Professional Documents
Culture Documents
Micrologic A Manual PDF
Micrologic A Manual PDF
User manual
All Compact NS800-3200 and Masterpact Micrologic 2.0 A: basic protection and ammeter
NT and NW circuit breakers are equipped
E51352A
E51384A
Micrologic 2.0 A
t
with a Micrologic control unit
that can be changed on site.
Control units are designed to protect
power circuits and connected loads. 100 %
40 %
menu
long time
0 Ir Isd I
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
instantaneous
Isd
3 4 5
2.5
2
1.5
x Ir
6
10
8 Long time + Instantaneous
setting
Micrologic 2.0 A
E51450A
E51354A
Micrologic 5.0 A
t
X
Y
100 %
40 %
Z Ir
.6
.5
.7
.4
Isd 4
3
menu
long time
.8
x In
short time
5
.9
1
.95
tr
(s) 4 8 12
.98 1
tsd
(s)
2
.5
16
20
24
at 6 Ir
.4 .4 .3
Ii
6
alarm
instantaneous
8 10
0 Ir Isd Ii I
X: type of protection
x Ir x In
setting delay
Micrologic 6.0 A
t
E51395A
E51354A
t
"0" signifies the first generation.
Z: type of measurement 2
I t on
c A for "ammeter"
c P for "power meter" 100 %
2
I t off
c H for "harmonic meter" 40 %
c no indication: no measurements
menu
long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6
.5
.4
x In
1
.95 2
.98 1
.5
16
20
24
at 6 Ir
0 Ir Isd Ii I 0 Ig I
short time instantaneous
Isd tsd Ii
3
4 5 (s) . 4 .4 . 3 6
8 10
2.5
2
1.5
x Ir
setting
10
6
8
.3
.2
on
.1 2 0
I t
delay
.2
.1
4
3
2
x In
12
15
off Long time + Short time Ground-fault protection
test
Ig
C
B
D E F
I
G
H
tg
(s)
.3
.2
. 4 .4 .3
.1 2 0
.2
.1
+ Instantaneous
A
on I t off
ground fault
E51354A
E51452A
Micrologic 7.0 A
t
100 %
40 %
menu
I∆n
long time
Ir
.6
.5
.7
.8
.9
tr
(s) 4
.95 2
.98 1
8
12
16
20
alarm
0 Ir Isd Ii I 0 I
.4 1 .5 24
x In at 6 Ir
2.5
2
3
4 5
6
8
tsd
(s)
.3
.2
.4 .4 .3
.1 2 0
.2
.1
Ii
4
3
6
8
10
12
15
Long time + Short time Earth-leakage protection
1.5 10 on I t off 2 off
+ Instantaneous
x Ir x In
setting delay
test
E51389B
E51390A
1 top fastener 1
2 bottom fastener
3 protective cover 10
4 cover opening point logic
7.0 A
Micro
5 lead-seal fixture for protective cover
6 long-time rating plug 31
7 screw for long-time rating plug 12
8 connection with circuit breaker 11
9 infrared link with communications interfaces 13 9
10 terminal block for external connections 100 %
menu long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
1 24
.6 .98 .5 Ir
.5 at 6
Adjustment dials .4 x In
1
5 7
14 long-time current setting Ir
15 long-time tripping delay tr 3 6
16 short-time pickup Isd
17 short-time tripping delay tsd 4 8
2
18 instantaneous pick-up Isd
19 instantaneous pick-up Ii
20 ground-fault pick-up Ig Micrologic 7.0 A Micrologic 2.0 A
21 ground-fault tripping delay tg
E51391B
E51394A
22 earth-leakage pick-up I∆n 24 25 26 27 28
23 earth-leakage tripping delay ∆t Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm
7
.6 .95 2 16
14 .5
.4 1
.98 1
.5
20
24
Indications Micrologic 7.0 A
15
x In
instantaneous
at 6 Ir
Isd
3 4 5
31 2.5 6
x Ir
25 LED indicating short-time tripping setting
14
Ir
.7
long time
.8
.9
tr
(s) 4
8
12
alarm 28 1.5
x Ir
10
on
.1 2
I t
0 2
x In
off
.6
.5
.95 2
.98 1
16
20
17 setting delay
230
test
32
5 350
3 7
2 10
22 1
.5 30
20
140
60
800 33 Micrologic 6.0 A
earth leakage
E51392A
23 15 long time
Ir
.7
.8
.9
tr
(s) 4
8
12
alarm 28
.6 .95 2 16
14 .5 .98 1
.4
x In
1 .5
20
24
at 6 Ir
7
17 Isd
short time
tsd Ii
instantaneous
3
4
5 (s) .4 .4 .3 6
8
10
2.5 .3 .2
16 2
6
8 .2 .1
4
3
12
15 19
1.5 10 .1 2
0 2 off
x Ir on I t off x In
21 Ig
setting
tg
delay
test
32
D
E
F (s) .4 .4 .3
C G .3 .2
20 B H .2
.1 2 0
.1
33
A I
on I t off
ground fault
Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.
