You are on page 1of 20

Instruction manual

EK6
Earthing switch
Your safety first – always!

That’s why our instruction manual begins with these recom-


mendations:
WARNING
• Only install switchgear and/or switchboards in enclosed Always follow the instruction manual and
rooms suitable for electrical equipment. respect the rules
• Ensure that installation, operation and maintenance are of good engineering practice !
carried out by specialist electricians only. Hazardous voltage
• Comply in full with the legally recognized standards (IEC), can cause electrical shocks and burns.
the connection conditions of the local electrical utility and the Disconnect power, then earth and short-circuit
applicable safety at work regulations. before proceeding
• Observe the relevant information in the instruction manual with any work on this equipment.
for all actions involving switchgear and switchboards.

• Danger!
Pay special attention to the hazard notes in the instruction If you have any further questions on this instruction manual,
manual marked with this warning symbol. the members of our field organization will be pleased to pro-
• Make sure that under operation condition of the switch- vide the required information.
gear or switchboard
the specified data are not exceeded.
• Keep the instruction manual accessible to all persons con-
cerned with installation, operation and maintenance.
• The user’s personnel are to act responsibly in all mat-
ters affecting safety at work and the correct handling of the
switchgear.

Contents

Page
1 Summary 4
2 Technical Data 4
3 Structure and Funktion 6
4 Installation 8
5 Maintenance 9
6 Dimensional drawings 10

EK6 | Contents 3
1 Summary
Earthing switches of series EK6 are determined for indoor in-
stallation and conform to the requirements of IEC 62271-102.
They are fitted with snap-action operating mechanisms for
positive high-speed closing and sufficiently dimensioned to
conduct the rated short-circuit making current when closed
under load. The speed of the snap-action closing operation is
independent controls.
The earthing switches are supplied as kits with a pre-assem-
bled active part and corresponding earthing contacts supplied
loose. Correct installation of these parts in a switchgear panel
results in a functioning earthing switch.
Routine tests to IEC 62271-102 arc to be carried out at site
accordingly.

2 Technical data
Earthing switch Pole Part number Dimensional Rated short circuit

Rated short-time

circuit duration
Rated impulse
cen- drawing making current

Rated Voltage

Rated short-
test voltage
tres (For various feed
directions)

current
Weight

Typ p Number Sheet U UI Ith tth Ima Ima


mm kg kV kV kA s kA kA
EK6-R-1208 -Z- 150 150 GCE 716 93 12 R11 01 111) GCEM360524 1 12 75 31.5 3 65 80
EK6-R-1208 -P- 150 150 GCE 716 93 12 R21 01 111) GCEM360524 1
EK6 – 1208 – 210 210 GCE 716 93 12 R01 02 121) GCEM360524 1
EK6 – 1208 – 275 275 GCE 716 93 12 R11 03 131) GCEM360524 2
EK6 – 1208 – 150 150 GCE 716 93 12 R01 14 13 GCEM700092 1
EK6 – 1208 – 210 210 GCE 716 93 12 R01 15 14 GCEM700092 1
EK6 – 1208 – 275 275 GCE 716 93 12 R01 16 16 GCEM700092 2
EK6 - 1212 - 210 210 GCE 700 17 32 R01 01 31 GCEM700059 1 40 3 – 120
EK6 - 1212 - 275 275 GCE 700 17 32 R01 02 31 GCEM700059 1 50 1 – 120
2)
EK6 – 1706 – 150 150 GCE 716 93 12 R01 44 13 17.5 95 31.5 3 – 80
2)
EK6 – 1706 – 210 210 GCE 716 93 12 R01 42 14
2)
EK6 – 1706 – 210 210 GCE 716 93 12 R01 45 14
2)
EK6 – 1706 – 275 275 GCE 716 93 12 R01 46 16
2)
EK6-1710–210 210 GCE 700 17 32 R01 06 31 40 3 – 100
2)
EK6-1710–275 275 GCE 700 17 32 R01 05 31
2)
EK6-1710–275 275 GCE 700 17 32 R01 04 31
EK6 – 2406 – 210 210 GCE 716 93 12 R01 05 12 GCEM700092 5 24 125 25 3 50 63
EK6-R-2406-Z-210 210 GCE 716 93 12 R11 04 12 GCEM700092 5
EK6-R-2406-P-210 210 GCE 716 93 12 R21 04 12 GCEM700092 5
EK6 – 2406 – 275 275 GCE 716 93 12 M01 06 14 GCEM700092 6
EK6 – 2406 – 210 210 GCE 716 93 12 R01 17 14 GCEM700092 5
EK6 – 2406 – 275 275 GCE 716 93 12 R01 18 16 GCEM700092 6
EK6 – 2406 – 210 210 GCE 716 93 12 R01 19 14 GCEM700092 8 25 3 – 63
EK6 – 2406 – 275 275 GCE 716 93 12 R01 21 16 GCEM700092 9

