1.0 GENERAL
2.0 STANDARDS
The shunt capacitor bank and its associated equipment shall conform to the
latest additions of the following standards except to the extent explicitly modified in
the specification.
The Capacitor banks shall be Outdoor type with totally enclosed execution
arrangement suitable for operation in the climatic conditions of KOLKATA and
mounted on hot- dipped G.I Structures with suitable insulators as required complete
with enclosure, to be supplied by the bidder.
The bidder shall furnish details of connections between the capacitor units and
groups together with layout diagram showing the basic arrangement of banks
complete with dimensions.
c) Per phase and individual star group rating shall be built up by series parallel
combination of individual units so as to achieve the desired bank rating. The
individual capacity ratings shall be as per 1S: 2834 / IS: 13925 (Part - 1).
d) Although the tolerance in the output rating of each individual unit shall be as
per IS: 13925 yet it shall be ensured that in a completely assembled bank, the
variation from the nominal rating shall be within the specified tolerance values and
shall not cause nuisance alarm or tripping.
e) The tolerance in the output ratings shall not cause variation in the line currents by
that value specified in IS: 13925. Besides it shall also be ensured that these
asymmetrical currents shall not cause asymmetrical voltage rises, whether for short
periods or during prolonged operation.
f) Individual units shall be designed to meet with the requirements of the permissible
overloads as specified as per IS: 13925. Each unit shall also be provided with
internal discharge devices complying with the requirements of the IS.
g) The bidder shall decide the voltage rating of the NCT by considering the voltage
impressed on the NCT due to:
i) Failure of one or more parallel units in a series group.
ii) Failure of all the parallel units in one series group simultaneously. The
bidders shall furnish the design calculations for the same along with the
bid.
a) Each capacitor unit in the bank shall be self-contained outdoor type having 2
bushings suitably rated for series I parallel connections with other units to form
the capacitors bank of rated capacity at 50 Hz. The bushing shall be of porcelain and
shall be joined to the case preferably by welding.
e) The container of capacitor unit shall be of CRCA steel painted with suitable anti-
rust primer and two finishing coats of poly-urethane paints. The container shall
be made from sheet steel of suitable thickness designed to allow for expansion
and contraction due to all ambient and loading conditions expected during the life of
the unit.
f) The design of the internally fused capacitor units shall be such that it shall
permit up to 40% element failure in series group without passing more than 10%
over voltage on other healthy units.
g) Each capacitors unit shall be mounted in such a way that it can be easily removed
from the racks and replaced without removing other units including dismantling any
portion of the rack.
a) The design of the internal fuse shall be such that the residues from fuse
operation (s) shall not cause deterioration of the impregnating fluid. The fuse
assembly shall be distinct and separate from element packs and so constructed that
operation of fuse under worst conditions does not affect the other healthy
elements.
b) The fuses shall not melt or deteriorate when subjected to inrush currents during
the life of the bank.
c) The design of the fuse shall be such that it shall isolate only the faulty elements and
the operation of the fuse shall not affect the other healthy elements.
It will be necessary to make use of shunt filters, tuned to specific order of harmonic which
are found to be above permissible limits. The reactor design shall be such that the banks
are able to withstand the overload due to harmonics. The series reactor shall be -
d) Designed to have a linear V-I characteristics upto 150% of rated capacitor current.
a) The Metal enclosure along with the mounting racks shall be fabricated with hot dip
galvanized steel sheets sections.
c) The racks shall be complete with rack insulators, foundation bolts or any
other hardware, etc. for assembly into complete bank.
d) The height of the racks of capacitor banks shall be such that for making electrical
connections with other equipment, proper electrical clearances are maintained.
e) The capacitor bank along with its mounting racks and complete with its
outer enclosure shall be suitable for installation on the plinth.
f) The assembly of the banks shall be such that it provides sufficient ventilation for each
unit. Necessary louvers may be provided in the cubicle to ensure proper ventilation.
8.0 TESTS
The equipment offered should be routine and type tested as per relevant Standards.
Following test certificate shall be submitted along with bid:
a) Thermal stability
test
b) Impulse withstand test between terminal and
container. c) Endurance test.
The dimension of the capacitor bank should be as minimum as possible as the space
available at project site is limited. Before submission of offer the bidder may inspect
the site at any working day with prior appointment.
10.0 DEVIATION:
Unless mentioned clearly, the tender shall be deemed to conform to this specification
scrupulously. All deviations from this specification shall be brought out separately
& to be marked as “Deviation Schedule”. Such deviation suggested by the bidder may
or may not be accepted by the Purchaser. But any deviation in the offer, not clearly
brought out in the schedule of deviations, will not be considered during / after
tender evaluation or placement of order.
B CAPACITOR BANK
1. Rated Voltage (kV)
2. Maximum Continuous Over voltage Rating as % of
Rated Voltage (kV)
3. Rated Capacitance
4. Manufacturing Tolerance on Nominal Capacitance
Value
5. Number of unit in parallel per phase per series group
6. Number of series section per phase
D SERIES REACTOR
Type/Make
Voltage rating (kV)
Current Rating (A)
No. of phase
BIL (kV)
Frequency (Hz)
Reactance in ohms/in percentage
Maximum switching surge for each bank with & without
reactor
Short circuit rating (A)
Type of shielding magnetic/non-magnetic
Type of cooling (oil/air)