Professional Documents
Culture Documents
Dcr-Is 1893 PDF
Dcr-Is 1893 PDF
ESTIMATION
IS 1893-
1893-2002
1893-2002
is different!! Part 4
Part 5
:: Industrial and Stack-like Structures
:: Dams and Embankments
4
5 6
1
Coverage of Part 1 Major Changes
General Provisions Since the code has been revised after a very
Applicable to all structures long time (~18 years), there are many
Provisions on Buildings significant changes.
To address the situation that other parts of the Some of the philosophical changes are discussed
code are not yet released, Note on page 2 of in Foreword of the code.
the code says in the interim period, provisions of
Part 1 will be read along with the relevant
clauses of IS:1893-1984 for structures other
than buildings
This can be problematic.
For instance, what value of R to use for overhead
water tanks?
7 8
1962 and 1966 maps had seven zones (0 to VI) Latur (1993) earthquake (mag. 6.2, about 8000
In 1967, Koyna earthquake (M6.5, about 200 deaths) in zone I!
killed) occurred in zone I of 1966 map Revision of zone map in 2002 edition
In 1970 zone map revised: Zone I has been merged upwards into zone II.
Zones O and VI dropped; only five zones Now only four zones: II, III, IV and V.
No change in map in 1975 and 1984 editions In the peninsular India, some parts of zone I
and zone II are now in zone III.
9 10
Notice the location of Allahabad and Varanasi in Also notice another error in the new zone map
the new zone map. Location of Calcutta has been shown incorrectly
There is an error and the locations of these two in zone IV
cities have been interchanged in the map. Calcutta is in fact in zone III
Varanasi should be in zone III and Allahabad in Annex E of the code correctly lists Kolkata is in
zone II. zone III.
The Annex E of the code gives correct zones for
these two cities
11 12
2
Preface Other Effects
It is clear that the code is meant for normal Read second para, page 3
structures, and Earthquakes can cause damage in a number of
For special structures, site-specific seismic ways. For instance:
design criteria should be evolved by the Vibration of the structure: this induces inertia
specialists. force on the structure
By inertia force, we mean mass times acceleration
Landslide triggered by earthquake
Liquefaction of the founding strata
Fire caused due to earthquake
Flood caused by earthquake
13 14
17 18
3
Zone Criterion Peak Ground Acceleration
Our zone map is based on likely intensity. Maximum acceleration response of a rigid
It does not address the question: how often such system (Zero Period Acceleration) is same as
a shaking may take place. For example, say Peak Ground Acceleration (PGA).
Area A experiences max intensity VIII every 50 years,
Hence, for very low values of period,
Area B experiences max intensity VIII every 300 years
Both will be placed in zone IV, even though area A has acceleration spectrum tends to be equal to PGA.
higher seismicity We should be able to read the value of PGA
Current trend world wide is to from an acceleration spectrum.
Specify the zones in terms of ground
acceleration that has a certain probability of
being exceeded in a given number of years.
19 20
Ordinate at 0.1 to 0.3 sec ~ 2.5 times the PGA Spectral Acceleration (g)
1.20
(EPGA) defined as 0.40 times the spectral 0.0 0.5 1.0 1.5 2.0 2.5
Per iod (sec)
3.0 3.5 4.0 4.5
acceleration in 0.1 to 0.3 sec range (cl. 3.11) •Typical shape of acceleration response spectrum
There are also other definitions of EPGA, but we •Spectral acceleration at zero period (T=0) gives PGA
will not concern ourselves with those. •Value at 0.1-0.3 sec is ~ 2.5 times PGA value
21 22
Maximum Credible Earthquake (MCE): Other terms used in literature which are
Largest reasonably conceivable earthquake somewhat similar to max credible EQ:
that appears possible along a recognized fault Max Possible Earthquake
(or within a tectonic province). Max Expectable Earthquake
It is generally an upper bound of expected Max Probable Earthquake
magnitude.
Max Considered Earthquake
Irrespective of return period of the earthquake
which may range from say 100 years to 10,000
years.
Usually evaluated based on geological
evidence
23 24
4
Max Considered EQ (MCE) Max Considered EQ (MCE) (contd...)
25 26
This is the earthquake motion for which Cl. 3.6 of the code (p. 8)
structure is to be designed considering inherent Earthquake that can reasonably be expected to
conservatism in the design process occur once during the design life of the structure
What is reasonable…not made clear in our code.
UBC1997 and IBC2000:
Also, design life of different structures may be different.
Corresponds to 10% probability of being
exceeded in 50 years (475 year return period)
27 28
29 30
5
Example on Modal Mass Example on Modal Mass (contd…)
31 32
33 34
35 36
6
Centre of Stiffness
Cl. 4.5 defines Centre of Stiffness as The point
through which the resultant of the restoring
Section 4 forces of a system acts.
37 38
39 40
41 42
7
Dual System (contd…) Dual System (contd…)
In the new code several choices are available to Conditions of Cl. 4.9 are not met. Here, two
the designer: possibilities exist (see Footnote 4 in Table 7, p. 23):
Frames are not designed to resist seismic loads. The entire
When conditions of Cl. 4.9 are met: dual system. load is assumed to be carried by the shear walls. In Example
Example 1: Analysis indicates that frames are taking 30% of 2 above, the shear walls will be designed for 100% of total
total seismic load while 70% loads go to shear walls. Frames seismic loads, and the frames will be treated as gravity
and walls will be designed for these forces and the system frames (i.e., it is assumed that frames carry no seismic
will be termed as dual system. loads)
Example 2: Analysis indicates that frames are taking 10% Frames and walls are designed for the forces obtained from
and walls take 90% of the total seismic load. To qualify for analysis, and the frames happen to carry less than 25% of
dual system, design the walls for 90% of total load, but total load. In Example 2 above, the frames will be designed
design the frames to resist 25% of total seismic load for 10% while walls will be designed for 90% of total seismic
loads.
43 44
47 48
8
Soft Story Soft Storey (contd…)
Cl. 4.20 defines Soft Storey There is not much of a difference between soft
storey and extreme soft storey buildings as
Sl. No. 1 in Table 5 (p. 18) defines Soft Storey
defined in the code, and the latter definition is
and Extreme Soft Storey
not warranted.
