You are on page 1of 8

engineers newsletter providing insights for today’s hvac

system designer

managing the ins and outs of…


Commercial Building Pressurization
from the editor… the pressure inside is greater than the
Providing energy-efficient thermal Why Pressure Matters pressure outside.
comfort without adversely affecting in Commercial Buildings
indoor air quality or violating codes Untreated outdoor air leaks into— During the summer, exfiltration of cool,
poses a considerable design challenge. infiltrates—the building when indoor dehumidified indoor air benefits the
Yet something as subtle as air pressure is less than the pressure building by keeping the envelope dry.
movement through the building outside. Control strategies typically But excessively positive pressure
envelope can determine whether an strive to limit or eliminate infiltration as makes opening and closing doors
otherwise well-designed HVAC system a means of minimizing HVAC loads and difficult and creates noisy high-velocity
performs effectively. related operating costs. Infiltration isn’t airflow around doors and windows. It
always bad, however. During the can also wreak havoc with temperature
This EN reviews the importance of heating season, for example, a small control by impeding supply airflow into
controlling building pressure. It amount of dry outdoor air leaking into occupied spaces.
identifies the effects of indoor–outdoor the building envelope discourages
air pressures on building performance, moisture from condensing there. During the winter, even slightly positive
and then evaluates two common pressure forces moist indoor air into
methods for directly controlling But excessively negative pressure the building envelope. Moisture may
pressure in commercial buildings. causes problems. Uncomfortable
drafts and stratification interfere with
temperature control and may Ducted or Plenum Return?
encourage odor migration. Outward- Ducting return air from a building’s occupied
swinging doors become difficult to spaces back to the air handler increases the initial
open, and inward-swinging doors fail cost of the system, so why do it? Is it to meet
to reclose, compromising security. local codes? Sometimes. Is it to facilitate return-
path cleaning? Maybe. Is it to avoid moisture
problems in the ceiling plenum? Probably not. To
Any amount of infiltration during the understand why, consider the following
cooling season can raise the dew point example…
within the building envelope, which
increases the likelihood of microbial Suppose that the pressure in the return air plenum
must be approximately 0.03 in. wg less than the
growth and structural deterioration.
pressure in the occupied space to overcome the
Infiltration of warm, moist air also return-grille pressure drop. If building pressure is
affects occupied spaces by increasing controlled to 0.05 in. wg, then the plenum
latent loads. pressure will be +0.02 in. wg with respect to
outdoors. This slight difference between the
indoor and outdoor pressures will induce very
Conditioned indoor air leaks out of—
little infiltration. ■
exfiltrates from—the building when

© 2002 American Standard Inc. All rights reserved Volume 31, No. 2 ■
condense on cold surfaces inside walls,
hastening structural deterioration. Semantics of Building Pressure Control
True or False: “Relief” and “exhaust” intake airflow and maintain proper building
Ideally, the net pressure inside the are interchangeable descriptors for air pressure.
building relative to outside should range removed from a building.
from slightly negative or neutral during Intake airflow describes the rate at which the
Although it’s true that both relief air and air handler brings air into the building. Local
cold weather (minimizing exfiltration) to
exhaust air leave the building, their purposes codes or industry standards require a
slightly positive during warm weather
(and definitions) differ. minimum amount of intake airflow for proper
(minimizing infiltration). Excessive ventilation and to dilute and remove general
building pressure, whether negative or Exhaust airflow—which may be central or contaminants. Additional outdoor air
positive, should be avoided. local, constant or variable—carries is brought into the building during economizer
contaminants from the building. Local codes operation to provide “free” cooling.
or industry standards define how much
exhaust air must be removed from specific In the absence of infiltration and exfiltration,
types of spaces (rest rooms, for example), negative building pressure results when
Forces that regardless of pressure-related concerns or exhaust-plus-relief airflow exceeds intake
Affect Pressure operating mode. airflow. Conversely, positive building pressure
Preventing extreme building pressures results when exhaust-plus-relief airflow is less
Relief airflow removes air from the building than intake airflow. ■
is much easier said than done. In most
(again, either centrally or locally) to balance
structures, the indoor–outdoor
pressure difference results directly
from the combined effect of weather,
wind, and operation of the mechanical
ventilation system. barometric pressure, temperature, and When indoor air is warmer than outdoor
humidity ratio. air, the less dense column of air inside
Weather. Like a column of water in a the building results in a net negative
pipe, the weight of a column of air Temperature-related differences in pressure below the neutral pressure
results in a “head” pressure that indoor and outdoor air density create level (NPL) and a corresponding net
increases from the top of the column to differences in pressure that can affect positive pressure above it. Because all
the bottom. Described as hydrostatic infiltration, exfiltration, and the direction building envelopes contain unavoidable
pressure, but more commonly known of air movement within shafts and cracks and openings, this pressure
as “stack pressure,” the weight of the stairwells (Figure 1). difference induces outdoor air to enter
air column is affected by local the lower floors and indoor air to leave
the upper floors. These leakage
characteristics also encourage upward
airflow—normal stack effect—within
Figure 1. Stack effect and building pressure shafts and stairwells.