Micrologic 2.0 A
E51358A
t
1
0 Ir Isd I
1. current setting Ir (long time)
2. tripping delay tr (long time) for 6 x Ir
3. pick-up Isd (instantaneous)
E51386A
E51396A
1
2
I t on 2
I t on
2
2
I t off 2
1 I t off 1
3
4 2 2
5
0 Ir Isd Ii I 0 Ig I 0 I∆n I
1. current setting Ir 1. pick-up Ig (ground 1. pick-up I∆n
(long time) fault) (earth leakage)
2. tripping delay tr 2. tripping delay tg 2. tripping delay ∆t
(long time) for 6 x Ir (ground fault) (earth leakage)
3. pick-up Isd (short time)
4. tripping delay tsd
(short time)
5. pick-up Ii
(instantaneous)
Long-time protection
The long-time protection function protects cables (phases and neutral)
against overloads. This function is based on true rms measurements.
Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of
an overload or not). The thermal memory optimises the long-time protection
function of the circuit breaker by taking into account the temperature rise in the
cables. The thermal memory assumes a cable cooling time of approximately
15 minutes.
Instantaneous protection
c the instantaneous-protection function protects the distribution system
against solid short-circuits. Contrary to the short-time protection function,
the tripping delay for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds
the set value, with a fixed time delay of 20 milliseconds.
c this function carries out true rms measurements.
Instantaneous pick-up Ii
Micrologic control unit 5.0 A, 6.0 A and 7.0 A
pick-up li = In (*) x … accuracy ± 10 % 2 3 4 6 8 10 12 15 OFF
Type Description
Residual c the function determines the zero-phase sequence
current, i.e. the vectorial sum of the phase and neutral
currents
c it detects faults downstream of the circuit breaker.
Source Ground Return c using a special external sensor, this function
directly measures the fault current returning
to the transformer via the earth cable
c it detects faults both upstream and downstream
of the circuit breaker
c the maximum distance between the sensor
and the circuit breaker is ten metres.
Overload LED
E51398B
long time
Ir tr alarm
.8 (s) 4
8
.7 .9 12
.6 .95 2 16
.5 .98 1 20
.4 1 .5 24
x In at 6 Ir
This LED signals that the long-time current setting Ir has been overrun.
E51400A
Caution.
The battery maintains the fault indications.
If there are no indications, check the
battery.
E51402A
If no information is displayed on the screen, c all Micrologic control units measure the true rms value of currents
c the most heavily loaded phase is continuously displayed on the digital screen
see the technical appendix "Digital display".
c using the navigation buttons, it is possible to display successively the I1, I2, I3,
neutral IN, Ig, I∆N and stored-current (maximeter) values
c the percent load on each phase is displayed. A bargraph displays the currents
measured on phases 1, 2 and 3 as a percentage of the long-time current setting Ir.
E60371A
1.125 x Ir
100 % 1 x Ir
0.8 x Ir
0.6 x Ir
40 % 0.4 x Ir
Example
For a circuit breaker with a 4000 A rating and a current displayed on Micrologic of
49 A, the accuracy is:
0.5% x 4000 + 1.5% x 49 = ± 21 A
E51383A
/2
3D+N
4P 4D
4P 3D
Setting procedure
1. Open the protective cover.
E51411A
E51410A
7.0 A 7.0 A
logic logic
Micro Micro
Ir=
A
1
menu
automatically displayed
2 on the digital screen in
absolute value with the
relevant units.
c Current in amperes
(A and kA);
c Tripping delays in
seconds.