In Bhuj earthquake of January 2001, numerous Most Indian buildings will be soft storey as per this definition
soft storey buildings collapsed. simply because the ground storey height is usually different
from that in the upper storeys.
Hence, the term Extreme Soft Storey and cl. 7.10 Hence, the definition of soft storey needs a review.
(Buildings with Soft Storey) were added hurriedly We should allow more variation between stiffness of adjacent
after the earthquake. storeys before terming a building as a “soft storey building”
The code does not have enough specifications on
computation of lateral stiffness and this undermines the
definition of soft storey and extreme soft storey.
49 50
Note that the stiffness and strength are two Soft storey refers to stiffness
different things. Weak storey refers to strength
Stiffness: Force needed to cause a unit
Usually, a soft storey may also be a weak
displacement. It is given by slope of the force-
displacement relationship.
storey
Strength: Maximum force that the system can
take
51 52
53 54
9
General Principles and Design Criteria (Section 6)
55 56
Usually, the vertical motion is weaker than the All structures experience a constant vertical
horizontal motion acceleration (downward) equal to gravity (g) at
On average, peak vertical acceleration is one- all times.
half to two-thirds of the peak horizontal Hence, the vertical acceleration during ground
acceleration. shaking can be just added or subtracted to the
Cl. 6.4.5 of 2002 code specifies it as two-thirds gravity (depending on the direction at that
instant).
57 58
Example: A roof accelerating up and down by Main concern is safety for horizontal
0.20g. acceleration.
Implies that it is experiencing acceleration in the Para 2 in cl. 6.1.1 (p. 12) lists certain cases
range 1.20g to 0.80g (in place of 1.0g that it where vertical motion can be important, e.g.,
would experience without earthquake.)
Large span structures
Factor of safety for gravity loads (e.g., dead and Cantilever members
live loads) is usually sufficient to cover the Prestressed horizontal members
earthquake induced vertical acceleration Structures where stability is an issue
59 60
10
Design Lateral Force
Effects other than shaking
• Philosophy of Earthquake-Resistant Design
Ground shaking can affect the safety of – First calculate maximum elastic seismic forces
structure in a number of ways: – Then reduce to account for ductility and overstrength
Shaking induces inertia force Lateral Force
Soil may liquefy
H, ∆
Sliding failure of founding strata may take place Maximum
Fire or flood may be caused as secondary effect Elastic Force
63 64
65 66
11
Redundancy Ductility
Yielding at one location in the structure does not As the structure yields, two things happen:
imply yielding of the structure as a whole. There is more energy dissipation in the structure
Load distribution in redundant structures due to hysteresis
provides additional safety margin. The structure becomes softer and its natural
period increases: implies lower seismic force to
Sometimes, the additional margin due to be resisted by the structure
redundancy is considered within the Higher ductility implies that the structure can
“overstrength” term. withstand stronger shaking without collapse
67 68
Ductility
Response
Non linear
resistant structure can be designed for much Maximum
Load Capacity Fy
Response
Due to
lower force than is implied by a strong shaking. Load at
First
Significant
Yield
Redundancy
First Yield Fs
The combined effect of overstrength, Due to
Overstrength
Design force Fdes Figure: Courtesy
redundancy and ductility is expressed in terms Dr. C V R Murty
69 70
Imply that the earthquake resistant structures As of now, ductile detailing provisions for
should generally be ductile. precast structures and for prestressed concrete
IS:13920-1993 gives ductile detailing structures are not available in Indian codes.
requirements for RC structures. In the past earthquakes, precast structures have
Ductile detailing provisions for some steel shown very poor performance during
framing systems are available in IS:800-2007. earthquakes.
However, it is advisable to refer to international
codes/literature for ductile detailing of steel The connections between different parts have
structures. been problem areas.
Connections in precast structures in high seismic
regions require special attention.
71 72
12
Past Performance Para 4 of Cl. 6.1.3
The performance of flat plate structures also has This is an important clause for moderate seismic
been very poor in the past earthquakes. regions.
For example, in the Northridge (California) The design seismic force provided in the code is
earthquake of 1994. a reduced force considering the overstrength,
Additional punching shear stress due to lateral redundancy, and ductility.
loads are serious concern.
Hence, even when design wind force exceeds
design seismic force, one needs to comply with
the seismic requirements on design, detailing
and construction.
73 74
Soil Structure Interaction (Cl. 6.1.4) Soil Structure Interaction (Cl. 6.1.4) Contd…
If there is no structure, motion of the ground Presence of structure modifies the free field
surface is termed as Free Field Ground Motion motion since the soil and the structure interact.
Hence, foundation of the structure experiences
Normal practice is to apply the free field motion a motion different from the free field ground
to the structure base assuming that the base is motion.
fixed. The difference between the two motions is
This is valid for structures located on rock sites. accounted for by Soil Structure Interaction (SSI)
For soft soil sites, this may not always be a good SSI is not the same as Site Effects
assumption. Site Effect refers to the fact that free field motion
at a site due to a given earthquake depends on
the properties and geological features of the
subsurface soils also.
75 76
77 78
13
Direction of Ground Motion (Cl. 6.1.5) (contd…)
79 80
81 82
83 84
14
Cl.6.2 Assumptions Mexico Earthquake of 1985
Same as in the 1984 edition, except the Note Earthquake occurred 400 km from Mexico City
after Assumption a) Great variation in damages in Mexico City
There have been instances such as the Mexico Some parts had very strong shaking
earthquake of 1985 which have necessitated In some parts of city, motion was hardly felt
this note. Ground motion records from two sites:
UNAM site: Foothill Zone with 3-5m of basaltic
rock underlain by softer strata
SCT site: soft soils of the Lake Zone
85 86
PGA at SCT site about 5 times higher than that at UNAM Extremely soft soils in Lake Zone amplified weak
site long-period waves
Epicentral distance is same at both locations Natural period of soft clay layers happened to
be close to the dominant period of incident
seismic waves
This lead to resonance-like conditions
Buildings between 7 and 18 storeys suffered
extensive damage
Natural period of such buildings close to the
period of seismic waves.