1) without earthing contact


2) Dimensional drawings on request.
The earthing switches are suitable for the normal operating conditions of the
„minus 5 indoor class“.

4 Summary | EK6
Key to order code:
Earthing switch version Type designation
Earthing switch E · · – · – · · – · – ·
With snap action mechanism · K · – · – · · – · – ·
Design code · · 6 – · – · · – · – ·
Mechanism on right · · · – R – · · – · – ·
Rated voltage 12 kV · · · – · – 12 · – · – ·
Rated short circuit making current 80 kA · · · – · – · 08 – · – ·
Predominantly for panel type ZK8 · · · – · – · · – Z – ·
(P types predominantly for panel type ZP)
Pole centres 150 mm · · · – · – · · – · – 150
Complete type designation E K 6 – R – 12 08 – Z – 150

EK6 | Key to order code 5


3 Structure and function
Earthing switches of series EK6 have three pairs of earthing The earthing switch has a snap action closing mechanism
blades which are located on the operating shaft and are freely which functions independently of the rotation of the drive
movable. The pairs of earthing blades are electrically con- shaft. The switching speed and torque achieved in this proc-
nected to each other by a short-circuiting bridge and to earth ess are independent of the actions of the operating mecha-
potential at the bearing brackets by two stranded copper nism.
conductors. Driver levers and toggle springs located between In the opening process, in contrast, the toggle springs have
the bearing brackets are used to transmit the force during no effect on the speed of contact separation.
the switching process. Fixing the active part on a torsionally A ring lever or suitable manual or motorized operating mecha-
rigid switchgear panel wall or crossbeam provides it with the nism with the necessary torque for the type of switch and an
necessary stability. operating angle 90° can be fitted for operation of the switch.
The earthing contacts designed to suit the relevant switch
type are to be bolted to the conductor bars supported on Note:
suitable insulating parts, e.g. pintype insulators or current Always open earthing switches by turning until
transformers, on the opposite side and parallel to each other, the stop is reached.
and the position adjusted until it conforms to that show in the The earthing switches can also be fitted with an auxiliary
dimensional drawings. switch for annunciation purposes.

1 2 3 4 5
Figure 1: Example of the active part
of an earthing switchmounted on a
switchgear panel partition, shown in
the open position.

1 Bearing bracket
2 Toggle spring
3 Short-circuiting bridge
4 Pair of earthing blades
5 Eathing conductor
6 Bevel gear mechanism
(not belonging to the
earthing switch)
7 Actuating shaft
8 Driver lever

6 7 8

6 Structure and Function | EK6


11 8 9 2 7
Figure 2: Example of an earthing
switch mounted in a switchgear
panel, shown in the closed position.

2 Toggle spring
7 Actuating shaft
8 Driver lever
9 Setting ring
10 Earthing contact
10.1 Earthing tongue
11 Current transformer

10 10.1

Figure 3: Live parts of an earthing


switch with a rated short-circuit
making current of 120 kA, mounted
on a sheet steel partition.