When indoor air is cooler than outdoor


air, the column of air inside the building
is more dense. The result is a net
negative pressure at the top of the
building and a corresponding net
positive pressure at the bottom. Unless
building pressure is controlled, outdoor
air will infiltrate the upper floors while
indoor air exfiltrates from the lower
levels. The pressure difference also
induces downward airflow in stairwells
and shafts—reverse stack effect.

■ 2 Trane Engineers Newsletter — Vol. 31, No. 2


The 2001 ASHRAE Handbook– throughout the building envelope, the Because it’s impossible to control
Fundamentals provides an equation to neutral pressure level exists at the weather, stack-effect pressure
quantify the stack-effect pressure mid-height (HNPL = 25 ft). differences are best addressed using
difference:1 vertical compartmentalization to
On a hot day (To = 95°F = 555°R, reduce the height of the indoor air
⎛ T o – T i⎞ ρo = 0.0715 lbm /ft³), the difference in column. (See “What’s the Right
Δp s = C 1 ⋅ ρ o ⋅ ⎜ -----------------⎟ ⋅ g ⋅ ( H NPL – H )
⎝ Ti ⎠ indoor–outdoor air densities produces Setpoint for Building Pressure?,” p. 6.)
a +0.013 in. wg pressure difference at Vestibule-type entries and revolving
where,
the ground floor. Without building doors (which can accommodate a
Δps = difference between indoor and outdoor
pressure control, conditioned indoor air high pressure difference without
stack pressures, in. wg
exfiltrates from the lower floors compromising door operation) will
C1 = conversion factor,
0.00598 in. wg · ft · sec²/lb m (H = 0 ft), keeping that part of the minimize stack-induced air currents at
ρo = outdoor air density at outdoor air envelope dry. A less desirable condition entrances, elevators, and stairwells.
temperature, lb m /ft³ exists at the top floor (H = 50 ft), To reduce air currents at the building
g = gravitational constant, 32.2 ft/sec² however, where the –0.013 in. wg envelope, use a well-designed, well-
H = height above reference plane, ft pressure difference encourages entry constructed air barrier.
HNPL = height of neutral-pressure plane above of hot (possibly humid) outdoor air.
reference plane, ft Note: A building actually consists of
Ti = indoor air temperature, °R On a cold day (To = 0°F = 460°R, many interconnected “containers”
To = outdoor air temperature, °R ρo = 0.0863 lbm /ft³), the density of with differing pressures. Unless strict
the indoor air column produces net contaminant control is necessary
The following example illustrates the pressures of –0.058 in. wg at the (hospitals, clean rooms), however, most
magnitude of stack effect in a four- ground floor and +0.058 in. wg at the building-pressure control schemes treat
story, air-conditioned building (H = 50 ft, top floor. This time, lack of building the building as one “equi-pressure
Ti = 75°F = 535°R). Assuming that cracks pressure control permits warm, moist container” to regulate envelope airflow
and openings are evenly distributed indoor air to exfiltrate from the upper and permit proper door operation.
floors of the building, while cold air
infiltrates the lower floors. The Wind. Wind pressure “pushes”
substantial pressure difference outdoor air into the windward side of
1 American Society of Heating, Refrigerating, created by wintertime stack effect the building and “pulls” indoor air from
and Air-Conditioning Engineers, Inc., 2001,
ASHRAE Handbook: Fundamentals (Atlanta, GA: may make it difficult to open outward- the leeward side (Figure 2). The
ASHRAE), 26.5–Equation 17. swinging doors at building entrances. differential pressure exerted on building

