Low profile
design Attractive new enclosures offer a flat,
extremely low profile appearance that
leaves the ceiling clean and
uncluttered.
360°
coverage With a full 360° of coverage, these
sensors are able to control a wide
range of applications, either
individually, or for large areas, in
zones that overlap.
SmartSet™
technology
Watt Stopper SmartSet technology means no
adjustments are needed at installation.
SmartSet monitors the space to identify usage
patterns. With this information, it automatically
Walk-
adjusts the time delay and sensitivity settings
for both optimal performance and maximum
through mode
energy efficiency.
Low & line voltages Low voltage sensors are well suited in most
applications. The simplicity of low voltage wiring
allows for optimal placement. However, some
applications, because of installer preference, are
better suited to line voltage ceiling mount sensors.
Our new generation of sensors are available in both
line and low voltage models to match each and
every application and installation style.
Diffusers
Both the ultrasonic and dual technology
sensors benefit from the new Ultrasonic
Diffusers. The diffusers are able to evenly
distribute the ultrasound in order to achieve
a more comprehensive coverage of the
controlled area.
One touch
light level
Many occupancy sensors contain a built-in
light level sensor. Our new generation
sensors incorporate this feature PLUS a
unique one-touch set up.
Manual
operation
When the application calls for manual on/off control
in addition to the occupancy based control, the new
generation sensors do the job. They offer the
convenience of a low voltage switch input (on the low
voltage sensor models) so that wiring to a
momentary wall switch is quick and easy.
Occupancy sensor technologies
Passive infrared
ceiling mount sensors
Many Watt Stopper PIR sensors
are enhanced with advanced Passive infrared technology (PIR)
technologies to ensure higher
sensitivity to minor motion PIR technology senses occupancy by detecting the
without the potential for false
difference between heat emitted from the human body in
activations. These include
Detection Signature Analysis motion and the background space.
and Pulse Count Processing.
Relying on a clear line-of-sight view, passive infrared
WPIR
sensors make 100% coverage cut off possible. These
CX series
sensors utilize a unique Fresnel lens which divides the
CI-200 series
coverage area into zones, enhancing detection of small
CI-300 series
movement.
CB-100
WS-200 WN-100-120/277
WA-200, WA-300 WD series
3 800.879.8585 • www.wattstopper.com WI-200, WI-300
Ultrasonic technology
Ultrasonic technology
These sensors utilize our Advanced Signal Processing Circuitry to
automatically adjust the signal detection threshold in
compensation for changing levels of activity and airflow. This
helps eliminate false ON activations common in other ultrasonic
sensors.
W series
WT series
UT-300 series
Dual technology
5 800.879.8585 • www.wattstopper.com
Common building spaces, such as
copy rooms, are ideal for
occupancy based control. With a
passive infrared sensor placed in
the corner of the ceiling or as a
wall switch replacement, users
can save hours of wasted lighting
each day.
In large conference
rooms, occupants may be
still for long periods of time.
Dual technology sensors will
be able to detect the small motion
and keep lights on as long as the
space is occupied.
In warehouses, a passive
infrared sensor mounted to
a ceiling or fixture will
control the lighting
between shelves – so that
lighting in unoccupied areas
will turn off or turn to a lower
level. Users can achieve this
control with fluorescent as well
as HID lighting.
800.879.8585 • www.wattstopper.com 6
WS-200 Automatic Wall Switch
Specifications Applications
• Dual 120/277 voltage • Compatible with all electronic • Small offices
• 30 sec to 30 min time delay ballasts and PL lamp ballasts • Small conference rooms
• Built-in light level sensor 2 to 200 • 2.6” x 1.7” x 2” L x W x D • Break rooms
fc (107 to 1,614 lux) (66.0mm x 44.2mm x 50.8mm) • Utility rooms
• No minimum load requirement • UL and CUL listed, 5 year warranty • Storage closets
15'
(4.6m)
Order Information
CATALOG # VOLTAGE* LOAD REQUIREMENTS COVERAGE*
WS-200 120 VAC; 60 Hz or 0-800 Watt Ballast or up to 900 ft2 (83.6 m2), 180°
277 VAC; 60 Hz 0-1200 Watt Ballast
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond, -G for Grey, -B for Black; Single-gang cover plate
ASP-211 included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate with switch
option, specify color. *Models for 220-240 VAC (WS-230) and 347 VAC (WS-347) are available.