EK6 | Structure and Function 7


4 Instalation
When installing earthing switches in switchgear panels, the 6. Irrespective of the routine testing of the relevant switch-
following details must be taken into account if perfect switch- gear panels/switchboard to IEC 62271-200, the earthing
ing functions etc. are to be achieved: switch is to be subjected to routine testing in accordance
• The active part of the earthing switch is supplied in the with IEC 62271-102, on completion of installation.
open position and with pretensioned toggle springs. • Check for unimpeded function of the high-speed
• The earthing switch can be installed in any position. switching system when the switch has been installed
• Do not operate the switch without earthing contacts! without stress or distortion.
• Install the active part and earthing contacts without stress • Check the tightening torque for the M 12 hexagon nut
or distortion and parallel to each other on a torsionally on the short-circuiting bridge, possibly removing a pair
rigid and flat panel wall/crossbeam and conductor bar of earthing blades to provide access. This torque is
respectively. important for correct function!
• Precisely maintain the spatial/dimensional position of the Rated tightening torque:
earthing contacts relative to the active part as shown in – without lubricant: 86 Nm
the dimensional drawing for the relevant switch type. – with oil or grease lubricated: 40 Nm.
• Only use insulated mountings with a cantilever strength • Bolt the copper earthing conductors to the bearing
equivalent to a cast resin pin type insulator to DIN 48136: brackets and connect the other ends to the switch-
– For switches to dimensional diagram GCEM 360524, board earthing bar.
sheets 1 and 2 and GCEM 700092, sheets 1, 2, 5, 6, 8 • Perform at least 20 mechanical opening and closing
and 9: Form B, 12 kV or 24 kV, 7.5 kN operations on the earthing switch after completion of
– For switches to dimensional diagram GCEM 700059, installation.
sheet 1: Form C, 12 kV, 16 kN Auxiliary switches:
• Fit the operating mechanism. • Auxiliary switches on the side wall of the switchgear
• The operating shaft can be moved after the two setting panel:
rings have been released. Observe the tightening torque of – 2 x 5 pole auxiliary switches:
4 Nm for the M6 threaded pins. GCE 8282292R0101
• Adjust the motion sequence of the earthing blades in rela- (contact arrangement as per order)
tion to the earthing contacts as follows: – Signalling of open and closed positions
1. Grease the contact areas. – Operation by rod mechanism (engages with M 12
2. Close the switch with the fixing bolts in the earthing threaded bar)
contacts loosely tightened. • Auxiliary switches on the rear wall of the switchgear
3. Check that the blade pairs are properly located on the panel:
contact tongues of the earthing contacts and adjust if – S1 + S2 (2 NCC + 2 NOC = 2 change-over): GCE
necessary. 7169 272 R0108
4. Tighten the fixing bolts and carry out a test switching – S1 + S2 + S3 (3 NCC + 3 NOC = 3 change-over):
operation. GCE 7169 272 R0107
5. Maximum permissible deviation between the central – Signalling of the closed position only.
position of the earthing blades and the contact tongues
of the earthing contacts:
• ≤ 1 mm for switches to dimensional diagram GCEM
360524, sheets 1 and 2, and GCEM 700092, sheets
1, 2, 5, 6, 8 and 9
• ≤ 0.6 mm for switches to dimensional diagram GCEM
700059, sheet 1.
Measuring Point: Clearance between the earthing
blades and the contact tongues during opening.
Take care when handling the switch!

8 Instalation | EK6
5 Maintenance
Closing of the switch several times under load conditions
(maximum loading two closing operations at 100 % of the
rated short-circuit making current) makes inspection and
possibly mainten ance necessary. The electrical and mecha-
nical functions of the switch must not be adversely affected,
and only slight contact welding is permissible. The pairs of
earthing blades and the earthing contacts should be replaced
if necessary.
Otherwise, it is advisable to carry out inspection and main-
tenance of the earthing switches at appropriate intervals
together with the switchboard, particularly in exceptional
operating conditions and/or under adverse environmental in-
fluences such as pollution and aggressive air:
• Check whether the operating mechanism functions
smoothly and easily.
• Carry out general visual examination for the condition of
mechanical fasteners, dirt, moisture and corrosion.
• Remove any dust deposits on insulating parts with a dry,
non-fraying cloth (do not use cleaning wool).
• Regrease the mechanically movable parts and con-
tacts (applying grease thinly) using Isoflex Topas NB
52 lubricant, ABB part number (ordering reference)
GCE0007249P0100.
• Take into account the details given in section 4 in as far as
these are relevant to the work.

EK6 | Maintenance 9
f p p g

25
6
B-B

265

E: GCE8684219P0101

10 Dimensionals drawing | EK6


15 80 30
90
10

58

*)
65
40

90 ø 11
58 17
c 96 S 35,5
°
3 35,5 0 0
96 ø5 B 22 ° 38
48 H C
A L 9 x 19 15 ø 15
275

25
*)
29
29

5
50

35
3
25
26

40
Dimensionals drawing

40

117

72
75

ø 13
17

R
4

160
225
25

17
17

(195)

