Professional Documents
Culture Documents
1E{TERl{ATt0}tArE
(affili6e
i l'0rganisation
Internationale - lS0)
deNormalisation
B E C t l M M A I I l l A T lIl(El I tI A C E I
II{TERt{ATI(lilE
ATL E C T R t l T E C H I { IC
C (A} LM M I S S I ( | N
(affiliated
to the International
Organization - lS0)
for Standardization
IE C RECl|MMEl{llATIll}I
Publication
99-lA
Premidre - Firstedition
6dition
1965
Gomplfment
i la Publication
99-lll95Sl
pourlesparaloudres
Recommandations
partie:Parafoudres
Premi0re i rdsistance
uariable
Supplement
l0 Publication
99-lll95Sl
Recommendalions lor lightning
arresters
Partl: l,lon-linear
resistor-type
arresters
Bureau
Central
de la Commission
Electrotechnioue
lnternationale
1 , r u ed eV a r e m b 6
Gendve,
Suisse
c 0 t f i t | l t s s t 0Ei L
t E c T R 0 T E G H i i l t01u{ E
TERilATt0ilALE
(affili6e
i l'0rganisation
Internationale - lS0)
deNormalisation
R EC l l IIIM A TIl l A TI(l
D EIItA CE I
IT{TERl{A
t lTI I A L E L E G T B ( l C
TEH l { I C A LC ( l M MSI S I t l T I
(affiliated
to the International
0rganization - lS0)
for Standardization
IE C REC{lMMEilDATIllII
g9-lA
Publication
Premidre - Firstedition
ddition
1965
Complfment
e la Publication
99-lll95Sl
pourlesparafoudres
Recommandations
partie:
Premiire Paraloudres
i r6sistance
uariable
Supplemcnt
t0 Publication
99-l[95S1
Recommendations lor lightning
arresters
Partl: l{on-linear
resistor-type
arresters
PERPLlST{KA,{N
P U S A TP E $ V E L l 0 l l i l | l i l A g t t l H l t L i S T ? r t ( r {
- '\-.,-j1) *
t
n". {grade : .i (i .ii i
I
I
rarrsgal ,
I
t--
Z S A P Ri ? ' l ' l
Bureau
Central
de la Commission
Electrotechnique
Internationale
1, ruedeVarembd
6endve.
Suisse
-3-
CONTENTS
Page
FonEwoRo 5
PnErecE 5
Clause
l. Object.
6. New definitions. 37
6.I Impulse protective level of an arrester 37
6.2 Rated impulse protective level of an arrester 37
6.3 Protective ratio . 37
- 5 -
FOREWORD
I) The formal decisions or agreements of the I E C on technical matters, prepared by Technical Committees on which all the
National Committees having a special interest therein are represented, express, as nearly as possible, an international
consensus of opinion on the subjects dealt with.
2) They have the form of recommendations for international use and they are accepted by the National Committees in that
sense.
3) In order to promote this international unification, the I E C expresses the wish that all National Committees having as
yet no national rules, when preparing such rules, should use the I E C recommendations as the fundamental basis for these
rules in so far as national conditions will permit.
4) The desirability is recognized of extending international agreement on these matters through an endeavour to harmonize
national standardization rules with these recommendations in so far as national conditions will permit. The National
Committees pledge their influence towards that end.
PREFACE
A draft was preparedby a Committee of Experts and was discussedat the meetingsheld in Interlaken
in 1961and in Bucharest in1962. As a resutt of this latter meeting, a draft was submitted to the National
Committeesfor approval under the Six Months' Rule in December 1962.
Australia Netherlands
Belgium Norway
Canada Sweden
Czechoslovakia Switzerland
Denmark Turkey
Finland Union of Soviet
France SocialistRepublics
Germany United Kingdom
Hungary United Statesof America
Japan
5ff.e
- 7
l. Object
The subjectis a broad one with many ramificationsand it would require a volume of considerable
bulk to explain all possiblecasesin detail. It is not proposedto do this in this guide, but the more basic
casesare discussedand step-by-stepdirection toward proper and economicalsolutions are provided. In
some cases,experienceor predeterminedpracticesgive sulficient information for some of thesestepsto be
performed without further consideration.The more complex casesof some installations,to which a number
of linesor cablesare connected,no doubt merit specialstudy by experiencedengineers.