7 800.879.8585 • www.wattstopper.com
WA Automatic Wall Switches
Specifications Applications
• Universal 100-300 VAC; 50/60 Hz • Built-in light level sensor 8 to 180 • Public area offices
operation fc (86 to 1,937 lux) • Small offices
• 1.0mm hard poly IR2 lens • No minimum load requirement • Small conference rooms
• SmartSet (automatic) time delay or • Compatible with all electronic • Storage closets
fixed (5-30 minute) ballasts and PL lamp ballasts
• SmartSet (automatic) or reduced • 2.6” x 1.7” x 1.9” (66.0mm x
sensitivity 43.2mm x 48.3mm)
• Zero Crossing Circuitry • UL and CUL listed, 5 year warranty
10'
The WA-200 can be wired for The WA-300 can be wired for (3.1m)
Order Information
CATALOG # DESCRIPTION VOLTAGE LOAD REQUIREMENTS COVERAGE
WA-200 Automatic wall switch 100/120 VAC; 50/60 Hz or 0-800 Watt Ballast or up to 300 ft2
230/277 VAC; 50/60 Hz 0-1200 Watt Ballast (28 m2)
WA-300 Automatic wall switch, 100/120 VAC; 50/60 Hz or 0-800 Watt Ballast or up to 300 ft2
dual relays 230/277 VAC; 50/60 Hz 0-1200 Watt Ballast (28 m2
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond, -G for Grey, -B for Black; Single-gang
cover plate ASP-211 included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang
cover plate with switch option, specify color.
800.879.8585 • www.wattstopper.com 8
WI Automatic Wall Switches
Choice of auto-ON or manual-ON operation Two relays for control of two separate lighting
loads or circuits (WI-300)
4 level lens for superior desktop detection
DIP switch adjustable sensitivity and time delay
Built-in light level sensor
Specifications Applications
• Dual 120/277 VAC • No minimum load requirement • Offices
• Time delay of 15 sec to 30 min (WI- • Compatible with all electronic • Conference rooms
200); 30 sec to 30 min (WI-300) ballasts and PL lamp ballasts
• Built-in light level sensor 10 to 150 • 2.8” x 4.8” x 1.5” (72.1mm x
fc (107 - 1,614 lux) (on secondary 121.9mm x 38.1mm)
relay of WI-300) • UL and CUL listed, 5 year warranty
• LED indicator
Neutral Neutral
277V Ground (GRN/YEL) 0°
120V Ground (GRN) Load
Hot Black
Hot (BLK) Load (RED)
5° 4-level Fresnel lens
Blue Primary detects horizontal and
Load
12° vertical motion.
Secondary
Maximum coverage
Red Red
Load
40'
30° under ideal conditions
Ground (GRN) (12.2m) and for half-step walking
motion is 1000 ft2.
The WI-200 can be wired for The WI-300 can be wired for 15'
single-level lighting (shown), or bi-level (shown) or dual circuit (4.6m)
Order Information
CATALOG # DESCRIPTION VOLTAGE LOAD REQUIREMENTS COVERAGE
WI-200 Automatic wall switch 120 VAC; 60 Hz or 0-800 Watt Ballast or up to 1000 ft2 (92.9m2) 180°
277 VAC; 60 Hz 0-1200 Watt Ballast
WI-300 Automatic wall switch, 120 VAC; 60 Hz or 0-800 Watt Ballast or up to 1000 ft2 (92.9m2) 180°
dual relays 277 VAC; 60 HZ 0-1200 Watt Ballast
Add -W to cat # for White, -A for Light Almond; Order ASP-121 for blank switch 2-gang box
plate; Order ASP-122 for 2-gang box plate with switch option (WI-200 only)
9 800.879.8585 • www.wattstopper.com
WN Motion Sensor Nightlight Switch
Built in nightlight illuminates whenever Terminal wiring for quick and easy installation
overhead lights are off
Zero Crossing Circuitry increases product
longevity
Specifications Applications
• 120 or 277 VAC, 60 Hz • 2.63” x 1.69” x 1.88” (66.8mm x • Hotel guest bathrooms
• Time delay of 15 min, 30 min, 1 42.9mm x 47.8mm) • Military housing
hour or 2 hours • UL and CUL listed, 5 year warranty • Healthcare facilities
• 1.0mm hard poly IR2 lens
Order Information
CATALOG # VOLTAGE LOAD REQUIREMENTS COVERAGE
WN-100-120 120 VAC; 60 Hz 0-500W incandescent, fluorescent up to 300 ft2 (28 m2), 180°
and compact fluorescent
WN-100-277 277 VAC; 60 Hz 0-1200W incandescent, fluorescent up to 300 ft2 (28 m2), 180°
and compact fluorescent
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang cover plate with switch
option, specify color.