Time (sec)
87 88
89 90
15
Loads and Stresses Cl.6.3 Load Combinations and Increase in
Permissible Stresses
• Loads
– EQ forces not to occur simultaneously with Cl.6.3.1.1 gives load combinations for Plastic
maximum flood, wind or wave loads Design of Steel Structures
Same as in IS:800-1978
– Direction of forces
More load combinations in IS:800-2007
• One horizontal + Vertical
Cl.6.3.1.2 gives load combinations for Limit
• Two horizontal + Vertical
State Design for RC and Prestressed Concrete
Structures
Same as in IS:456-2000 (RC structures) and
IS:1343-1980 (Prestressed structures) with one
difference
91 92
During earthquake, ground moves in all Vertical component is usually smaller than the
directions; the resultant direction changes every horizontal motion
instant. Except in the epicentral region where vertical
Ground motion can resolved in two horizontal motion can be comparable (or even stronger) to
and one vertical direction. the horizontal motion
Structure should be able to withstand ground As discussed earlier, generally, most ordinary
motion in any direction structures do not require analysis for vertical
Two horizontal components of ground motion ground motion.
tend to be comparable
Say, the epicentre is to the north of a site.
Ground motion at site in the north-south and
east-west directions will still be comparable.
95 96
16
Direction of Horizontal Ground Motion in Design
(Cl.6.3.2.1) Cl.6.3.2.1 (contd…)
Consider a building in which horizontal (also If at a given instant, motion is in any direction
termed as lateral) load is resisted by frames or other than X or Y, one can resolve it into X- and
walls oriented in two perpendicular directions, Y-components, and the building will still be safe
say X and Y. if it is designed for X- and Y- motions,
One must consider design ground motion to act separately.
in X-direction, and in Y-direction, separately Minor typo in this clause: “direction at time”
That is, one does not assume that the design should be replaced by “direction at a time”
motion in X is acting simultaneously with the
design motion in the Y-direction
97 98
1.5 (DL+LL)
1.2 (DL+LL+ELx) ELx = Design EQ load in X-direction
loads acting separately will be unconservative
1.2 (DL+LL-ELx) for elements not oriented along X- and Y-
1.2 (DL+LL+ELy) ELy = Design EQ load in Y-direction
1.2 (DL+LL-ELy)
directions.
1.5 (DL+ELx)
1.5 (DL-ELx)
1.5 (DL+ELy)
1.5 (DL-ELy)
0.9DL +1.5ELx
0.9DL-1.5ELx
0.9DL+1.5ELy
0.9DL-1.5ELy
99 100
Load Combinations…
Combinations… Load Combinations…
Combinations…
x
Elements at 450 orientation designed only for 70%
of lateral force
ELy
101 102
17
Load Combinations…
Combinations…
Non-Orthogonal Systems (Cl.6.3.2.2) (contd…)
– Solution :: Try (100%+30%) together
A lateral load resisting element (frame or wall) is
most critical when loading is in direction of the ELx
element. x
It may be too tedious to apply lateral loads in
each of the directions in which the elements are 0.3ELy
oriented. y
For such cases, the building may be designed 0.3ELx
for:
100% design load in X-direction and 30% design x
load in Y-direction, acting simultaneously
100% design load in Y-direction and 30% design ELy
load in X-direction, acting simultaneously
Note that directions of earthquake forces are reversible. Hence, all
combinations of directions are to be considered.
103 104
Load Combinations…
Combinations…
Non-Orthogonal Systems (Cl.6.3.2.2) (contd…)
– Justification :: Say ELx = ELy = V
Thus, EL now implies eight possibilities: y
+(Elx + 0.3ELy) Vcosθ
+(Elx - 0.3ELy) θ
-(Elx + 0.3ELy) V x
-(Elx - 0.3ELy) V*=Vcosθ + 0.3Vsinθ
+(0.3ELx + Ely)
+(0.3ELx - ELy) 0.3Vsinθ 0.3V
-(0.3ELx + ELy)
-(0.3ELx - ELy) 1.5
ELx+0.3ELy
V* 1 0.3ELx+ELy
0.5
0
0 15 30 45 60 75 90 θ
105 106
107 108
18
Cl.6.3.4.1 Cl.6.3.4.2
In complex structures such as a nuclear reactor In place of 100%+30% rule, one may take for
building, one may have very complex structural design force resultants as per square root of
systems. sum of squares in the two (or, three) directions
Need for considering earthquake motion in all of ground motion
three directions as per 100%+30% rule.
Now, EQ load means the following 24 EL = (ELx)2 + ( ELy)2 + (ELz)2
combinations:
± Elx ± 0.3ELy ± 0.3ELz
± Ely ± 0.3ELx ± 0.3ELz
± Elz ± 0.3ELx ± 0.3ELy
Hence, EL now means 24 combinations
A total of 73 load cases for RC structures!
109 110
111 112
113 114
19
General Principles and Design Criteria (Section 6)
115 116
Response Spectrum versus Design Spectrum Response Spectrum versus Design Spectrum (contd…)
Consider the Acceleration Response Spectrum Natural period of a civil engineering structure
Notice the region of red circle marked: a slight cannot be calculated precisely
change in natural period can lead to large Design specification should not very sensitive to
variation in maximum acceleration a small change in natural period.
Hence, design spectrum is a smooth or average
Spectral Acceleration, g
117 118
119 120
20
Design Spectrum (contd…) Design Spectrum (contd…)
121 122
Design SPECTRUM…
SPECTRUM… Design Lateral Force…
Force…
123 124
21
Importance factor
Soil Effect
• Importance factor I
– Degree of conservatism Recorded earthquake motions show that
– Willing to pay more for assuring essential services response spectrum shape differs for different
– Domino effect of disaster type of soil profile at the site
– Important & community buildings
S.No. Building I
1 Important, Community & Lifeline Buildings 1.5
2 All Others 1.0
• Can use higher value of I Fig. from
Geotechnical
• Buildings not mentioned can be designed for higher value of I Earthquake
depending on economy and strategic considerations Engineering, by
Kramer, 1996
• Temporary (short term) structures exempted from I
Period (sec)
127 128
This variation in ground motion characteristic for Design Spectrum depends on Type I, II, and III
different sites is now accounted for through different soils
shapes of response spectrum for three types of sites.
Type I, II, III soils are indirectly defined in
Table 1 of the code.
