arranged to


automatically start, run, and shut down the engine at the
minimum no-flow test frequency and duration required by NFPA
25.
12.7.2.7.2 Performance of this weekly program timer shall be
recorded as a pressure drop indication on the pressure recorder.
(See 12.4.4.)
12.7.2.7.3 A solenoid valve drain on the pressure control line
shall be the initiating means.
12.7.2.7.4 The engine shall shut down automatically on high
engine temperature, low oil pressure, or high cooling water
temperature if no other starting or running cause exists.

Aon Fire Protection Engineering 31


Connectivity Scope

C.1.1 This annex covers considerations relating to the access of


fire pump controllers, including access methods, security
considerations, accessible information, potential use of
accessible information, long-term improvement in reliability, and
standardization that allows the full potential of connectivity to be
met.

Aon Fire Protection Engineering 32


Connectivity – Access Levels

C.8 Recommended Requirements.


C.8.1 Separate access protocols should be used for the
following access levels:
(1) Read-only access to performance information — Level 1
(2) Access for statistical analysis by independent body — Level
2a
(3) Access for manufacturer analysis — fire pump — Level 2b
(4) Access for manufacturer analysis — controller — Level 2c
(5) Access for remote testing — Level 2d with alarm to be
triggered if the pump is not restored to automatic mode within 8
hours

Aon Fire Protection Engineering 33


Connectivity – Remote Operation of Fire Pumps

C.7 Remote Control. Remote starting and/or stopping is


prohibited.

Aon Fire Protection Engineering 34


Connectivity – Equipment Data Table

Table D.8.2.2 Recommended Equipment Data


Data Accessible To

Information Source*

Remote Operations
Independent 3rd
party statistical

Diesel Engine
Manufacturer

Manufacturer

Manufacturer
Performance
Supervision
Monitoring

Monitoring
Fire Pump

Controller

analysis
Data

Fire Pump Manufacturer M X X X X X


Fire Pump Type M X X X X X
Rated Flow M X X X X X
A
• A – Controller should access and record data automatically
• M – Requires Manual Input at time of installation or test
• M/A – Probably Requires Manual Input at time of installation or test but may be able to Record
Automatically

Aon Fire Protection Engineering 35


Connectivity – Continuously Monitored Data

Table D.8.2.3 Continuously Monitored Data


Data Accessible To

Information Source*

Remote Operations
Independent 3rd
party statistical

Diesel Engine
Manufacturer

Manufacturer

Manufacturer
Performance
Supervision
Monitoring

Monitoring
Fire Pump

Controller

analysis
Data

Fire Pump Power Status M X X X X X X


Fire Pump Running Status M X X X X X X
Fire Pump Test Running M X X X X X X
Suction Pressure A X X X X X X
A
• A – Controller should access and record data automatically
• M – Requires Manual Input at time of installation or test
M/A – Probably Requires Manual Input at time of installation or test but may be able to Record
Automatically

Aon Fire Protection Engineering 36


Connectivity – Test Performance Data

Table D.8.2.4 Recommended Test Performance Data


Data Accessible To

Information Source*

Remote Operations
Independent 3rd
party statistical

Diesel Engine
Manufacturer

Manufacturer

Manufacturer
Performance
Supervision
Monitoring

Monitoring
Fire Pump

Controller

analysis
Time Stamped Data
Multiple Data Sets1

Test Date A X X X X X
Test Reference Identifier A X X X X X
Data Set Reference Identifier A X X X X X
Suction Pressure A X X X X X
System Pressure A X X X X X
A
• A – Controller should access and record data automatically
• M – Requires Manual Input at time of installation or test
• M/A – Probably Requires Manual Input at time of installation or test but may be able to Record
Automatically
1A “Record Data Now Button” or input from a tablet or computer is needed to record each set and / or

subset of performance data along with the Test and Data Set Identifier, recommend providing for a
minimum of 5 data sets for constant speed pumps and 7 data sets for variable speed pumps