E51412A
40 %
menu
See the user manual for the portable Using the portable test kit
test kit To test the control unit, connect the portable test kit via the test connector.
E51410A
E51413A
7.0 A 7.0 A
logic logic
Micro Micro
100 % 100 %
40 % 40 %
menu
1 menu
E60365A
long time
alarm
In = 2000 A
E51366A
Ir .8
.7 .9
.6 .95 Ir = 0.7 x In = 1400 A
.5 .98
.4 1 Isd = 3 x Ir = 4200 A
x In
instantaneous
Isd
3 4 5
2.5 6
2 8
1.5 10
x Ir
1 setting
In = 2000 A
A
2000
In =
t
on the available settings Ir
Isd
0 I
long time tr = 1 s
tr alarm
(s)
8
4 12
2 16
1 20
.5 24
at 6 Ir
E51370A
tr
0 I
E60367A
long time In = 2000 A
E51366A
Ir alarm
.8 .9
.7 Ir = 0.7 x In = 1400 A
.6 .95
.5 .98
.4 1
Isd = 2 x Ir = 2800 A
x In
short time instantaneous Ii = 3 x In = 6000 A
Isd 4 5 Ii
3 6 8 10
2.5 6 4 12
2 8 3 15
1.5 10 2 off
x Ir x In
1 setting
In = 2000 A
A
2000
In =
long time tr = 1 s
Thresholds tr alarm
(s) 8 12
4
I2t ON curve I2t OFF curve 2 16
1 20
E51373A
E51372A
t
Ir
t
Ir .5 24 tsd = 0.2 s
at 6 Ir
short time
tsd
(s) .4 .4 .3
.3 .2 I2t on I2t off
Isd Isd
.2 .1
.1 2 0
on I t
Ii Ii
delay
0 I 0 I
Tripping delays
I2t ON curve I2t OFF curve
E51376A
E51375A
t t
tr tr
tsd tsd
0 I 0 I
E51414A
long time
alarm
In = 2000 A
E51366A
Ir .8
.7 .9
.6 .95
.5 .98
.4
x In
1 Ir = 0.7 x In = 1400 A
short time instantaneous
Isd Ii
3 4 5 6 8 10 Isd = 2 x Ir = 2800 A
2.5 6 4 12
2 8 3 15
1.5 10 2 x In off
x Ir Ii = 3 x In = 6000 A
1 setting
test
Ig
D E F
C G
B Ig = 640 A
In = 2000 A B H
A
A I
2000
In =
ground fault
long time
Thresholds tr alarm
(s) 4
8
12 tr = 1 s
I2t ON curve I2t OFF curve 2 16
1 20
E51373A
E51372A
t t .5 24
Ir Ir at 6 Ir
short time
tsd
(s) .4 .4 .3 tsd = 0.2 s
.3 .2
Isd Isd .1
.2
.1 2 0 I2t on I2t off
on I t off
Ii Ii delay
test
tg
0 I 0 I (s)
.4 .4 .3
.3 .2
E51416A
E51415A
t t
.2 .1 tg = 0.2 s
.1 2 0
on I t off
ground fault
Ig Ig
0 I 0 I
Tripping delays
I2t ON curve I2t OFF curve
E51376A
E51375A
t t
tr tr
tsd tsd
0 I 0 I
E51418A
t
E51419A
tg tg
0 I 0 I
E51420A
long time
Ir alarm
E51366A
.8 .9
.7
.95
In = 2000 A
.6
.5 .98
.4 1
Ir = 0.7 x In = 1400 A
x In
short time instantaneous Isd = 2 x Ir = 2800 A
Isd Ii
3 4 5 6 8 10 Ii = 3 x In = 6000 A
2.5 6 4 12
2 8 3
1.5 10 2
15
off
I∆n = 1 A
x Ir x In
1 setting
test
I∆n
(A) 3 5 7
2 10
1 20
In = 2000 A .5 30
A
2000
In =
earth leakage
long time
Thresholds tr alarm tr = 1 s
(s) 4 8 12
I2t ON curve I2t OFF curve 2 16
1 20
E51373A
E51372A
t t .5 24
Ir Ir at 6 Ir
short time
tsd tsd = 0.2 s
.4 .4 . 3
(s)
.3 .2
Isd Isd .2 .1
.1 2 0
on I t off
I2t on I2t off
Ii Ii delay
test
∆t
(ms) 230
0 I 0 I 350
140
E51421A
t
800
60 ∆t = 140 ms
earth leakage
I∆n
0 I
Tripping delays
I2t ON curve I2t OFF curve
E51375A
E51376A
t t
tr tr
tsd tsd
0 I 0 I
t
E51423A
∆t
0 I
The procedure for closing the circuit Resetting the fault indications
c determine why the circuit breaker tripped.