Spectral Acceleration Coefficient (Sa /g)
Period(s)
129 130
131 132
22
Response Reduction Factor Response Reduction Factor (contd…)
As discussed earlier, the structure is allowed to be For buildings, Table 7 gives values of R
damaged in case of severe shaking.
For other structures, value of R is to be given in
Hence, structure is designed for seismic force much less
than what is expected under strong shaking if the
the respective parts of code
structure were to remain linear elastic
Earlier code just provided the required design force
It gave no direct indication that the real force may be
much larger
Now, the code provides for realistic force for elastic
structure and then divides that force by (2R)
This gives the designer a more realistic picture of the
design philosophy.
133 134
Response Reduction Factor (R) (contd…) Response Reduction Factor (R) (contd…)
Study Table 7 very carefully including all the footnotes. Note 6 prohibits ordinary RC shear walls in
We have already discussed terms: Dual systems, OMRF,
and SMRF
zones IV and V.
Notes 4 and 8 were covered earlier when we discussed Such a note is not there for OMRF.
Dual systems. This confuses people and they take it to mean
The values of R were decided based on engineering that the code allows Ordinary Moment Resisting
judgment. Frames in zones IV and V.
The effort was that design force on SMRF as per new
provisions should be about the same as that in the old As per IS:13920, all structures in zones III, IV
code.
For other building systems, lower values of R were
and V should comply with ductile detailing (as
specified. per IS:13920). Hence, Ord. RC shear walls
It is hoped that with time, these values will be refined prohibited in zones III also.
based on detailed research.
This needs to be corrected in the code.
135 136
In its place, there could be a general note that For other structures, there are situations where
some of the above systems are not allowed in (I/R) will need to exceed 1.0
high seismic zones as per IS:4326 or IS:13920. For instance, for bearings of important bridges.
137 138
23
Response Reduction Factor …
Design Spectrum for Stiff Structures
– R values can be taken as for Dual Systems,
only if both conditions below are satisfied For very stiff structures (T < 0.1sec), ductility is not
helpful in reducing the design force.
• Shear walls and MRFs are designed to resist VB in
Codes tend to disallow the reduction in force in
proportion to their stiffness considering their
the period range of T < 0.1sec
interaction at all floor levels
Design spectrum assumes peak
• MRFs are designed to independently resist at least extends to T=0
Actual shape of response spectrum
25% of VB (may be used for higher modes only)
Spectral acceleration
Shear Wall MRF
T(seconds)
Concept sometimes used by the codes for
response spectrum in low period range.
139 140
first (fundamental) mode period T ≤ 0.1sec even Cl.6.4.4 allows the design spectrum to be one-
though the code does not specify so. half if the structure is at depth of 30m or below.
For higher modes, this restrictions should not be imposed. Linear interpolation for structures and
foundations if depth is less than 30m.
141 142
143 144
24
Equations for Design Spectrum Site Specific Design Criteria Cl.6.4.6
Response spectrum shapes in Fig. 2 are for 5% Seismic design codes meant for ordinary projects
damping. For important projects, such as nuclear power plants,
dams and major bridges site-specific seismic design
These shapes are also given in the form of criteria are developed
equations These take into account geology, seismicity, geotechnical
Table 3 gives multiplying factors to obtain conditions and nature of project
design spectrum for other values of damping Site specific criteria are developed by experts and
usually reviewed by independent peers
Note that the multiplication is not to be done for
A good reference to read on this:
zero period acceleration (ZPA) Housner and Jennings, “Seismic Design Criteria”,
Earthquake Engineering Research Institute, USA, 1982.
145 146
Buildings (Section 7)
Sub-sections
Cl. 7.1: Regular and Irregular Configurations
Cl. 7.2: Importance Factor I and Response Reduction
Factor R
Cl. 7.3: Design Imposed Loads for Earthquake Force
Calculation
Cl. 7.4: Seismic Weight
Cl. 7.5: Design Lateral Force
Cl. 7.6: Fundamental Natural Period
Cl. 7.7: Distribution of Design Force
Cl. 7.8: Dynamic Analysis
Sections 7.1 to 7.7 on Buildings Cl. 7.9: Torsion
Cl. 7.10: Buildings with Soft Storey
IS:1893-2002(Part I) Cl. 7.11 Deformations
Cl. 7.12 Miscellaneous
147 148
149 150
25
Importance of Configuration (contd…) Regular versus Irregular Configuration
Quote from NEHRP Commentary: Tables 4 and 5 list out the irregularities in the
The major factors influencing the cost of complying with the building configuration
provisions are:
1. The complexity of the shape and structural framing system for Table 4 and Fig. 3 for Irregularities in Plan
the building. (It is much easier to provide seismic resistance in a Table 5 and Fig. 4 for Irregularities in Elevation
building with a simple shape and framing plan.)
2. The cost of the structural system (plus other items subject to
special seismic design requirements) in relation to the total cost
of the building. (In many buildings, the cost of providing the
structural system may be only 25 percent of the total cost of the
project.)
3. The stage in design at which the provision of seismic resistance
is first considered. (The cost can be inflated greatly if no
attention is given to seismic resistance until after the
configuration of the building, the structural framing plan, and the
materials of construction have already been chosen).
151 152
153 154
26
Design Lateral Force (Cl. 7.5) …
Design Lateral Force (Cl. 7.5) (contd…)
• Seismic Weight of Building W
– Dead load Now, Cl. 7.5.2 makes it clear that one has to
– Part of imposed loads evaluate seismic design force for the entire
building first and then distribute it to different
frames/ walls.
Imposed Uniformly % of Imposed Load
Cl. 7.5.2 does not mean that one has to
Distributed Floor Loads to be considered
necessarily carry out a 3-D analysis.
(kN/m2)
One could still work with 2-D frame systems.
Up to and including 3.0 25
Above 3.0 50
157 158
Fundamental Natural Period (Cl. 7.6) Fundamental Natural Period (Cl. 7.6) (contd…)
159 160
Rationale for new equations for T Observations on Steel Frame Buildings During San Fernando EQ
161 162
27
Observations on RC Frame Buildings During San Fernando EQ Observations on RC Shear Wall Buildings During San Fernando EQ
163 164
Vertical Distribution of Seismic Load (Cl. 7.7.1) Vertical Distribution of Seismic Load (Cl. 7.7.1) (contd…)
Lateral load distribution with building height
depends on Hence, NEHRP provides the following expression for
Natural periods and mode shapes of the building vertical distribution of seismic load
Shape of design spectrum Wi hik
Qi = V B n
In low and medium rise buildings,
Fundamental period dominates the response,
∑W h
j =1
j
k
j
165 166
167 168
28
Horizontal Distribution... (Cl. 7.7.2) (contd…)
169 170
171 172
173 174
29
Flexible Floor Diaphragms Analysis for Flexible Floor Diaphragm Buildings
There are instances where floor is not rigid.
