1/11 SiteStar alarm installation instructions

SiteStar Alarm connection with FPRA Flexi


Power Rectifier module
2/11 SiteStar alarm installation instructions

The information in this document is subject to change without notice and describes only the product defined in the
introduction of this documentation. This document is intended for the use of Nokia Siemens Networks customers only for
the purposes of the agreement under which the document is submitted, and no part of it may be used, reproduced,
modified or transmitted in any form or means without the prior written permission of Nokia Siemens Networks. The
document has been prepared to be used by professional and properly trained personnel, and the customer assumes full
responsibility when using it. Nokia Siemens Networks welcomes customer comments as part of the process of continuous
development and improvement of the documentation.
The information or statements given in this document concerning the suitability, capacity, or performance of the mentioned
hardware or software products are given “as is” and all liability arising in connection with such hardware or software
products shall be defined conclusively in a separate agreement between Nokia Siemens Networks and the customer.
However, Nokia Siemens Networks has made all reasonable efforts to ensure that the instructions contained in the
document are adequate and free of material errors and omissions. Nokia Siemens Networks will, if deemed necessary by
Nokia Siemens Networks, explain issues which may not be covered by the document.
Nokia Siemens Networks will correct errors in the document as soon as possible. IN NO EVENT WILL NOKIA SIEMENS
NETWORKS BE LIABLE FOR ERRORS IN THIS DOCUMENT OR FOR ANY DAMAGES, INCLUDING BUT NOT
LIMITED TO SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL OR ANY MONETARY
LOSSES,SUCH AS BUT NOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESS
OPPORTUNITY OR DATA,THAT MAY ARISE FROM THE USE OF THIS DOCUMENT OR THE INFORMATION IN IT
This document and the product it describes are considered protected by copyrights and other intellectual property rights
according to the applicable laws.
Wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark of Nokia Corporation. Siemens
is a registered trademark of Siemens AG.
Other product names mentioned in this document may be trademarks of their respective owners, and they are mentioned
for identification purposes only.
Copyright © Nokia Siemens Networks 2009. All rights reserved.
3/11 SiteStar alarm installation instructions

Version History

Version Date Author Comments


Marko P Komulainen
0.1 24th August 2009 First Draft
Kari Immonen
1.0 10th September 2009 Marko P Komulainen 1st release

2.0

Abbreviations
AC Alternating Current

DC Direct Current

BTS Base Transceiver Station

NO Normal Open

NC Normal Closed

EAC External Alarm Connection

FPRA Flexi Power Rectifier

PDA Power Distribution Assembly

CLU Climate control Unit


4/11 SiteStar alarm installation instructions

Table of contents

Version History ..................................................................................... 3

1. Introduction ............................................................................ 5

2. SiteStar Description ............................................................... 6

3. FPRA Alarm Descriptions ...................................................... 7

4. FPRA Alarm Interface Card ................................................... 9


4.1 Alarm Cable Installation ...................................................................................10
5/11 SiteStar alarm installation instructions

1. Introduction
This document gives supplementary information for connecting the SiteStar battery
cabinet alarm cable to the FPRA Flexi Power Rectifier module.

Full details on the installation of the SiteStar cabinet unit can be found in the
SiteStar Installation Manual, which is supplied with cabinet.

Alarm connection details for connecting FPRA further to both GSM/EDGE and
WCDMA applications please refer to separate FPRA Alarm Connection document.

Note: SiteStar cabinet delivery includes alarm cable between the cabinet and
FPRA.
6/11 SiteStar alarm installation instructions

2. SiteStar Description
SiteStar is a cabinet housing batteries either up to 2 strings or 4 strings depending
on the cabinet type. Cabinet is primarily meant to be used together with FPRA
Flexi Power Rectifier to power the BTS and charge the batteries inside SiteStar
cabinet.

SiteStar cabinet provides multiple alarms bundled into a single alarm output.
The alarm can either be connected as normally closed (NC) or normally open
(NO). The external alarm will be triggered by:
• CLU failure: compressor fail, heater fail (if equipped), fan fail or controller fail
• Temperature: Internal temperature outside regulation window or external
temperature outside system specification
• Door open
• Mains failure

During cabinet startup sequence the external alarm will be trigged several times.

Ext Alarm 9-pol D-SUB connection is following:


Pin1 NO
Pin2 COMMON
Pin3 NC
Pin8 +12VDC
Pin9 Ground
7/11 SiteStar alarm installation instructions

3. FPRA Alarm Descriptions


The PDA supplies six isolated and floating EAC alarms to the BTS, which are
summarized in Table 1 below.
‘Ext Alarm In’ should be used to connect SiteStar alarm into FPRA and then
‘remote battery test’ functionality is disabled.

EAC alarm Description (see Note)

Main 1
Mains phase failure indicates any single phase voltage of the 3-
Main 2
phase FPRA power source configuration that is below 85VAC
Main 3

Critical • Battery low voltage


• PDA controller fail
• DC distribution failure (e.g. Circuit Breaker tripped)

Major • Battery test failure


• Rectifier fail
• High float voltage
• Rectifier Fan Failure
• Input voltage too high or too low (rectifier shutdown)
• Surge Protection Device tripped

Minor • Battery temperature High/Low


• Rectifier temperature High
• Rectifier over current
• Extended mains voltage range
• Low mains voltage range

Ext Alarm In • Remote-start for Battery Test (as default or SiteStar alarm in)

Table 1: Alarm Description

NOTE:
- these are the factory-default alarm settings
- user can re-configure the alarm settings as required
8/11 SiteStar alarm installation instructions

Full details of alarms and their configuration can be found in the FPRA User
Manual, which is supplied with the unit.
9/11 SiteStar alarm installation instructions

4. FPRA Alarm Interface Card


Figure 3 shows the FPRA Alarm Interface Card

Figure 3: Alarm Interface Card

To detach the card from the PDA, loosen the two screws with a cross headed
screwdriver, and pull the card out of the PDA (see Figure 4).

Figure 4: Removing the Alarm Interface Card


10/11 SiteStar alarm installation instructions

4.1 Alarm Cable Installation


SiteStar alarm cable is connected to the J11 connector of the Alarm Interface Card,
see Figure 5.

Figure 5.

SiteStar D-sub connector Cable FPRA alarm board – J11 connector

Pin 1 (NO) Brown** Pin1 (-)

Pin 2 (COMMON) Red No connection, connect together with


Black wire*

Pin 3 (NC) Orange No connection

Pin 8 (+12VDC) White** Pin2 (+)

Pin 9 (GND) Black No connection, connect together with


Red wire*

* NOTE: Connects SiteStar Pin2 and Pin9 together.

** NOTE: Correct wire colours shown on table above, not on Figure5.


11/11 SiteStar alarm installation instructions

The procedure for installing and grounding the Alarm cable is as follows:

• Connect the screening to position ‘A’ on the drawer assembly with a cable-tie (refer to
Figure 6 for details) Ensure the cable screen firmly touches the sidewall of the drawer
as this provides the grounding of the cable screen.

J11
Figure 6.

• Push the drawer back into its slot horizontally until the drawer pin matches the internal
connector of the PDA and secure the two thumbscrews.

NOTE: IT IS RECOMMENDED THAT THE USER WEAR AN ANTI-STATIC STRAP


CONNECTED TO AN APPROPRIATE GROUNDING POINT PRIOR TO CARRYING OUT
ANY ALARM CABLE INSTALLATION