breaker following a fault trip is presented
The fault indication is maintained until it is reset on the control unit.
in the circuit-breaker user manual. v press the fault-trip reset button.
E51439A
Micrologic 7.0 A
Press the battery-test button (same as the fault-trip reset button) to display
the battery status.
E51441A
40 %
E51445A
100 %
40 %
E51456B
7.0 A
logic
Micro
100 %
40 %
menu
If the circuit breaker does not open, contact the Schneider after-sales
support department.
Symbols used: Three menus may be accessed on Micrologic control units, providing the following
information:
E51404A
c phase current measurements I1, I2, I3, neutral IN, ground-fault current Ig on the
Micrologic 6.0 A control unit and earth-leakage current I∆n on the Micrologic 7.0 A
control unit;
c maximeter current values for phases I1, I2, I3, neutral IN, the maximum ground-
Briefly press a key. fault current Ig on the Micrologic 6.0 A control unit and the maximum earth-leakage
current I∆n on the Micrologic 7.0 A control unit;
c protection settings and tripping delays.
E51405A
E51406A
E51407A
E51408A
Press and hold a key. Max
Ir=
A A A
Press the "menu" button Press the "menu" button Press the "menu" button
to access the maximum to access the protection to return to the current
current values measured settings and tripping measurements.
by the maximeter. delays.
100 %
40 %
Current values may be read in the Display of current I1. Display of current I2. Display of current I3.
"Measurements" menu, which is also the
E51425A
E51426A
E51427A
main menu.
A A A
If no particular action is taken, the system
displays the current value of the most
heavily loaded phase.
"Measurements" menu
100 % 100 % 100 %
Phase 1 is the most heavily loaded.
E51409B
40 % 40 % 40 %
A
Press the "arrow" button Press the "arrow" button Press the "arrow" button
100 % to go on to current I2. to go on to current I3. to go on to current IN if
the neutral is protected.
E51428A
E51409B
A A A
40 % 40 % 40 %
Maximum current values may be read in Display of the Display of the Display of the
maximum I1 current. maximum I2 current. maximum I3 current.
the "Maximeter" menu.
E51430A
E51431A
E51432A
MAX MAX MAX
If no particular action is taken, the system A A A
returns to the main menu.
"Maximeter" menu.
E51407A
A
40 % 40 % 40 %
100 % Press the "arrow" button Press the "arrow" button Press the "arrow" button
to go on to the maximum to go on to the maximum to go on to the maximum
I2 current. I3 current. current IN if the neutral is
40 % protected.
menu
E51433A
E51435A
MAX MAX MAX
A A A
40 % 40 % 40 %
Maximum current values can be reset Select the maximum Reset. Select another value
current value to be to reset or return to
using the "Maximeter" menu.
reset (e.g. I2 max.). the main menu.
E51436A
E51437A
E51438A
returns to the main menu. MAX MAX MAX
A A A
"Maximeter" menu.
E51407A
Max
A
100 % 100 % 100 %
40 % 40 % 40 %
100 %
40 %
Press the "arrow" button Press and hold the Press the "arrow" button
menu as many times as "arrow" button down for as many times as
required to select I2 max. three to four seconds. required to select another
The current value flashes maximum value to reset
during the reset, then or return to the main
changes to the present menu.
value (the new
maximum).
Or
Ig= A
Or
E71903A
E71904A
E71905A
set. Note that the COM module should be
set up only when installed. Modification of a A
c language.