Siting Pressure Sensors Figure 2. Wind and building pressure


Regardless of whether the relief system uses a locations that can be influenced by wind-induced
return fan or a relief fan, direct control of pressure fluctuations.
building pressure requires a differential pressure
sensor to monitor the indoor–outdoor pressure
Outdoor sensor. Again, placement of outdoor
difference.
sensors typically follows one of two common
practices. Many designers place the outdoor
Indoor sensor. Two schools of thought exist pressure sensor on the roof-mounted air handler.
regarding placement of the indoor sensor. Some Others use multiple sensors (one at each corner
designers place it near the door, where over-/ of the building, at least 15 ft above the roof) and
under-pressurization effects are most noticeable; average their signals to cancel the effect of wind
others isolate the indoor sensor from the door to pressure. In any case, select sensors that will
dampen the effect of rapid pressure changes minimize wind effect.
caused by door operation.
For applications in which the building is tall and
In either location, the indoor pressure sensor compartmentalized for pressure, position an
should include sufficient signal filtering to outdoor pressure sensor at the elevation of each
minimize the effects of high-speed pressure compartment. ■
changes. It is also important to avoid perimeter

“providing insights for today’s HVAC system designer” 3 ■


surfaces as a result of wind velocity is effective wind speed (UH ) is 25 mph between intake airflow and relief
calculated as:2 and that the wind-surface-pressure airflow determines whether the net
coefficient (Cp ) is 0.50 at the ground building pressure is positive or
2
2 ( UH ) floor (0 ft), then the windward pressure negative. (See “Semantics of Building
Δp w = C 2 ⋅ s ⋅ C p ⋅ ρ o ⋅ ---------------
2 difference will be 0.023 in. wg on a hot Pressure Control,” p. 2.) Excess intake
day and 0.028 in. wg on a cold day. airflow pressurizes the building by
where,
creating a net positive pressure
Δpw = wind surface pressure relative to
At the top floor (50 ft), where the wind- (Figure 3); excess relief airflow
outdoor static pressure in undisturbed
flow, in. wg surface-pressure coefficient may reach depressurizes the building by creating
Cp = wind-surface-pressure coefficient, 0.80, the windward pressure difference a net negative pressure.
dimensionless (0.5 to 0.8 for this rises to 0.037 in. wg on a hot day and
example) 0.044 in. wg on a cold day. Depending on the system type, control
C2 = conversion factor, strategy, and operating schedule, intake
0.0129 in. wg · ft³/lb m · mph² Arguably, the best way for designers and relief airflows may vary during
ρo = outdoor air density at outdoor air to mitigate the effect of wind is by normal system operation. As examples,
temperature, lb m /ft³
maintaining a very negative building the relief fan may operate intermittently
s = shelter factor (0.40 for this example)
pressure during the winter (deterring on demand, and intake (outdoor) airflow
UH = effective wind speed, mph
leeward exfiltration) and a very positive will modulate with airside economizer
building pressure during the summer operation.
Like stack effect, wind pressure (deterring windward infiltration).
varies with outdoor air density and However, successful implementation
building height; wind pressure also also requires the use of a vestibule to
varies with the shelter provided by the prevent interference with door Controlling
immediate landscape, including nearby operation, and an effective air barrier in Building Pressure
trees and buildings. To illustrate the the building envelope to prevent large
Depending on the season and the
magnitude of wind-effect pressure, let’s indoor–outdoor pressure differences
height of the structure, the preferred
revisit our example building at the hot from creating undesirable airflows.
building pressure may be positive or
and cold weather conditions described negative. Meanwhile, the actual
previously. If we assume that the Mechanical ventilation system.
building pressure can be positive or
Some fans force air into the building;
negative due to the combined forces of
others force it out. The balance
2
wind, weather, and operation of the
Ibid., 26.5–6.
mechanical ventilation system. (See
“What’s the Right Setpoint for Building
Pressure?,” p. 6.)
Figure 3. Effect of fan operation on building pressure
Establishing the preferred building
pressure in the face of continuously
changing conditions usually requires an
automated control scheme. For VAV
applications with airside economizers,
designers typically modulate relief
airflow to directly or indirectly maintain
building pressure within an acceptable
range. 3

3 Noteworthy articles include “Comparing


Economizer Relief Systems” by Steven Taylor,
PE, (2000) ASHRAE Journal 42 no. 9: 33–42; and
“The Impact of Airtightness on System Design”
by Wagdy A.Y. Anis, AIA (2001) ASHRAE Journal
43 no. 12: 31–35.