“Not rigid” does not mean it is completely flexible! One can actually model the floor slab in the
Hence, buildings with flexible floors should be carefully computer analysis.
analyzed considering in-plane floor flexibility.
Note 1 of Cl. 7.7.2.2 gives the criterion on when the
Fig. on next slide shows the vertical analogy
floor diaphragm is not to be treated as rigid. method to consider diaphragm flexibility in
lateral load distribution
Definition of Flexible Floor
Diaphragm (Cl. 7.7.2.2)
175 176
177 178
Buildings (Section 7)
Sub-sections
Cl. 7.1: Regular and Irregular Configurations
Cl. 7.2: Importance Factor I and Response Reduction Factor R
Cl. 7.3: Design Imposed Loads for Earthquake Force Calculation
Cl. 7.4: Seismic Weight
Cl. 7.5: Design Lateral Force
Cl. 7.6: Fundamental Natural Period
Cl. 7.7: Distribution of Design Force
Section 7.8: Dynamic Analysis Cl. 7.8: Dynamic Analysis
Cl. 7.9: Torsion
IS:1893-2002(Part I) Cl. 7.10: Buildings with Soft Storey
Cl. 7.11 Deformations
Cl. 7.12 M iscellaneous
This lecture covers sub-section 7.8
179 180
30
About This Lecture Requirement of Dynamic Anal. Cl. 7.8.1
181 182
Expressions for design load calculation (cl. In tall buildings, higher modes can be quite
7.5.3) and load distribution with height based significant.
on assumptions In irregular buildings, mode shapes may be
Fundamental mode dominates the response quite irregular
Mass and stiffness distribution are evenly Hence, for tall and irregular buildings, dynamic
distributed with building height
analysis is recommended.
Thus, giving regular mode shape
Note that industrial buildings may have large
spans, large heights, and considerable
irregularities:
These too will require dynamic analysis.
183 184
Lower Bound on Seismic Force (Cl. 7.8.2) Lower Bound on Seismic Force (Cl. 7.8.2) (contd…)
This clause requires that in case dynamic There are considerable uncertainties in modeling
analysis gives lower design forces, these be a building for dynamic analysis, e.g.,
Stiffness contribution of non-structural elements
scaled up to the level of forces obtained based
Stiffness contribution of masonry infills
on empirical T.
Modulus of elasticity of concrete, masonry and
Implies that empirical T is more reliable than T soil
computed by dynamic analysis Moment of inertia of RC members
Depending on how one models a building, there
can be a large variation in natural period.
Ignoring the stiffness contribution of infill walls
itself can result in a natural period several times
higher
185 186
31
Lower Bound on Seismic Force (Cl. 7.8.2) (contd…) Value of Damping Cl. 7.8.2.1
Empirical expressions for period Damping to be used
Based on observations of actual as-built Steel buildings: 2% of critical
buildings, and hence RC buildings: 5% of critical
Are far more reliable than period from dynamic For masonry buildings? Not specified.
analysis based on questionable assumptions Recommended value is 5%
Even when the results of dynamic analysis are Implies that a steel building will be designed for
scaled up to design force based on empirical T: about 40% higher seismic force than a similar
The load distribution with building height and to RC building.
different elements is based on dynamics.
The code should specify 5% damping for both
steel and RC buildings.
187 188
Value of Damping Cl. 7.8.2.1 (contd…) Value of Damping Cl. 7.8.2.1 (contd…)
Damping value depends on the material and the Choice of damping has implications on seismic
level of vibrations safety.
Higher damping for stronger shaking Hence, damping value and design spectrum
Means that during the same earthquake, level go together.
damping will increase as the level of shaking
increases.
Most codes tend to specify 5% damping for
buildings.
We are performing a simple linear analysis, while
the real behaviour is non-linear. What value of damping to be used in “static
Hence, one fixed value of damping is used in our procedure” of Cl. 7.5?
analysis. Not specified. I recommend 5% be mentioned in
the code.
189 190
191 192
32
Number of Modes Cl. 7.8.4.2 (contd…) Modal Combination Cl. 7.8.4.4
Last sentence reads as: This clause gives CQC method first and then
The effect of higher modes shall be included by simpler method as an alternate.
considering missing mass correction using well CQC is a fairly sophisticated method for modal
established procedures
combination. It is applicable both when the
It should read as: modes are well-separated and when the modes
The effect of modes with natural frequency are closely-spaced.
beyond 33 Hz shall be included by….
Many computer programs have CQC method
built in for modal combination.
193 194
195 196
For first five modes of vibration, natural period/ All natural frequencies differ from each other by
natural frequency and maximum response are more than 10%.
given. Estimate the maximum response for the As per Cl. 3.2, none of the modes are closely-
structure. spaced modes.
As per section a) in Cl. 7.8.4.4, we can use
Mode 1 2 3 4 5 Square Root of Sum of Squares (SRSS) method
Natural 0.95 0.35 0.20 0.14 0.11 to obtain resultant response as
Period
Natural 1.05 2.86 5.00 7.14 9.09 = (1100) 2 + (350) 2 + ( 230) 2 + (150) 2 + (120) 2 = 1193
Frequency
Response 1100 350 230 150 120
Quantity
197 198
33
Example 2 on Modal Combination Example 2 on Modal Combination (contd…)
For first six modes of vibration, natural period/ As per Cl. 3.2, modes 2 and 3 are closed spaced since
natural frequency and maximum response are their natural frequencies are within 10% of the lower
frequency.
given. Estimate the maximum response for the
Similarly, modes 5 and 6 are closely spaced.
structure.