Aon Fire Protection Engineering 37


Connectivity – Performance Data

Table D.8.2.5 Recommended Performance Data


Data Accessible To

Information Source*

Remote Operations
Independent 3rd
party statistical

Diesel Engine
Manufacturer

Manufacturer

Manufacturer
Performance
Supervision
Monitoring

Monitoring
Fire Pump

Controller

analysis
Time Stamped Data
Multiple Data Sets1

Flow through pump M/A X X X X X


RPM adjusted Net Pressure A X X X X X
RPM adjusted Flow A X X X X X
% of Factory Certified Curve A X X X X X
Hours on diesel engine or electric motor A X X X X X
Maximum System flow Demand (at
M X X X X X
pump discharge Flange)
Maximum System pressure Demand (at
M X X X X X
pump discharge Flange)
Pump passed initial test M X X X X X
Pump could supply maximum system
M X X X X X
demand

• A – Controller should access and record data automatically


• M – Requires Manual Input at time of installation or test
• M/A – Probably Requires Manual Input at time of installation or test but may be able to Record
Automatically
1A “Record Data Now Button” or input from a tablet or computer is needed to record each set and / or

subset of performance data along with the Test and Data Set Identifier, recommend providing for a
minimum of 5 data sets for constant speed pumps and 7 data sets for variable speed pumps

Aon Fire Protection Engineering 38


Maintenance Data

Table D.8.2.6 Maintenance Data


Data Accessible To

Information Source*

Remote Operations
Independent 3rd
party statistical

Diesel Engine
Manufacturer

Manufacturer

Manufacturer
Performance
Supervision
Monitoring

Monitoring
Fire Pump

Controller

analysis
Data

Date of Maintenance / Repair M X X X X X


Maintenance / Repair Identifier M X X X X X
-Pump could supply maximum system
M X X X X X
demand before maintenance / repair
Pump was significantly impaired M X X X X X
Pump was partially impaired M X X X X X
Failure Mode M X X1 X2 X X3
Explanation of Failure M X X1 X2 X X3
Part replaced (1) M X X1 X2 X X3
Part replaced (2) M X X1 X2 X X3
Part replaced (3) M X X1 X2 X X3
Part replaced (4) M X X1 X2 X X3
A
• A – Controller should access and record data automatically
• M – Requires Manual Input at time of installation or test
• M/A – Probably Requires Manual Input at time of installation or test but may be able to Record
Automatically
• 1For Failure Modes and Parts Replacement that involve the fire pump or motor

• 2For Failure Modes and Parts Replacement that involve the fire pump controller

• 3For Failure Modes and Parts Replacement that involve the Diesel Engine Driver
4A “Record Data Now Button” or input from a tablet or computer is needed to record each set and / or

subset of performance data

Aon Fire Protection Engineering 39


Connectivity – Failure Mode

Table D.8.2.7
FAILURE MODE
Water supply inadequate
Electric power supply failure
Pipe, fitting, and/or valve failure:
Controller failure:
Pump running condition failure:
Pump running operation failure:
Relief valve failure:
Diesel engine failure:
Diesel engine system failure:
Component Failure (Identify
Component)
Other (provide comment)

Aon Fire Protection Engineering 40


Connectivity – Components List

Table D.8.2.8
Components List
Impeller
Shaft
Bearings
Electric Motor
Diesel Engine
Batteries
Controller
Circuit Board
Relief valve
Check Valve
Control Valve

Aon Fire Protection Engineering 41


Connectivity – ModBus Registers
Table D.8.2.9.1(a)
Recommended Standardized Electric Motor Controller Modbus Register Definitions
Permanen
ModBus Analog or
Register Use Format t / Static
Register Digital
/Dynamic
40001 AC Volts lines 1-2 A xxxxx D
40002 AC Volts lines 2-3 A xxxxx D
40003 AC Volts lines 3-1 A xxxxx D
40004 AC Amps line 1 A xxxxx D
40005 AC Amps line 2 A xxxxx D
40006 AC Amps line 3 A xxxxx D
40007 System Pressure (psi or bars) A xxxx.x or xxx.xx1 D
40008 Suction Pressure (psi or bars) A xxxx.x or xxx.xx1 D
40009 VFD Speed (HZ) A Xxxxx D
40010 Aux Input #1, 0-100% A xxxxx D
40011 Aux Input #2, 0-100% A xxxxx D
MODBUS REGISTER DESCRIPTION ALARM ON STATE
40012 Alarm Register #1 D
Minimum Run Delay Timing High D bit-0 D
Accelerate Delay Timing High D bit-1 D
High Zone Delay Timing High D bit-2 D
Sequence Delay Timing High D bit-3 D
Load Shed Active High D bit-4 D
Low Discharge Pressure Alarm High D bit-5 D
Low Suction Alarm High D bit-6 D
Low Suction Shutdown Active High D bit-7 D
System Over Pressure Alarm High D bit-8 D
Restart Delay Timing High D bit-9 D
Weekly Test Demand Active High D bit-10 D
Failure to Start Alarm High D bit-11 D
Lockout Active High D bit-12 D
VFD Ready High D bit-13 D
VFD Forward Command Active High D bit-14 D
VFD Reverse Command Active High D bit-15 D