25
ø 13

S 10
B 36 87 13 20 25 87 6 12 26
+3
a 255 +- 1,5 10 40 50 250 0 60

A-A
W L E: GCE8384542P0180 E: GCE6186188P0101

19
,7

0
ø 30 - 0,1
°
90

See section 4 for the auxiliary switches fitted Contact blade distance: 8 ± 0,3 mm
Contact thickness: 10 mm
E = Earthing contact, H = Auxiliary switch, L = Rating plate, Caution! Contact force: 734 N
S = Operating/Switching angle, W = Shaft section, C = ON, O = OFF, Observe the notes on installation in section 4. Contact spring force (cup springs): 313 N
Operating angle: 90O
Switching angle: 90O

+
) maximum projection of contact
Part number Type p a c g f Md Md Weight blades: 5 mm
OFF ON kg (rated dimensions: 3 mm)
GCE7169312R0102 EK6-1208-210 210 544 420 247-20 58 210 Nm 110Nm 12
Earthing switch EK6 Dimensional drawing
GCE7169312R2101 EK6-R-1208-P-150 150 424 300 195-20 100 210 Nm 110Nm 11
12 kV-Types GCEM360524, Sheet 1
GCE7169312R1101 EK6-R-1208-Z-150 150 424 300 247-20 48 210 Nm 110Nm 11
f p p g

25

B-B

90 15 80 30

10
58
40

c 96
ø 11
p 115 17
S 35,5
22 °
96 3 0
48 H B C
ø5 L 9 x 19
275

25
29

5
50

35
26

40
75

ø 13

160
225
17
17

(195)

25
S
B 36 87 6 12 26
+3
a 250 0 60

L E: GCE6186188P0101

– See dimensional drawing GCEM 360 524, Contact blade distance: 8 + 0,3 mm
sheet 1, for shaft profile Contact thickness: 10 mm
E = Earthing contact, H = Auxiliary switch, L = Rating plate, – See section 4 for auxiliary switches fitted Contact force: 734 N
S = Operating/Switching angle, C = ON, O = OFF, Contact spring force (cup springs): 313 N
Caution! Operating angle: 90O
Observe the notes on installation in section 4. Switching angle: 90O

Part number Type p a c g f Md Md Weight


OFF ON kg Earthing switch EK6 Dimensional drawing
GCE7169312R0103 EK6-1208-275 275 674 550 195-20 100 210 Nm 110Nm 13 12 kV-Types GCEM360524, Sheet 2

EK6 | Dimensionals drawing 11


f p p g

12 Dimensionals drawing | EK6


B-B
E: GCE7003225P0101 40
90 20
Y
58

S
c 96
ø 13 / 13,5
k
32

96 3 22 0
35,5
ø5 C °
48
H B L 9 x 19
68
170

25
29
95 +- 4

5
50
32

35
20

40
73 +- 4
9

160
225
17
4

(195)

25
15

B 87
S 45 + 2
36
a 262 +- 1,5 262 +- 1,5

– See section 4 for the auxiliary switches fitted Contact blade distance: 8 ± 0,3 mm
– See dimensional drawing GCEM 360 524, sheet 1, Contact thickness: 9 mm
E = Earthing switch, H = Auxiliary switch, L = Rating plate, for shaft profile Contact force: 739 N
Y = View direction for switch position Contact spring force (cup springs): 720 N
S = Operating/Switching angle, C = ON, O = OFF, Caution! Operating angle: 90O
Observe the notes on installation in section 4. Switching angle: 90O

Part number Type p a c g f k Md Md Weight1)


OFF ON kg
GCE7169312R0114 EK6-1208-150 150 424 300 160 75 75 220 Nm 120 Nm 13
GCE7169312R0115 EK6-1208-210 210 544 420 175 50 100 220 Nm 120 Nm 13 Earthing switch EK6 Dimensional drawing
1) including earthing contact (Weight 3 Pieces: 1,8 kg) 12 kV-Types GCEM700092, Sheet 1
f p p g

B-B
E: GCE7003225P0101 40
Y 90 20

58

c 96 S
p 115 ø 13 / 13,5
32

96 3 100 22 0
C 35,5
°
48 H
ø5 B L 9 x 19
68
170

25
29
95 +- 4

5
50
32

35
20

40
73 +- 4

R 9

160
225
17
4

(195)