E71907A
E71908A
40 % 40 % 40 %
Set the baud rate, then go on to the next Set the parity.
parameter.
5. Language
E71909A
E71910A
E71911A
40 % 40 % 40 %
E60369A
10 000
5 000 Ir = 0.4…1 x In
2 000
1 000
500
200
100 tr = 0.5…24 s
50
20
10
5
t(s)
2
Isd = 1.5…10 x Ir
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
10 000
5 000 Ir = 0.4…1 x In
2 000
1 000
500 tr = 0.5…24 s
200
100
50
20
10
5
t(s) Isd = 1.5…10 x Ir
2
1
I2t ON
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
0.1 0. 1
.1 I2t OFF
0 0
.05
Ii = 2…15 x In . OFF (1)
.02
.01
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
x Ir x In
E46266A
10 000
5 000
2 000
Ig = A…J x In (1)
1 000 1200 A max.
500
200
100
50
20
10
5
t(s) I2t ON
2
1
.5 0.4 0.4
0.3 0.3
.2 0.2 0.2
2 0.1 0.1
.1 It OFF
0 0
.05
.02
.01
.005
.002
.001
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I / In
Caution.
Change the long-time rating plug
Following any modifications to the long-
Proceed in the following manner.
time rating plug, all control-unit protection
parameters must be checked. 1. Open the circuit breaker.
2. Open the protective 3. Completely remove
cover of the control unit. the long-time rating plug screw.
E51378A
E51379A
7.0 A 7.0 A
logic logic
Micro Micro
100 % 100 %
40 % 40 %
menu menu
Caution. 4. Snap out the rating 5. Clip in the new rating plug.
If no long-time rating plug is installed, the plug.
6. Refit the screw for the
E51380A
100 %
disabled.
menu
alarm
long
time tr 8 12 100 %
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
40 %
menu
alarm
long
time tr 8 12
(s) 4 16
Ir .8 .9
.7 2 20
.95
.6 1 24
.98 .5 @ 6 Ir
.5 1
.4 x In
Operating principle
c A fault occurs at point A.
Downstream device no. 2 clears the fault and sends a signal to upstream device
no. 1, which maintains the short-time tripping delay tsd or the ground-fault tripping
delay tg to which it is set.
c A fault occurs at point B.
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the set time delay is not taken into account and the device
1 B trips according to the zero setting. If it is connected to a device further upstream, it
sends a signal to that device, which delays tripping according to its tsd or tg setting.
Note :
On device no. 1, the tsd and tg tripping delays must not be set to zero because this
would make discrimination impossible.
2
A
Caution. Wiring
If the protection function is not used on c maximum impedance: 2.7 Ω / 300 metres
circuit breakers equipped for ZSI c capacity of connectors: 0.4 to 2.5 mm2
protection, a jumper must be installed to c wires: single or multicore
short terminals Z3, Z4 and Z5. c maximum length: 3000 metres
c limits to device interconnection:
If the jumper is not installed, the short-time v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)
and ground-fault tripping delays are set can be connected to a maximum of 10 inputs;
to zero, whatever the position of the v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and
adjustment dial. to an input ZSI - IN CR (Z4) or GF (Z5).
E71912A
point B
2 Z1
Z2
Z3 tsd = 0.2
Z4
Z5
point A
Z1 downstream Z1
Z2 circuit-breaker Z2
Z3 Z3
Z4 Z4
Z5 Z5
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
For information on connecting an external c display of measurements operates without an external power supply.
The digital display goes off if the current drops below 0.2 x In (In = rated current).
power supply, see the electrical diagrams
An optional 24 V external power supply may be used to maintain the display of
in the circuit-breaker user manual. currents.
c the maximeter does not operate for currents under 0.2 x In.
The display back-lighting and the maximeter may be maintained, whatever the
current, by adding a 24 V external power supply. Even if an external power supply
is installed, the long-time, short-time, instantaneous and earth protection functions
will not use it.
Thermal memory
The thermal memory is the means to take into account temperature rise and
cooling caused by changes in the flow of current in the conductors.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
c for long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping
curves.
04443724AA-B 10-01