Steven T. Taylor
A S H R A E J O U R N A L a s h r a e . o r g O CT O B E R 2 0 1 3
water pumps align with the chillers but are offset to provide tubepull space and piping connections
between the pumps. This is a very
compact layout but it still provides
adequate maintenance access for
all equipment.
VSD
14 in. CWS
VSD
Cooling
Tower 1
VSD
Cooling
Tower 2
Cooling
Tower 3
14 in. CWS
10 in.
10 in.
10 in.
14 in. CWS
10 in.
VSD
Chiller 3
VSD
Chiller 2
VSD
Chiller 1
8 in.
Flow Meter
12 in.
12 in.
8 in.
12 in. CHWS
6 in.
Min. Flow
Bypass
8 in.
8 in.
VSD
VSD
VSD
12 in. CHWR
10 in.
10 in.
VSD
10 in.
VSD
VSD
Cooling
Tower 1
Cooling
Tower 3
Cooling
Tower 2
10 in.
10 in.
10 in.
10 in.
10 in.
10 in.
10 in.
10 in.
10 in.
10 in.
VSD
8 in.
8 in.
Chiller 3
VSD
Chiller 2
VSD
Chiller 1
8 in.
Flow Meter
8 in.
8 in.
8 in.
8 in.
8 in.
12 in. CHWS
6 in.
Min. Flow
Bypass
VSD
VSD
VSD
12 in. CHWR
O CT O B E R 2 0 1 3 a s h r a e . o r g A S H R A E J O U R N A L
51
A S H R A E J O U R N A L a s h r a e . o r g O CT O B E R 2 0 1 3
CT
2
Equalizer
Tip 3: Valves
Chilled water plants, within the plant itself, should
have only two kinds of valves for flow isolation and balance: butterfly valves for large piping (typically 3 in.
[nominal 80 mm] and larger) and ball valves for smaller
piping. These are not only the least expensive types of
valves, they also are the easiest to use since they require
only a quarter turn to open and close (unlike globe
and gate valves) and they may be used for balancing
Conclusions
One would think that a chilled water plant that has
x chillers and pumps and provides y tons of cooling
capacity would cost about the same no matter how it is
ultimately designed and configured. But that is not the
case; first costs can vary substantially depending on the
details. Hopefully, these three tips can help designers
minimize central plant first costs.
References
1. Taylor, S. 2002. Primary-only vs. primary-secondary variable flow
systems. ASHRAE Journal (2).
2. Taylor, S., J. Stein. 2002. Balancing variable flow hydronic systems. ASHRAE Journal (10).
3. Taylor, S. 2002. Degrading chilled water plant Delta-t: causes and
mitigation. ASHRAE Transactions 108(1).