Combined response of modes 2 and 3 as per section b)
Mode 1 2 3 4 5 6 in Cl.7.8.4.4 = 230+190=420
Natural period 0.94 0.78 0.74 0.34 0.26 0.25
Combined response of modes 5 and 6 = 90 + 80 = 170
(sec) Combined response of all the modes as per section a)
Natural frequency 1.06 1.28 1.35 2.94 3.85 4.00
(Hz) = (850) 2 + (420) 2 + (200) 2 + (170) 2 = 984
Response Quantity 850 230 190 200 90 80
199 200
Dynamic Analysis as per Cl. 7.8.4.5 Lumped Mass Model for Cl. 7.8.4.5
The analysis procedure is valid when a building can
be modeled as a lumped mass model with one
degree of freedom per floor (see fig. next slide)
X3(t)
If the building has significant plan irregularity, it
requires three degrees of freedom per floor and the X2(t)
procedure of Cl. 7.8.4.5 is not valid.
X1(t)
201 202
Summary
Dynamic analysis requires considerable skills.
Just because the computer program can
perform dynamic analysis: it is not sufficient.
One needs to develop in-depth understanding of Lecture 3
dynamic analysis.
There are approximate methods (such as
Rayleigh’s method, Dunkerley’s method) that
one should use to evaluate if the computer This lecture covers
results are right.
Sections 7.9 to 7.11
It is not uncommon to confuse between the
units of mass and weight when performing IS:1893-2002(Part I)
dynamic analysis.
Leads to huge errors.
203 204
34
Torsion
Buildings (Section 7)
• Uncertainties
Sub-sections
Cl. 7.1: Regular and Irregular Configurations
– Location of imposed load
Cl. 7.2: Importance Factor I and Response Reduction Factor R – Contributions to structural stiffness
Cl. 7.3: Design Imposed Loads for Earthquake Force Calculation
Cl. 7.4: Seismic Weight • Accidental Eccentricity
Cl. 7.5: Design Lateral Force
– Torsion to be considered in Symmetric Buildings
Cl. 7.6: Fundamental Natural Period
Cl. 7.7: Distribution of Design Force • Design Eccentricity
Cl. 7.8: Dynamic Analysis
1.5 esi + 0.05 bi
207 208
Torsion…
Torsion… First Equation for Design Eccentricity (contd…)
– Two cases of Design Eccentricity bi
esi
CM Calculated locations of
CM* CS CM CM* CS CR CM
CM and CR
ith floor
0.05bi 0.05bi *
esi CR CM CM
0.5esi Location CM* to be used
esi
in analysis for first eqn. of
1.5esi+0.05 bi
cl. 7.9.2
1.5esi + 0.05bi esi − 0.05bi
Considering EQ in Y-Direction
209 210
35
Second Equation for Design Eccentricity Second Equation for Design Eccentricity (contd…)
bi
In second equation, it is expected that there is
accidental eccentricity in the opposite sense, esi
i.e., it tends to oppose the computed Calculated locations of
CR CM
eccentricity. CM and CR
ith floor
Hence, factor 1.5 is not applied to the computed
eccentricity.
Again, this equation also should be understood
to mean having + and - sign for second term, *
CM CR CM
whichever is critical: Location CM* to be used
esi in analysis for first eqn. of
0.05 bi
edi = esi ± 0.05bi cl. 7.9.2
Considering EQ in Y-Direction
211 212
Torsion…
Torsion… Torsion…
Torsion…
CS CM CS CM
213 214
Torsion…
Torsion… Torsion…
Torsion…
CS CM CS CM
CM*
0.05bi
215 216
36
Torsion…
Torsion…
Definition of Centre of Rigidity
• Incorporating the provision in practice…
– Solution Earlier we defined Centre of Rigidity as:
If the building undergoes pure translation in the
• Effect of esi only
horizontal direction (that is, no rotation or twist or
A-B torsion about vertical axis), the point through
which the resultant of the restoring forces acts is
• Effect of 0.05bi only the Centre of Rigidity.
C-A This definition was for single-storey building.
How do we extend it to multi-storey buildings?
• Effect of 1.5esi+0.05bi along with shear Recall that I mentioned in Lecture 2 that we will
B+1.5(A-B)+(C-A) not distinguish between the terms Centre of
= 0.5(A-B)+C
Rigidity and Centre of Stiffness.
217 218
219 220
37
Single Floor Definition of CR Choice of Definition
Question is: which definition of CR to choose for
multi-storey buildings?
In fact, some people also use the concept of
Shear Center in place of CR. But, we need not
CR
jth floor does not concern ourselves about it.
rotate
(other floors may Results could be somewhat different depending
rotate) on which definition is used. But, the difference is
not substantial for most buildings.
Use any definition that you find convenient to use.
223 224
225 226
Column Column
shear
shear
Lateral load Lateral load
proportional to proportional to
the mass the mass
distribution distribution
distributed Resultant of column distributed Resultant of column
Central nodes of both ends of
Central nodes of both ends of along the floor shears passes through along the floor shears passes through
the diaphragm are constrained
the diaphragm are constrained length the center of rigidity of length the center of rigidity of
to ensure equal horizontal to ensure equal horizontal
displacement the floor displacement the floor
(a) Lateral loads are applied at all floors of the (b) Free body diagram of a (a) Lateral load is applied at the (b) Free body diagram of a
constrained model particular floor constrained floor particular floor
Fig. Dhiman Basu Fig. Dhiman Basu
227 228
38
Alternative to Locating CR Superposition Method
It is tedious to locate CR’s first and then Apply lateral load profile at the CM’s and analyse
calculate eccentricity. the building; say the solution is F1
One could follow an alternate route using This incorporates the effect of computed
computer analysis, provided one is using All- eccentricity (without dynamic amplification or
accidental ecc.)
Floor Definition.
Apply lateral load profile at CM’s but restrain the
This method is based on superposition
floors from rotating; say this solution is F2
concept and was first published by Goel and
This amounts to solving the problem as if the
Chopra (ASCE, Vol 119, No. 10).
lateral loads were applied at the CRs since the
floors did not rotate.
The difference of F1 and F2 gives the solution
due to torsion caused by computed eccentricity.
229 230
Solution F1 Solution F2
Fig. CVR Murty
231 232
233 234
39
Bldgs with Soft Storeys Cl. 7.10 Buildings with Soft Storeys…
Storeys…
• Inverted
pendulum !!
