Cables Aislados de Media Tensión

Aluminium Medium Voltage Cables


Cables type Al/XLPE/CWS/PE 19/33kV

Construction

1- Round stranded and compacted aluminum conductors, class 2, with longitudinal blocked

2- Inner semiconducting layer.

3- XLPE insulation.

4- Outer semi-conducting layer (bonded).

5- Longitudinal water blocking (semi-conductive tape of suitable material).

5- Metallic screen (combination of copper wires and copper tape).

6- Longitudinal water blocking (n/conductive tape of suitable material).

9- Outer sheath in PE black color.

Applications
Medium voltage transport and distribution networks, industrial plants, power plants, transformer units, connection between overhead lines and transformers. The cables
can be installed in ducts, galleries, directly buried in the soil or in the open air. The armoured versions are particulary suitable to be directly buried in the soil, when an
extra mechanical protection is needed.

Maximum conductor temperature in normal operation 90 ºC. Maximum conductor temperature in short-circuit 250 ºC (5s maximum).

Standards
BS7870-4.10;

Electrical and dimensional characteristics of Cables


Outer
Diameter Outer Approx. Capacitance Inductance Reactance
Diameter of Insulation Nominal area of the sheath
Code Product Description over diameter weight
conductor Thickness metallic screen nominal
insulation of cable (kg/m)
thickness C L XL
- - mm mm mm mm2 mm mm Al µF/km mH/km Ω/km
C101516 AL/XLPE/CWS/PE BQ 1x70/25-BS 9,7 25,7 2,0 36 1,14 0,16 0,43 0,134
C101517 AL/XLPE/CWS/PE BQ 1x95/25-BS 11,2 27,2 2,1 38 1,27 0,18 0,41 0,128
C101518 AL/XLPE/CWS/PE BQ 1x120/25-BS 12,6 28,6 2,1 39 1,38 0,19 0,39 0,124
C101257 AL/XLPE/CWS/PE BQ 1x150/25-BS 14,0 30,0 2,2 41 1,50 0,21 0,38 0,121
C101519 AL/XLPE/CWS/PE BQ 1x185/25-BS 15,6 31,6 2,2 42 1,67 0,22 0,37 0,117
19/33 kV

C100689 AL/XLPE/CWS/PE BQ 1x240/25-BS 18,0 34,0 2,3 45 1,91 0,25 0,36 0,112
7,1 25,0
C100690 AL/XLPE/CWS/PE BQ 1x300/25-BS 20,3 36,3 2,4 47 2,16 0,27 0,35 0,109
C97205 AL/XLPE/CWS/PE BQ 1x400/25-BS 22,9 38,9 2,5 50 2,50 0,29 0,33 0,105
C101521 AL/XLPE/CWS/PE BQ 1x500/25-BS 26,1 42,1 2,6 54 2,89 0,32 0,32 0,101
C101522 AL/XLPE/CWS/PE BQ 1x630/25-BS 30,0 46,0 2,7 58 3,45 0,36 0,31 0,098
C101523 AL/XLPE/CWS/PE BQ 1x800/25-BS 34,0 50,0 2,8 62 4,11 0,40 0,30 0,095
C101524 AL/XLPE/CWS/PE BQ 1x1000/25-BS 38,1 54,1 3,0 66 4,80 0,44 0,29 0,092
Outer layer
Penultimate layer

Voltage
Short-circuit current-carrying capacity (1s) kA Maximum Resistance Current Rating (A)
Cross drop
sections Air (1) Underground (2) V/A.km
Outer layer
Penultimate layer

Screen
Conductor (250°C) DC at 20°C (W/Km) AC at 90°C (W/Km)
(240°C) (cos j =0,8)
mm2 Al Cu Al Al Al Al Al
70 6,6 0,443 0,568 230 185 0,93
95 8,9 0,320 0,410 280 220 0,70
120 11,3 0,253 0,324 325 250 0,58
150 14,1 0,206 0,264 365 280 0,49
185 17,4 0,164 0,210 425 315 0,41
240 22,6 0,125 0,160 500 365 0,34
3,7
300 28,2 0,100 0,128 575 415 0,29
400 37,6 0,078 0,100 670 470 0,25
500 47,0 0,0605 0,078 740 530 0,21
630 59,2 0,0469 0,060 840 585 0,18
800 75,2 0,0367 0,047 925 670 0,16
1000 94,0 0,0291 0,037 1040 705 0,15
The currents and voltage drops are indicated for a 3 phase installation. Frequency 50 Hz.
(1) - Maximum temperature in open air 30 ºC. (2)- Depth of burial 0,8m; Soil thermal resistivity 1,5K.m/W; Maximum temperature of the ground 20 ºC.
The values ​quoted are indicative only. To indicate characteristic of other compositions, communicate Solidal commercial services.
Documento Técnico - 136-ING-02/SOLIDAL/16 - pág. 1/2
Data: 18/10/2015
Packaging
B
L
k