■ 4 Trane Engineers Newsletter — Vol. 31, No. 2


Return fan with direct control.
Alternatives for Return-Fan Control Figure 4 illustrates a typical VAV system
ASHRAE Guideline 16P recommends using because of the disparity between the with a return fan and direct control of
the pressure in the return air plenum as the fan curves. building pressure:
basis for controlling a return-fan relief system.
(See “Return fan with direct control,” pp. 5– Flow tracking indirectly controls building 1 A flow sensor (in this case, a flow-
6.) This simple, direct approach is pressure by monitoring both supply and return measuring damper) monitors intake
inexpensive to implement; it’s also more airflows. The capacity of the return fan
airflow to maintain the proper volume
reliable than the following commonly used “tracks” supply airflow to maintain a fixed
control schemes: signal tracking and flow differential between the two. of outdoor air for ventilation.
tracking.
Flow tracking works best in applications with The pressure in the mixed-air plenum
Signal tracking monitors supply-duct constant local exhaust. Successful changes as the actuator modulates the
pressure to regulate the speeds of the supply implementation also requires expensive, well- linked intake and recirculating dampers.
and return fans. Building pressure is calibrated flow sensors because the difference
controlled indirectly (and ineffectively) between supply and return airflows can be a
Note: An intake airflow sensor controls
very small fraction of the sensed airflow. ■
ventilation more accurately than supply/
return airflow tracking. Monitoring
intake airflow also costs less and is
Note: Intake airflow is usually pushes air out of the damper and usually more reliable than using an
modulated to control ventilation and prevents overpressurization. injection fan, pressure sensor, and
economizer cooling. variable frequency drive.
Relief dampers are often inexpensive to
For controls to maintain either positive install; however, susceptibility to wind 2 A pressure sensor monitors
or negative building pressure by and stack effect often limits their use to supply-duct static pressure and adjusts
modulating relief air, the minimum small HVAC systems and single-story supply-fan capacity accordingly.
intake airflow must exceed maximum buildings.
exhaust airflow; relief airflow can then Note: For DDC/VAV systems, ASHRAE
be used to “trim” the difference Depending on the configuration of the Standard 90.1 requires duct-static-
between airflow into and out of the air distribution system, schemes for pressure reset based on VAV-box
building. active building pressure control position to minimize supply-duct static
involve either a return fan or a relief fan. pressure and, therefore, supply-fan
Minimum relief airflow yields positive Table 1 (p. 8) compares the pros and horsepower.
building pressure, while maximum cons of these two approaches.
relief airflow yields negative building
pressure. For systems with airside-
economizer operation, minimum relief
Figure 4. Typical VAV system with central return fan
airflow may be zero, while maximum
relief airflow may approach maximum
intake airflow.

Building pressure can be regulated


passively or actively. Passive building
pressure control most commonly
consists of a gravity-operated damper
in the occupied space. When the
economizer operates, the positive
pressure that develops inside the space

“providing insights for today’s HVAC system designer” 5 ■


3 The thermostat in each occupied 5 A pressure sensor in the return air the return fan. This strategy modulates
space detects the dry-bulb temperature plenum adjusts the capacity of the the plenum-pressure setpoint, and
and appropriately modulates the supply return fan. (See “Alternatives for therefore return-fan speed, based on
airflow. Return-Fan Control,” p. 5.) the positions of the relief and
recirculating dampers.
4 Local exhaust fans (in rest rooms, for The return fan, which operates
example) remove some of the air from whenever the supply fan does, pulls 6 A differential pressure sensor
the occupied spaces. return air from the occupied space and monitors the indoor–outdoor pressure
pressurizes the return air plenum at the difference. Its signal modulates the
The remaining air either exfiltrates, if air handler. Air from this plenum either position of the relief damper, directly
the spaces are pressurized; or, it passes through the recirculating controlling building pressure.
returns to the air handler, accompanied damper into the mixed air plenum or
by “infiltrated” air, via a return duct or exits the building through the relief The outdoor intake and recirculating
ceiling plenum. damper. dampers can share the same actuator.
However, the relief damper must be
An energy-efficient enhancement to controlled separately to accommodate
return-air-plenum control, optimized varying building-pressure setpoints.
damper control, keeps one damper
nearly wide open to ease the burden on

What’s the Right Setpoint for Building Pressure?