235 236
OR
Buildings with Soft Storeys Cl. 7.10 (contd…) Buildings with Soft Storeys Cl. 7.10 (contd…)
This clause gives two approaches for treatment There are reservations on the way entire Cl.
of soft storey buildings. 7.10 has been included in the code.
First approach is as per 7.10.2 First approach is too open ended and does not
It is a very sophisticated approach. enable the designer to implement it.
Based on non-linear analysis. Second approach is too empirical and may be
Code has no specifications for applying this impractical in some buildings.
approach.
Also note that Table 5 defines Soft Storey and
Cannot be applied in routine design applications
with current state of the practice in India. Extreme Soft Storey
Second approach as per 7.10.3 is an empirical And yet, nowhere the treatment is different for
provision. these two!
239 240
40
Buildings with Soft Storeys Cl. 7.10 (contd…) Deformations Cl. 7.11
We need considerable amount of research on For a good seismic performance, a building
Indian buildings with soft storey features in needs to have adequate lateral stiffness.
order to develop robust design methodology. Low lateral stiffness leads to:
Large deformations and strains, and hence more
damage in the event of strong shaking
Significant P-∆ effect
Damage to non-structural elements due to large
deformations
Discomfort to the occupants during vibrations.
Large deformations may lead to pounding with
adjacent structures.
241 242
Deformations C.7.11…
C.7.11…
Deformations Cl. 7.11 (contd…)
• Inter-storey Drift
– Storey drift under design lateral load with partial Note that real displacement in a strong shaking
load factor 1.0 will be much larger than the displacement
δ < 0.004hi calculated for design seismic loads
Because design seismic force is a reduced force.
243 244
Note that higher the stiffness, lower the drift but Thus, in computation of drift:
higher the lateral loads. Hence, Stiffness contribution of non-structural elements
For computation of T for seismic design load and non-seismic elements (i.e., elements not
assessment, all sources of stiffness (even if designed to share the seismic loads) should not
unreliable) should be included. be included.
For computation of drift, all sources of flexibility This is because such elements cannot be relied upon to
provide lateral stiffness at large displacements
(even if unreliable) should be incorporated.
All possible sources of flexibility should be
incorporated, e.g., effect of joint rotation,
bending and axial deformations of columns and
shear walls, etc.
245 246
41
Para 2 of Cl. 7.11.1 Para 3 of Cl. 7.11.1
Cl. 7.8.2 required scaling up of seismic design This para allows larger than the specified drift
forces from dynamic analysis, in case these for single-storey building provided it is duly
were lower than those from empirical T. accounted for in the analysis and design.
This para allows drift check to be performed as
per the dynamic analysis which may have given
lower seismic forces, i.e., no scaling-up of forces
needed for drift check.
247 248
Compatibility of Non-Seismic Elements (Cl. 7.11.2) Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…)
Important when not all structural elements are During shaking, gravity columns do not carry
expected to participate in lateral load resistance. much lateral loads, but deform laterally with the
Examples include flat-plate buildings or buildings shear walls due to compatibility imposed by
with pre-fabricated elements where seismic load floor diaphragm
is resisted by shear walls, and columns carry only Moments and shears induced in gravity columns
gravity loads. due to the lateral deformations may cause
During 1994 Northridge (Calif.) earthquake, collapse if adequate provision not made.
many collapses due to failure of gravity ACI Code for RC design has a separate section
columns. on detailing of gravity columns to safeguard
against this kind of collapse.
249 250
Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…) Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…)
P1
Pi ∆ i
F1 Since deflections are calculated using design
Gravity columns Shear Wall P2 seismic force (which is a reduced force), the
h1
F2 deflection is to be multiplied by R.
P3
Floor slab
h2 Multiplier R could be debated since it will only
F3
∆ ∆ ensure safety against Design Basis Earthquake.
P4
h3 For safety against Maximum Considered
F4
Earthquake, multiplier should be (2R).
h4
Imposed
displ. at
Shear Wall
all floors
Floor slab
Gravity
n
column Pi ∆ i + ∑ Fi ∑ h j
j= 1
251 252
42
Separation Between Adjacent …Cl. 7.11.3 Separation Between Adjacent …Cl. 7.11.3 (contd…)
During seismic shaking, two adjacent units of Pounding effect is much more serious if floors of
the same building, or two adjacent buildings one building hit at the mid height of columns in
may hit each other due to lateral displacements the other building.
(pounding or hammering). Hence, when two units have same floor
This clause is meant to safeguard against elevations, the multiplier is reduced from R to
pounding. R/2.
Multiplication with R is as explained earlier:
since deflection is calculated using design
seismic force which are reduced forces.
253 254
255 256
Soft Timber
Structural
Grade Steel
257 258
43
Foundations Cl. 7.12.1 Foundations Cl. 7.12.1 (contd…)
This clause is to prevent use of foundation types Recall newly-introduced Note 7 inside Table 1 of
vulnerable to differential settlement. the code which states:
In zones IV and V, ties to be provided for Isolated R.C.C. footing without tie beams, or
isolated spread footings and for pile caps unreinforced strip foundation shall not be
permitted in soft soils with N<10.
Except when footings directly supported on rock
This note is applicable for all seismic zones.
It would be better to bring this note inside Cl.
7.12.1.
259 260
5Av
261 262
263 264
44
Building Configuration Building Configuration…
Configuration…
• Two types
Irregular Orientation of Lateral
– Plan Irregularities Force Resisting System
– Vertical Irregularities
∆ + ∆2
∆ 2 > 1.2 1
∆1 Floor ∆2 2
265 266
Look at the top two figures of page. 19 (Fig. 3) These figures were taken from NEHRP
Can you make out anything what this figure is Commentary where it appears as follows:
trying to show?
Heavy
Mass
267 268
Building Configuration…
Configuration… Building Configuration…
Configuration…
– Re-entrant Corners – Diaphragm Discontinuity
Flexible
A
L Opening
A A
A
A A Opening
> 0.15 − 0.20
L L
269 270
45
Out-
Out-of-
of-Plane Offsets Building Configuration…
Configuration…
271 272
Building Configuration…
Configuration… Building Configuration…
Configuration…
– Non-Parallel System • Vertical Irregularities
– Stiffness Irregularity (Soft Storey)
ki < 0.7ki +1
ki+1 k +k +k
ki ki < 0.8 i +1 i + 2 i + 3
ki-1
3
273 274
Building Configuration…
Configuration… Mass and Stiffness Irregularity
– Mass Irregularity • It is really the ratio of mass to stiffness of a storey
• induced by the presence of a heavy mass on a that is important.
floor, say a swimming pool.