In the present state of the art, complete protection against damagefrom overvoltagemay prove to be
extremely costly and it may not be good engineeringpractice to provide it. Proceduresare recommended
which are expectedto provide conservativesolutions that can be justified economically.Theseprocedures
are basedon theoretical studies,the resultsof tests,and experience.
This guide presumesthat lightning arrester earth terminals are interconnectedwith earthed parts of
equipment, also that both line and earth connectionsof the arresterare as short as is practicable.
The procedure for the selectionand location of arrestersin relation to the insulation to be protected
can be reducedto a seriesof steps,which are elaboratedin subsequentparagraphs:
c) determine the impulse withstand strength of the insulation to be protected, bearing in mind that
air insulation decreaseswith increasinsaltitude;
b-____
-9 -
ol
6,/determine the voltage at the insulation to be protected as limited by the arrester,taking into consi-
deration the separationdistancesand other factors applicableto the point of application;
h) in the event that stepsc) and g) indicate that the arresterselectedis inadequate,it may be necessa-
ry to chooseanother arresterrating or class,or in the casewhen an entirely new station is being
designed,to increasethe insulation levelof the equipmentto be protected.
3.1.1 By multiplying the highest systemvoltage by the coefficientof earthing at the point of
installation of the arrester(Clause l7 in Publication 99-1). The value of the coefficientof
earthing can be estimatedfrom the curves in Figure 1. Experienceshows that for arrester
application the coefficientof earthing can be classifiedinto a limited number of groups.
Note.-lf XolXt lies between 0 and -20, resonance conditions may occur. For systems with isolated
neutrals, the ratio XolXr is, however, usually lower than -20 so that resonance conditions are
not likely.
-***;;;,,**;i*6ll';i
i
-- ll -
a) suddenlossof load ;
Estimate the magnitude and wave shape of the discharge current, largely by the degree of
shielding against direct lightning strokes to lines, stations, substations and distribution transfor-
mer installations.Suchinstallationsmay be divided into two classes:
effectivelyshielded,or
non-effectivelyshielded.
Shielding for line end protection on medium voltage lines located on woodeu poles with
an earth wire which is earthed at each pole, but with no earthing of crossarmsoutside the
protected zone, may not prevent back flashes(back flashovers)if the earth resistanceat the
poles is high. However, the shielding will tap off the lightning stroke current, and also will
limit overvoltagesentering from beyond the shielding. Such overvoltagesmay be very high
becauseof the wood insulation. This shielding, while not fulfilling the requirements for an
effectively-shieldedstation, will limit the magnitude of the discharge current below that
discussedin Sub-clause3.2.2for non-effectively-shielded stations,the amount dependingon the
particular conditions at the installation.
_ 1 3_
d) the length of the shielded portions of the incoming lines. (Minimum values of lengths
involved are under consideration.)
The impulse withstand strength for equipment is defined by its full wave impulse test voltage
(seeTable of Standardinsulation levelsin IEC Publication 71, Recommendationsfor Insulation
Co-ordination).
- 1 5-
Most types of insulation withstand short-duration voltage peaks of higher peak value than
the withstand strengthfor standard full waves.The smallestdifferenceis exhibited by irradiated
spark gaps such as are used in lightning arresters.Next in order are solid insulation, oil and
paper insulation,and finally air gapswith non-uniform field distributionsuchas rod gaps.
The effectof duration of the impulse on the insulation withstand strengthis a complicated
function with great dispersion,and no accuratenumerical information can be given. However,
as a working hypothesisit is generallyassumedthat oil and paper insulation in liquid-filled
transformers has a withstand strength of not less than 157, above its full-wave withstand
strengthfor voltage peaks shorter than 3 microseconds.
Note.- Certain types of solid insulation, such as that in rotating machines and in dry-type transformers (or
or-
:1'il:1ll#:;Hpe'fransf
ffi:';:i:::H":;?J:,.,i:HTn*i3H-,':T"l#,,::r1::,ffi
Determine where necessary,by consultation with the manufacturer, the switching surge
insulation withstand strength of the equipment to be protected in high-voltagestations(100 kV
and higher). This is important when the impulse insulation withstand strengthis more than one
level below the standardinsulationlevels(seeTable in I E C Publication7l) sincein this casethe
need for protection generallyresults from the possibility of switching surgesrather than from
lightn i n g(S u b -c l a u s 3
e .6 .2 .3 .3a n d S ecti on5).