The answer depends on a number of factors: minimize or eliminate infiltration at the top building of only four stories. To cope with
Where is the sensor? What is the building’s floor by pressurizing the building as much as winter stack effect, tall buildings typically
geographic location? Is it sheltered? What’s possible without interfering with proper door include vestibules with revolving doors. This
the climate like? operation. arrangement effectively separates the indoor
air column from outdoor air, enabling proper
Conventional practice is to situate the indoor A similar tactic is employed for winter door operation despite the large indoor–
pressure sensor on the ground floor. A control operation to discourage exfiltration of moist outdoor pressure difference.
scheme is then devised to maintain a slightly indoor air near the top of the building
positive building pressure (0.00 in. wg to envelope. But this time, the target pressure is “Compartmentalizing” tall buildings—that is,
+0.05 in. wg or more) during summer neutral or slightly negative (0.00 in. wg to – vertically dividing the building into separate
operation. In hot humid climates, a setpoint 0.02 in. wg or less). In cold climates, where air distribution systems—can help minimize
greater than +0.10 in. wg may be appropriate, winter stack effect exerts considerable force, the effect of stack pressure differences by
especially for tall buildings and multistory further depressurization is often necessary… reducing the height of the indoor air column.
pressure compartments. The objective is to perhaps –0.10 in. wg on a windy day for a (Elevators usually require a separate vertical
compartment.)

Compartmentalization and winter stack effect Without compartmentalization, minimizing air


leakage through the entire building envelope
due to stack effect would require a very
positive setpoint during the summer and a
very negative setpoint during the winter.

Ultimately, the extent to which a building can


be pressurized depends on its construction
(whether it is “tight,” “leaky,” or something
in-between) and its operation. A well-sealed
building must include controls to avoid
developing excessive pressure, while even
marginal pressurization may be unachievable
in a “leaky” building. ■

■ 6 Trane Engineers Newsletter — Vol. 31, No. 2


Relief fan with direct control. Figure 5. Typical VAV system with central relief fan
Figure 5 illustrates another typical VAV
relief fan and
system, but in this case, a relief fan relief/exhaust damper
directly controls building pressure: RELIEF
RA
1 The flow sensor (a flow-measuring return air local
plenum exhaust fan
damper, as in the previous example) EA
monitors intake airflow to maintain
occupied

RRA
proper ventilation. space
infiltration exfiltration

2 Supply-fan capacity is based on


recirculating variable-speed
the signal of a pressure sensor that damper supply fan VAV box
monitors supply-duct pressure.
SA
INTAKE MA
3 Airflow from each VAV box is
flow-measuring mixed air
modulated based on the dry-bulb intake (OA) damper plenum filters coils
temperature detected by the
thermostat in each occupied space.

4 Local exhaust fans and exfiltration Capacity control can be accomplished configuration is preferred. Use a return
remove a percentage of air from by “riding the fan curve” as the relief fan if the ducted return adds more
occupied spaces; the rest (including damper modulates or by equipping the pressure drop than a reasonably sized
“infiltrated” air) returns to the air relief fan with speed control. supply fan can handle.
handler, usually by way of a ceiling-
plenum return. Air from the return air plenum either
passes into the mixed air plenum
5 The relief fan only operates when through the recirculating damper, or Closing Thoughts
necessary to relieve excess building exits the building through the Building pressure control is important
pressure. With minimum intake airflow, relief damper. for two reasons:
relief airflow is seldom necessary
during mechanical cooling and heating Why pick one relief method versus ■ It is fundamental to attaining the
operation. Note, too, that without a another? Choosing a relief system design targets for infiltration and
return fan it is unnecessary to monitor based on the unique requirements of exfiltration.
and control the static pressure in the each application lets you optimize the
return air plenum. costs of installing and operating it. ■ It enables proper door operation by
preventing excessively positive or
Although the relief fan (when running) Generally, the relief-fan configuration negative pressure.
relieves the burden on the supply fan, works best in VAV systems designed
the latter still must be sized to handle with a ceiling-plenum return. Relief fans Both factors affect the performance
the pressure drop of the entire system effectively control building pressure; and longevity of the building and its
at design airflow. For this reason, the they are also easier to control, less systems. Direct control of building
relief-fan configuration is typically expensive to install, and less costly to pressure, whether with a return fan or a
applied in ceiling-plenum-return operate than return-fan configurations. relief fan, best manages the combined
systems. effects of weather, wind, and
When a ducted return is necessary (see mechanical ventilation.
6 As in the return-fan example, a “Ducted or Plenum Return?” p. 1), be
differential pressure sensor monitors sure to evaluate both relief- and return- Return fan control works. Although
and directly controls building pressure fan configurations: If the supply fan can it requires at least one additional
by adjusting the relief fan’s capacity. handle the pressure drop from the air- pressure sensor (which can be difficult
handler’s discharge opening to its to situate) and continuous operation of
return opening, then the relief-fan the return fan, it also permits a smaller

“providing insights for today’s HVAC system designer” 7 ■


supply fan. Use this type of relief if the
air distribution system includes
return ducts.