25
15

B 87
S 45 + 2
36
a 262 +- 1,5 262 +- 1,5

– See section 4 for the auxiliary switches fitted Contact blade distance: 8 ± 0,3 mm
E = Earthing contact, H = Auxiliary switch, L = Rating plate, – See dimensional drawing GCEM 360 524, sheet 1, Contact thickness: 9 mm
Y = View direction for switch position indicator for the shaft profile Contact force: 739 N
S = Operating/Switching angle, C = ON, O = OFF, Contact spring force (cup springs): 720 N
Caution! Operating angle: 90O
Observe the notes on installation in section 4. Switching angle: 90O

Part number Type p a c g f Md Md Weight 1)


OFF ON kg
Earthing switch EK6 Dimensional drawing
GCE7169312R0116 EK6-1208-275 275 674 550 210 50 220 Nm 120 Nm 16 12 kV-Types GCEM700092, Sheet 2
1) including earthing contact (Weight 3 Pieces: 1,8 kg)

EK6 | Dimensionals drawing 13


f p p g

15
0
40 - 0,2

14 Dimensionals drawing | EK6


262 +- 1,5
B - B

Y E: GCE7001716P0101
90 I
96
S
c
p 96 k 0
20

58 35,5 ø 13
96 C °
B
L 9 x 19

36
50
80

50

35

225
90°

160
0

210
R
170

R2

(195)
21
0

25
92

ø 13
20

22 15 38
L B
48 36 94
a 262 +- 1,5

E = Earthing contact, I = Isolator, L = Rating plate, – See dimensional drawing GCEM 360 524, sheet 1, 0
Contact blade distance: 38,5 -0,6 mm
Y = View direction for switch position indicator (ZS1-Type), for shaft profile 0
Contact thickness: 40 -0,2 mm
S = Operating/Switching angle, C = ON, O = OFF, Contact force: 500 N
Caution!
Operating angle: 90O
Observe the notes on installation in sector 4.
Switching angle: 90O

Part number Type p a c g f k Md Md Weight 1)


OFF ON kg
GCE7001732R0102 EK6-1212-275 275 674 550 210 50 100 300 Nm 190 Nm 31
GCE7001732R0101 EK6-1212-210 210 544 420 175 60 100 300 Nm 190 Nm 31
1) including earthing contact Earthing switch EK6 Dimensional drawing
12 kV-Types for ZS-Feeder GCEM700059, Sheet 1
f p p g

B-B
90 20 E: GCE7003225P0101 40
Y 58

S
96 ø 13 / 13,5
c
32

96 0
3 100 22 35,5
ø5 C °
48
H B L 9 x 19
68
170

25
29
95 +- 4

5
50
32

35
32

5
20

40
73 +- 4
9

160
225
R

(195)
23
3

25
15

B S 45 + 2 SE SE
L 36 87
a 321 +- 1,5 321 +- 1,5

E = Earthing contact, H = Auxiliary swithch, L = Rating plate, S = Operating/Switching angle,


SE = Control electrode varies with panel design; X = View direction
for switch position indicator, Y = view direction for switch position indicator,
C = ON, O = OFF, – See dimensional drawing GCEM 360524, Contact blade distance: 8 ± 0,3 mm
sheet 1, for shaft profile Contact thickness: 9 mm
– See section 4 for auxiliary switches Contact force: 353 N
Part number Type p a c g f Md Md Weight 1) fitted. Contact spring force (cup springs): 376 N
OFF ON kg Operating angle: 90O
GCE7169312R0117 EK6-2406-210 210 544 420 175 50 220 Nm 120 Nm 14 Caution! Switching angle: 90O
GCE7169312R0105 EK6-2406-210 210 544 420 47 258 220 Nm 120 Nm 12 Observe the notes on installation
in section 4.
GCE7169312R1104 EK6-R-2406-Z-210 210 544 420 258 47 220 Nm 120 Nm 12
GCE7169312R2104 EK6-R-2406-P-210 210 544 420 190 -20 115 220 Nm 120 Nm 12 Earthing switch EK6 Dimensional drawing
1) including earthing contact (Weight 3 Pieces: 1,8 kg) 24 kV-Types GCEM700092, Sheet 5