• Our code should provide a waiver from mass and
stiffness irregularities if the ratio of mass to
stiffness of two adjacent storeys is similar.
Wi > 2 Wi −1
Wi+1
Wi
Wi-1
Wi > 2 Wi +1
275 276
46
Building Configuration…
Configuration… Building Configuration…
Configuration…
– Vertical Geometric Irregularities L1
A
A
> 0.15 − 0.20 L2 > 1.5L1
A A L
L1
L2
L
L
A A
L
L2
277 278
Building Configuration…
Configuration… Building Configuration…
Configuration…
– In-plane Discontinuity in Lateral Load Resisting Elements – Strength Irregularity (Weak Storey)
Lower Floor
Plan
279 280
Building Configuration…
(a) (b)
Arrangement of shear walls and braced frames- recommended.
Note that the heavy lines indicate shear walls and/or braced frames
281 282
47
Diaphragm Discontinuity Diaphragm Discontinuity (contd…)
Fig in NEHRP
Vertical Components of Seismic Resisting System
In buildings with vertical irregularity, load In irregular building, there may be concentration
distribution with building height is different from of ductility demand in a few locations.
that in Cl. 7.7.1. Special care needed in detailing.
Dynamic analysis is required. Just dynamic analysis may not solve the
In buildings with plan irregularity, load problem.
distribution to different vertical elements is
complex.
Floor diaphragm plays an important role and
needs to be modelled carefully.
A good 3-D analysis is needed.
285 286
Code on Irregularity
Our code has simplistic method of treating the
irregularities.
For irregular buildings, it just encourages dynamic
analysis.
Compare Tables of NEHRP shown earlier in this
lecture.
For each type of irregularity and for each seismic
performance category, different requirements
are imposed.
Seismic Force
Dynamic analysis is not always sufficient for
irregular buildings, and
Estimation
Dynamic analysis is not always needed for
irregularities.
287 288
48
Design Seismic Lateral Force
• Two ways of calculating
– Equivalent Static Method
• Seismic Coefficient Method
Single mode dynamics
Simple and regular structures
– Dynamic Analysis Method
• Response Spectrum Method
Multi-mode dynamics
Origin of
Equivalent Static
Irregular structures
• Time History Method
Special structures
Method
289 290
Property
Property Mode
Mode11 Mode
Mode22 Property
Property Mode
Mode11 Mode
Mode22
M1 M2 PSA (g) PSA (g)
PSA PSA1
K1 K2
Natural Frequency ω1 = ω2 = T1 T T2 T
M1 M2
PSA1 PSA2
Natural Period T1 = 2π / ω1 T2 = 2π / ω2 SD
SD1 = SD2 =
291 292 ω12 ω22
Property
Property Mode
Mode11 Mode
Mode22 Property
Property Mode
Mode11 Mode
Mode22
49
Dynamics of 2 DOF System…
System… Dynamics of 2 DOF System…
System…
Property
Property Mode
Mode11 Mode
Mode22
F11 F11
50
Equivalent lateral Force Method
• IS:1893 (Part1) - 2002
VB Example
301 302
3m
5m
3.0m
3m
3.0m
5m
4m
4.0m 3.5m
3m 5.0m
3.5m 3.0m 3.5m 3.5m 3.0m 3.5m
3.5m 5.0m
Plan Elevation
303 304
STEP 2 Step 2…
2…
51
Step 2…
2… Step 3
• Estimate Seismic Weight W… • Estimate Design Horizontal Acceleration
– Total Seismic Weight W Spectrum Value Ah
W = 4900 kN – Clause 6.4 of IS:1893(1)-2002
Maximum
Elastic
DL=1340 kN; LL=0 Acceleration
3m
S
DL=1620 kN; LL=75 kN
Z a (T ) I
Ah (T ) =
3m g
DL=1800 kN; LL=75 kN
4m
2R
Reduction to account
for ductility and
overstrength
3.5m 3.0m 3.5m
307 308
Step 3…
3… Step 3…
3…
– Importance factor I
S.No. Building I
1 Important, Community & Lifeline Buildings 1.5
2 All Others 1.0
309 310
Step 3…
3… Step 3…
3…
52
Step 3…
3… Step 4
• Estimate Ah… • Calculate Design Base Shear Vb
– OMF – Clause 7.5.3 of IS:1893(1)-2002
0.36 × 1.0 × 2.5
2× 3
= 0.15 Infilled Frame VB = Ah (Ta )× W
Ah =
0.36 × 1.0 × 2.08
= 0.125 Bare Frame
2× 3
0.09× 4900= 441kN SMF
VB =
– SMF 0.15× 4900= 735kN OMF
0.36 × 1.0 × 2.5
= 0.090 Infilled Frame
Ah = 2× 5
0.36 × 1.0 × 2.08
= 0.075 Bare Frame
2× 5
313 314
Step 5 Step 5
• Distribute Design Base Shear Vb • Locate point of application of Qi at each floor
along height – At each floor level at design eccentricity
– Clause 7.7.1 of IS:1893(1)-2002 • Clause 7.9.1 of IS:1893(1)-2002
Wi hi2
Qi = VB 1.5esi + 0.05bi , or
N edi =
∑ W j h 2j
EQ
esi − 0.05bi EQ
j =1 b
238.4 kN 397.4 kN
148.9 kN 248.1 kN
53.7 kN 89.5 kN
EQ
EQ
SMF OMF
SMF OMF esi b
315 316
Step 5…
5… Step 5…
5…
CS CM
0.05bi 0.05bi
esi
0.5esi esi
53
Step 5…
5… Step 5…
5…
CS CM CS CM
319 320
Step 5…
5… Step 5…
5…
CS CM
CM* Effect of 1.5esi+0.05bi along with shear
B+1.5(A-B)+(C-A) CS CM CM*
= 0.5(A-B)+C CC
0.05bi
0.05bi
321 322
Step 6 Step 6…
6…
323 324
ELy
54
Step 6…
6… Step 6…
6…
55