Relief fan control works, too. And it’s


often less costly to install and operate Table 1. Pros and cons of return fan vs. relief fan in VAV systems
than a central return fan. The fan Return fan Relief fan
horsepower necessary to overcome Advantages Advantages
the pressure drops of the relief damper ■ Lower differential pressure across the ■ Lower operating cost. Typically, the relief fan
and return path is about the same as for supply fan if the pressure drop of the return air can remain off during “non-economizer” hours
path is greater than the pressure drop of the and operate at low airflow during many
return-fan relief. But unlike the return outdoor air path. “economizer” hours. Also, the recirculating
fan, the relief fan only operates when damper can be sized for a lower pressure drop.
needed (usually during the economizer ■ Potentially lower initial cost for systems ■ Greater layout flexibility. The relief fan can be
mode). with ducted returns. Less supply fan pressure positioned anywhere in the return path (lower
can mean lower fan horsepower and/or a initial cost) because the supply fan draws the
smaller fan and smaller variable-speed drive. return path negative (relative to the occupied
Use relief fan control when the spaces) during modulated economizer operation.
supply fan can overcome the combined A ground-floor air handler with top-floor relief can
take advantage of winter stack effect to lower
pressure drop of the supply and return operating cost.
paths—usually in systems with ceiling
■ Simpler control scheme. One less sensor and
plenum return or with very short one less actuator simplifies installation and
return ducts—or when the system can balancing. Applications with a low return-path
pressure drop can accommodate lower-cost fans
benefit from locating the relief fan as well as fewer (less costly) controls.
remotely from the air handler. ■
Disadvantages Disadvantages
■ Higher operating costs, especially in climates ■ Negative building pressure at low loads. This
with extended hours of economizer cooling condition can occur when a variable-speed drive
By Dennis Stanke, applications
(The return fan must run whenever the supply controls relief-fan capacity, the supply airflow rate
engineer, and Brenda Bradley, fan operates.) is low, and required relief airflow is less than the
information designer, Trane. minimum airflow at lowest fan speed. (Using a
constant-speed relief fan with a modulated relief
damper avoids this disadvantage.)
You can find this and other issues
■ More complex (expensive) fan-speed ■ Greater likelihood of outdoor air leakage at
of the Engineers Newsletter in the control. Return-air-plenum pressure control the relief damper. The return air plenum
commercial section of www.trane.com. requires an additional pressure sensor and operates at negative pressure whenever the
modulating device (either a damper actuator or relief fan is off. (Using low-leak relief dampers
To comment, send a note to Trane, variable-speed drive). can minimize air leakage from outdoors.)
Engineers Newsletter Editor,
■ Difficult to situate the return-air-plenum ■ Higher differential pressure across the
3600 Pammel Creek Road, La Crosse, pressure sensor (in systems with return-air- supply fan than in return-fan systems. When the
WI 56401-7599, or e-mail us at plenum pressure control) because the return air relief fan is off, the supply fan must overcome
plenum is usually small and turbulent. the pressure drops of the return path as well as
comfort@trane.com.
the supply path. (For this reason, relief fans may
■ Requires more fan horsepower at part load. or may not be appropriate for systems with
Return-air-plenum pressure must always be ducted returns.)
positive enough to establish relief airflow; the
recirculating damper must therefore drop
significant pressure between the negative
mixed air plenum and positive return air
plenum. (Optimized damper control can reduce
part-load fan horsepower.)

■ Limited layout flexibility. The return fan must


be situated between the air handler and the
closest leg of the return path (usually near the air
handler) because it must draw the entire return
path negative relative to the occupied spaces. It
must also discharge into the return air plenum
during modulated economizer operation.
An American Standard Company
www.trane.com

For more information, contact your Trane believes the facts and suggestions presented here to be accurate. However,
local district office or e-mail us at final design and application decisions are your responsibility. Trane disclaims any
comfort@trane.com
responsibility for actions taken on the material presented.

■ 8 ADM-APN003-EN

You might also like