3.4 Tentativelvselectarresters
a) the needfor a medium or low protective level for the insulation to be protected.The l0 000
ampere non-linear resistortype arrestersprovide the best protectivelevels.The 5 000ampere
seriesA arrestersare next, and in Canada and the U.S.A. the 5 000 ampere SeriesB, or in
Europe the 2500 amperearrestersare last (seeTables I I I and IV of Publication 99-l) ;
lL_
-17-
b) the need for the best protection. As a generalrule, l0 000 ampere arresters(referred to in
some countriesas station arresters)are applied to high-voltagesystems(100 kV and above)
and to important stations of lower voltage systemswhich are consideredimportant enough
to require the best protection; 10 000 ampere or 5 000 ampere SeriesA arrestersare used
! on medium voltage transmissionsystems,5 000 ampere SeriesB arrestersor 2 500 ampere
arresterson distribution systemsfor the protection of small transformers;
2) the switching surge conditions indicate the use of arresterswith increasedcurrent dis-
chargecapacity for discharginglong lines, cablesand capacitor banks in casethe circuit
breakersrestrikeor other switchingsurgescausesparkoverof the arrester(Clause5);
The selection of the arrester voltage ratings corresponding to the highest system
voltages(U-) multiplied by the coefficient of earthing, is based on the assumption that in
servicethe highest systemvoltage (t/-) is only exceededunder abnormal operating condi-
tions, and that the probability of an arresteroperation coinciding with a voltage exceeding
the highest system voltage is very small. If abnormal system voltages are likely to be a
frequent occurrence,thereby increasingthe probability of arrester operations during such
conditions, it may be necessaryto use an arresterwith a voltage rating higher than recom-
mended above, dependingupon the particular circumstances.
I
-19-
b) Abnormal systemfrequency
Alternating current of frequencylessthan 48 or more than 62 Hz(c/s)mayrequirespecial
considerationin the manufactureor application of lightning arrestersand should be subject
to discussionbetweenthe user and the manufacturer.
As noted in Sub-clause3.6.3, this tentative choice of arrester classand voltage rating may
require modification.
2. - The procedures in Sub-clauses 3.5.1 and 3.5.2 are sufficient for arresters located close to the insula-
tion to be protected, and with the overhead lines brought directly into the station. The influence
of location of the arrester with respect to this insulation (separation distance) will be discussed in
3.6.2.3. The introduction of a cable between the overhead lines and the installation will be discussed
in Sub-clause 3.6.4.
-?. - Consideration should be given to the need for obtaining the switching surge protective level of the
arrester from the manufacturer. as covered in Sub-clauses3.3.3 and 3.6.2.3.3.
3.6 Co-ordinate the arrester protective level with the impulse withstand strength of the insulation to
be protected
3.6.1 General
The recommendedtreatment is different for different categoriesof installations depending
on whether they are effectivelyshietdedor not, on the number of lines normally connected,and
on the physical extensionof the installation.
There shall be a certain protective ratio provided between the impulse withstand strength
of the equipment installation to be protected (a guaranteedminimum value) and the impulse
protective level which is achievedat the piece of equipment in question under the assumptions
given in Sub-clauses3.3 and 3.5. This protective ratio is intended to cover exceptional cir-
cumstancessuch as abnormally higher magnitude or steepnessof infrequent occurrence.
_21 _
The recommended minimum protective ratio between insulation withstand strength and
impulse protectivelevel is l.2.It is pre-supposedthat the earths of all arrestersand equipment
are directly connectedtogether.
The reduction in the electric strength of air insulation with increasing altitude should be
considered,using the recommendationsfor the specificapparatus.
Install a set of arresters at or close to the transformer or transformers and check the
protective ratio as in the previouscaseof Sub-clause3.6.2.1,taking into account that the
incomirrg overvoltage waves are reduced by sharing of energy when several lines meet
in the station. However, consideration should be given to the casewhen one or more of the
lines are disconnectedby switching.
I Install one set of arrestersat a point which provides protection to all equipment but
givespreferenceto the transformer. Separationbetweenthe arresterand the insulation
to be protected is permissiblein effectively-shielded
installations.
*
I
-23-
3.6.2.3.2 For large installations with several incoming overhead lines, tronsformers. switchgear and
measuring equipment
Determine as well as possible the most strategic arrester locations and the number of
arresterswhich will give the wanted degreeof protection to different piecesof equipment.