NA: Not applicable. P: Permanent. S: Static. D: Dynamic


*One decimal place assumed if psi and two decimal places assumed if bar.

Aon Fire Protection Engineering 42


NFPA 2019 Proposals

Move All or part of Connectivty Annex to Body of Standard

Aon Fire Protection Engineering 43


NFPA 2019 Proposals (continued) _ Power

3.3.39 Power
3.3.39.1 Alternate Power. An power source that is available
independently of the primary power supply.
3.3.39.2 On-Site Power Production Facility. An on-site The
normal supply of electric power for the site that is expected to be
constantly producing power.
3.3.4039.3* On-Site Standby Generator. A facility producing
electric power on site as the alternate supply of electrical power.
It differs from an on-site power production facility, in that it is not
constantly producing power. [70:695.2]
3.3.39.4 Standby Power: An alternate power source this is
normally inactive but becomes active whenever the primary
power is lost.

Aon Fire Protection Engineering 44


NFPA 2019 Proposals (continued) - Power

4.26.9 The pressure maintenance pump shall not be required to


have alternate secondary or standby power.
5.5 Alternate Auxiliary Power. Where electric motor–driven fire
pump(s) are used, a reliable alternate emergency source of
power in accordance with Section 9.6 or a back-up fire pump in
accordance with Section 9.3 shall be provided for the fire pump
installation.

Aon Fire Protection Engineering 45


Remote Supervision of Non-Flow Fire Pump Test

4.3 Pump Operation.


4.3.1 Except as permitted in 4.3.2, In the event of fire pump
operation, qualified personnel shall respond to the fire pump
location to determine that the fire pump is operating in a
satisfactory manner whenever the fire pump is operating.
4.3.2 Where remote monitoring that meets NFPA 72 and all of
the following requirements, qualified personnel shall be
permitted to monitor the no-flow test remotely.
– 1) Visual observation adequate to verify the appropriate water
discharge thought the packing.

Aon Fire Protection Engineering 46


Remote Supervision of Non-Flow Fire Pump Test

– 2) Visual observation of both sides of the pump adequate to


identify smoke emitted from the pump, pump driver or
controller.
– 3) Smoke detection
– 4) Suction pressure
– 5) Discharge pressure
– 6) Unusual noise
– 7) Diesel engine temperature and oil pressure
– 8) Room temperature
– 9) Pump Speed
– 10) Pump or motor vibration
– 11) Flow through the circulation relief valve

Aon Fire Protection Engineering 47


Remote Supervision of Non-Flow Fire Pump Test

– 12) Discharge through the main pressure relief valve (when


provided)
– 13) Temperature of pump impeller casing
– 14) Temperature of pump packing
– 15) Visual and audible alarm for abnormal
– a) Suction pressure
– b) Discharge pressure
– c) Diesel engine temperature
– d) Room temperature
– e) Pump Speed (in excess of ±5% of rated speed)
– f) Pump or motor vibration
– g) Flow through the circulation relief valve
h) Discharge through the main pressure relief valve (when
Aon Fire Protection Engineering 48
provided)
Remote Supervision of Non-Flow Fire Pump Test

– h) Discharge through the main pressure relief valve (when


provided)
– i) Temperature of pump impeller casing
– j) Temperature of pump packing
16) Qualified shall respond to the pump house on an abnormal
alarm within 5 minutes
17) The value of each point monitored shall be recorded a
minimum frequency of every 2 minutes for a 10 minute test and
every 5 minutes for a 30 minute test..

Aon Fire Protection Engineering 49


Questions

Aon Fire Protection Engineering 50