EK6 | Dimensionals drawing 15


f p p g

16 Dimensionals drawing | EK6


X

B-B

Y 90 20 E: GCE7003225P0101 40 ø 13 / 13,5
58

c 96 S
p 115
0
32

96 3 100 22 35,5
C °
48 H
ø5 B L 9 x 19
68

25
170

29
95 +- 4

5
50

35
32

32

5
20

40
73 +- 4

160
225
R

(195)
23
3

25
15

B
S 45 + 2 SE SE
L
36 87
a 321 +- 1,5 321 +- 1,5

E = Earthing switch, H = Auxiliary switch, L = Rating plate, S = Operating/Switching angle – See section 4 for auxiliary switches fitted. Contact blade distance: 8 ± 0,3 mm
SE = Control electrode varies with panel design; X = View direction for switch position indicator, Y – See dimensional drawing GCEM 360 524, Contact thickness: 9 mm
= View direction for switch position indicator, sheet 1, for the shaft profile Contact force: 353 N
C = ON, O = OFF, Contact spring force (cup springs): 376 N
Caution! Operating angle: 90O
Observe the notes on installation in Section 4. Switching angle: 90O
Part number Type p a c g f Md Md Weight 1)
OFF ON kg
GCE7169312R0118 EK6-2406-275 275 674 550 210 50 220 Nm 120 Nm 16
GCE7169312M0106 EK6-2406-275 275 674 550 120 -20 55 220 Nm 120 Nm 14 Earthing switch EK6 Dimensional drawing
1) including earthing contact (Weight 3 Pieces: 1,8 kg) 24 kV-Types GCEM700092, Sheet 6
f p p g

90 B-B
Y 58

S
c 96 40
96 0 E
3 100 22 35,5 9
ø5 C °
48
H B L 9 x 19

25
29
20

5
50

35
32
32

40
222

125 +- 4

160
225
120

(195)
23
3

25
32

15

B S SE SE ø 13 / 13,5
L 45 + 2
36 87
a 321 +- 1,5
E GCE7003225P0102

E = Earthing contact, H = Auxiliary switch, L = Rating plate, S = Operating/Switching – See dimensional drawing GCEM 360 524, Contact blade distance: 8 ± 0,3 mm
angle, SE = Control electrode varies with panel design; sheet 1, for shaft profile Contact thickness: 9 mm
Y = View direction for switch position indicator, C = ON, O = OFF, – See section 4 for auxiliary switches fitted. Contact force: 353 N
Contact spring force (cup springs): 376 N
Caution! Operating angle: 90O
Observe the notes on installation in section 4. Switching angle: 90O

Part number Type p a c g f Md Md Weight1)


OFF ON kg
Earthing switch EK6 Dimensional drawing
GCE7169312R0119 EK6 -2406-210 210 544 420 175 50 220 Nm 120 Nm 14
24 kV-Types GCEM700092, Sheet 8

EK6 | Dimensionals drawing 17


1) including earthing contact
f p p g

18 Dimensionals drawing | EK6


Y 90 B-B E: GCE7003225P0102
58

c 96 S
p 115 40
96 3 100 22 0 E
35,5
C ° 9
48 H
ø5 B L 9 x 19
20

25
147 +- 4

29

5
50

35
32

32

40
222

120

125 +- 4

160
225
R

(195)
23
3

25
32

15
B S SE SE ø 13 / 13,5
L
36 87 45 + 2
a 321 +- 1,5

E = Earthing contact, H = Auxiliary plate, L = Rating plate, S = Operating/Switching – See dimensional drawing GCEM 360 524, Contact blade distance: 8 ± 0,3 mm
angle, SE = Control electrode varies with panel design; sheet 1, for shaft profile Contact thickness: 9 mm
Y = View direction for switch position indicator, C = ON, O = OFF – See section 4 for auxiliary switches fitted Contact force: 353 N
Contact spring force (cup springs): 376 N
Caution! Operating angle: 90O
Observe the notes on installation in section 4. Switching angle: 90O

Part number Type p a c g f Md Md Weight1)


OFF ON kg
Earthing switch EK6 Dimensional drawing
GCE7169312R0121 EK6-2406-275 275 674 550 210 50 220 Nm 120 Nm 16 24 kV-Types GCEM700092, Sheet 9

1) including earthing contact


EK6 | Dimensionals drawing 19
1VLM000047 Rev.-, en 2009.04.06
ABB s.r.o. The data and ilustrations in this catalogue are not
binding. We reserve the right to make changes of the
Videnska 117
content, in the course of technical development of the
619 00 Brno, Czech Republic product.
E-mail: info.ejf@cz.abb.com
Tel.: +420 547 152 413
Fax: +420 547 152 190

http://www.abb.com

You might also like