This can be rather difficult.
3.6.2.3.3 For installations with transformers having reduced insulation more than one step below
standord insulation levels (see Tables in Publication 7I )
For switching overvoltages,the insulation withstand level as well as the switching surge
impulse protective level of the arresters have values different from those for lightning
overvoltages and, therefore, the insulation coordination for switching surges must be
studied separately(seeSub'clause3.3.3).The results of such a study may lead to modifica-
tion of the arrester arrangement.As no standard values are establishedfor the insulation
co-ordination at switching overvoltages,it may sometimesbe necessaryto obtain guidance
from equipment manufacturers.
If co-ordination is not achievedby the procedure of Sub-clauses3.6.1 and 3.6.2 with the
arrester tentatively selectedin Sub-clause3.4, it becomesnecessaryto consider alternative
measuressuch as:
a) selectingan arrester of better class or lower rating to obtain a lower impulse protective
level.
Selectingan arrester with a lower voltage rating than that indicated by consideration of
-25-
b) changing the location of the arrester to reduce the separation distance and/or
the arrester
lead length;
c) increasingthe insulation level of the equipment to be protected;
d) improving the shielding.
3. 6. 4. 1. 1 G en e ra l
tations of spacefor the arrestersat the equipmentmay also make application at the junction
desirable.
The arrestersinstalled at the equipment should be connectedto the station earth with
the shortestpossiblelead. Arrestersinstalledat the cablejunction should be earthedand
interconnectedat the junction with the cable sheath if a metallic sheath is used. For the
prevention of circulating currentsin the cable sheathsit may not be desirableto earth these
at the equipment end also. If the cable hasa non-metallic sheath,the arresterat the junction
should be earthedat the junction and interconnectedwith the station earth by a conductor
installedadiacentto the cable.
3.6.5.I General
Although the currents through the arresterdue to lightning and switching overvoltagesare
small (up to I 000 A), accountmust be taken of their lonser duration.
Install the arrester between the neutral terminal and earth (i.e. the transformer earth
terminal) selectingit as directed in Sub-clause3.4. The arrester rating should be at least 0.7
-29-
times the highest phase-to-phasevoltage of the system(0.7 (In), provided the transformer is
fully insulated.
For transformers with graded insulation, refer to Tables C I and C Il for classification
of thesetransformers.Information on protection should be obtained from the manufacturer.
Tnslp C I
Categorieso.fgraded insulatiott
Tenrs C Il
Insulotionlevelsfor the neutralendsof h,indingsof transformers
havinggradedinsulation
Category 1 38
Category 3 | 35 to 65 I of the test voltage of the line end, determined according to the
characteristics of the apparatus and the system
Notes 1. - When choosing the category of neutral insulation, the possibility that the neutral earthing may
be altered at a later stage or that transformers may be interchanged, should be considered.
?. - Obtain the equivalent impulse strength for these power-frequency voltages from the manufacturer.
-31 -
Compare the impulse protective level of the arrester,namely the impulse sparkovervoltage
in this case,with the equipment insulation withstand strength. The impulse protective level
should be not more than 0.833 times the full-wave impulse withstand strength of the insula-
tion at the neutral.
4.1 Protection of series windings of equipment such as booster transfornters, reactors, current trons-
formers, and soforth
Sometimesit is expedientto provide surge protection acrossthe serieswindings of equipment.
Select the arrester having a standard voltage rating which is equal to or greater than the
maximum power-frequency voltage that will appear across the series winding under fault
conditions.
The dry-type insulated equipment covered by this paragraph includes such apparatus as dry-
type transformers and rotating machines which have full-wave impulse withstand insulation
strengths lower than those of liquid-immersed equipments. Generally the impulse withstand
strengthswith waves of short duration are consideredto be the same,or nearly the same,as the
full-wave impulse withstand strength.
4.2.1.1 Apply the procedure of Clause 3 including selectionof the arresteras directed in Sub-
c laus e3 .4 .
4.2.1.2 Compare the front-of-wave impulse sparkover protective level of the arrester with the
full-wave impulse withstand insulation strength of the transformer, or the impulse withstand
strength for any shorter durations for which higher values are given by the manufacturer.