82 d A

Maximum capacity

Type barrel 12 14 16 18 S 18 20 S 20 22 S 22 25

A (mm) 1250 1400 1600 1800 1800 2000 2000 2240 2240 2500

d (mm) 630 710 900 1000 1120 1000 1250 1000 1400 1500

L (mm) 710 810 980 960 960 960 960 1210 1210 1190

e (mm) 50 60 60 70 70 70 70 80 80 80

B (mm) 830 950 1120 1120 1120 1120 1120 1390 1390 1370

Tara (kg) 130 185 250 340 345 400 415 555 595 715

Cubage (m3) 1,30 1,86 2,87 3,63 3,63 4,48 4,48 6,97 6,97 8,56

Weight (Kgs) 1000 1500 2000 3000 3000 4000 4000 5000 5000 5000

K (mm) 50 80 80 80 80 80 80 100 100 100

Drum barrel diameter (d) 18xD


mm2 D mm m kgs m kgs m kgs m kgs m kgs m kgs m kgs m kgs m kgs m kgs
70 36 - - 500 860 800 1 330 1 000 1 690 900 1 560 1 500 2 430 1 100 1 900 2 500 3 950 1 700 2 900 2 400 3 970
95 38 - - 500 910 700 1 270 900 1 660 800 1 520 1 400 2 450 1 000 1 880 2 300 3 930 1 600 2 940 2 200 3 940
120 39 - - 400 820 700 1 360 900 1 770 700 1 460 1 300 2 470 1 000 2 000 2 100 3 900 1 500 2 980 2 000 3 900
150 41 - - - - 600 1 300 800 1 740 700 1 570 1 200 2 500 900 1 990 2 000 4 070 1 400 3 050 1 900 4 050
185 42 - - - - 600 1 450 700 1 740 600 1 540 1 100 2 600 800 2 010 1 800 4 160 1 300 3 200 1 700 4 120
240 45 - - - - 500 1 370 700 1 910 500 1 460 900 2 420 700 1 980 1 600 4 150 1 100 3 060 1 500 4 080
300 47 - - - - 400 1 280 600 1 890 500 1 640 800 2 470 600 1 960 1 400 4 180 1 000 3 180 1 400 4 340
400 50 - - - - - - 500 1 830 400 1 540 700 2 490 600 2 200 1 300 4 440 900 3 280 1 200 4 300
500 54 - - - - - - 400 1 750 400 1 760 600 2 520 500 2 180 1 100 4 450 800 3 430 1 000 4 260
630 58 - - - - - - - - 300 1 600 - - 400 2 090 - - 600 3 110 900 4 490
800 62 - - - - - - - - 300 1 810 - - 300 1 880 - - 600 3 530 800 4 630
Outer layer
Penultimate layer

Recommendation for the installation of cables

Minimum bending radius single-core (mm) Minimum bending radius three-core (mm) Maximum Pulling force (N)(2)

mm2 mm Permanent During installation Permanent During installation Aluminium

70 36 540 720 1 170 1 560 2 100

95 38 570 760 1 220 1 630 2 850

120 39 590 780 1 270 1 690 3 600

150 41 610 820 1 320 1 760 4 500

185 42 640 850 1 370 1 830 5 550


19/33 kV

240 45 680 900 1 460 1 940 7 200

300 47 710 950 1 540 2 050 9 000

400 50 760 1 010 1 630 2 180 12 000

500 54 810 1 080 1 740 2 320 15 000

630 58 870 1 160 1 880 2 500 18 900

800 62 930 1 240 2 010 2 680 24 000


(2) - Three-core cables multiply the value by 3.

Data: 18/10/2016 Documento Técnico - 136-ING-02/SOLIDAL/16 - pág. 2/2