The minimum protective ratio between insulation withstand strength and protective level
r ec o mme n d e di n 3 .6 .1i s 1 .2 .
Note. - No tests for the impulse insulation strength of dry-type transformers have been standardized by I E C.
4.2.2.1 For machines connected to overhead lines either directly or through a short length of
cable:
a) install, at the machine terminals between line and earth, both capacitors to slope off
the wave-front to approximately 10 microseconds or more and arresters to provide
additional protection. Also connect arresterson the overheadlines ahead of the machine
location or at an overheadline-cablejunction point;
-33-
c) compare the full-wave impulse insulation strengthof the insulation or the value as recom-
mended by the manufacturer, with the impulse protective level of the arrester for a
suitable protective ratio. (SeeSub-clause3.6.1.)
4.2.2.2 For machines connected to overhead lines through transformers, in some casesinstal-
lations may not require protection, or the capacitorscan be omitted at the machineterminals.
In some cases,for instance,with star (Y)-delta (D) transformers, better protection can be
obtained by a second set of arrestersconnected between phases.It is suggestedthat the
literature on this subject can be consulted or an investigation can be made with recurrent-
surge oscillograph.
When arrestersare installed at the machine terminals, follow the procedure in Sub-clause
4.2.2.1.
Note.- Theimpulseinsulationstrengthof rotatingmachines hasnot beenstandardized andno standardiza-
tion is contemplated
in theimmediate problemreferto the
future.For treatmentof theco-ordination
manufacturer of themachine. It is usualto takethepeakvalueof thea.c.testvoltageastheimpulse
insulationstrengthof therotatingmachine, of moreprecise
in theabsence information.
a) energizationof line or unit-connected line and transformer (no initial charge on the line);
f) clearing, following loss of load with regulation and over-speedingof alternating current
machines;
g) closingwhen out of phase;
h) linear resonant effectsinvolving an interaction of linear inductive and capacitive compo-
nents of the system as a consequenceof energizationor de-energizationof the part of the
s y s te m;
i) ferro-resonantnon-linear oscillations,causedby energizationor de-energizationinteraction
between system capacitanceand non-linear magnetizingimpedanceof transformers which
may result from single phase switching, open conductors, neutral instability, or over-
excitationof certain 3-phasecircuit configurations.
T he s es u rg e sa re c o v e re db y S u b - cl auses
5.1.1b),5.1.2 b) and 5.1.2d).
When the arrestersparks over with this type of switching surge,the charge on the line, cable
or capacitor bank dischargesthrough the arresterimpedance.If the arresteris connectedon the
line side of the circuit-breaker,the arrester is subjectedto the full dischargecurrent from the
line. This is a relativelylow-current long-durationdischarge.For long lines the magnitude of
dischargecurrent is dependenton the charge on the line and the surge impedance of the line
and the arrester.The duration is dependenton the length of the line.
T h e s es u r g e sa r e c o v e r e db y S u b - c l a u s e5s. 1 . a ) , 5 . 1 . 2a ) , 5 . 1 . 2c ) , 5 . 1 . 2e ) , 5 . L 2 . f ) a n d
5.1.2g).They can be affectedby the length of the line or the amount of capacitanceinvolved.
When the arrester sparks over with this type of surge,the dischargecurrent and/or duration
causesonly mediurnduty on the arresters.This can overstress the lower surgecapacityarresters.
When the arrestersparks over with this type of surge,experienceindicatesthat the discharge
currents are limited and handled without difficulty by lightning arrestersapplied as directed
in this guide.
-37 -
6. New definitions
The highest peak value of impulse voltage that may occur across the terminals of an arrester
under the prescribedconditions.
The impulse protective level is given numerically by the maximum of the following quantities:
- Front-of-waveimpulse sparkovervoltage,divided by l.l5t;
- 1.2150sparkovervoltage 2)
- Residual (discharge)voltage at a given dischargecurrent.
The impulse protective level with the residualvoltage referred to the nominal dischargecurrent.
6.3 Protectiveratio
The ratio of the insulation withstand characteristicsof the protected equipment to the arrester
protective level, expressedas a multiple of the latter figure.
*4,
il
-39-
' {
{
o O
\ 7 t 7
1 2 3 4 5 6
XolXt
a) Yoltage conditions neglecting positive and c/ Voltageconditionsfor Rr : Rz : 0.2 Xt
negative-sequence resistance Rr : Rz : 0