800.879.8585 • www.wattstopper.com 10
WD Dimmable Automatic Switch
Low profile, flat decorator design ASIC enhances reliability and helps to
eliminate false triggers
Zero voltage turn on/off increases life
of sensor
Specifications Applications
• WD-170, WD-270 operate at 120 • 1.0 mm hard poly IR 2 lens • Small offices
VAC; WD-180, WD-280 operate at • LED indicator • Public area offices
277 VAC • Adjustable sensitivity • Small conference rooms
• WD-170/180 time delay of 30 sec to • 2.7”x1.8”x2.2” (68.9mm x 45.7mm x
30 min 55.9mm)
• WD-270/280 fixed initial 15 min • UL and CUL listed, 5 year warranty
delay for dim; secondary adjustable
delay (5 min to 30 min) for off
Neutral
Load
Ground GRN
Hot BLK
Coverage shown is for half-
Load RED
Order Information
CATALOG # VOLTAGE LOAD REQUIREMENTS COVERAGE OFF MODE
WD-170 120 VAC; 60 Hz 10-500 W Ballast up to 300 ft2 (28 m2) Automatic-OFF
WD-180 277 VAC; 60 Hz 10-500 W Ballast up to 300 ft2 (28 m2) Automatic-OFF
WD-270 120 VAC; 60 Hz 10-500 W Ballast up to 300 ft2 (28 m2) Dim-bef-disconnect
WD-280 277 VAC; 60 Hz 10-500 W Ballast up to 300 ft2 (28 m2) Dim-bef-disconnect
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang plate with switch option,
specify color. WD-170/180.wiring.single level
11 800.879.8585 • www.wattstopper.com
CN, CW Vacancy Sensors for
Residential Use
Manual-on/automatic-off operation; lights Adjustable time delay from 1 to 30 minutes
cannot be overriden ON
Impact resistant hard lens
CN contains energy efficient nightlight
that illuminates whenever overhead CEC 2005 Title 24 compliant
lights are off
Specifications Applications
• 120 VAC, 60 Hz • No minimum load requirement CW CN
• Time delay of 1 min to 30 min • 2.63” x 1.69” x 1.88” (66.8mm x • Hallways • Bathroom
• 1.0mm hard poly IR2 lens 42.9mm x 47.8mm) • Laundry rooms • Bedrooms
• Compatible with 0-500W • UL and CUL listed, 5 year warranty • Garages
incandescent, fluorescent, compact
fluorescent, MLV, and ELV loads
optimally detect
Ground Neutral motion, the sensor
Green INDOOR USE ONLY
White must have a clear and
unobstructed view of
10'
(3.1m) occupants.
Order Information
CATALOG # DESCRIPTION VOLTAGE LOAD REQUIREMENTS COVERAGE
CN-100 Residential vacancy 120 VAC; 60 Hz 0-500W incandescent, fluorescent up to 300 ft2 (28 m2), 180°
sensor with nightlight and compact fluorescent
CW-100 Residential vacancy 120 VAC; 60 Hz 0-500W incandescent, fluorescent up to 300 ft2 (28 m2), 180°
sensor and compact fluorescent
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond. Single-gang cover plate ASP-211 included. Order ASP-422 for blank
2-gang cover plate, ASP-432 for 2-gang cover plate with switch option, specify color.
800.879.8585 • www.wattstopper.com 12
WPIR Passive Infrared Sensor
PIR occupancy sensor turns lights on and off ASIC technology reduces components and
based on occupancy provides greater reliability
Specifications Applications
• Adjustable time delay of 30 sec to • 2.5” x 2.5” x 1.14” • Small offices • Computer rooms
30 min (63.5mm x 63.5mm x 29.0mm) • Copy rooms • Racquetball courts
• Units per power pack: up to 8 (B); • UL and CUL listed, 5 year warranty • Break rooms • Library book stacks
up to 10 (BZ)
Adjustment
SE N
TI
M
Black
E
Blue
Red
Zone 1
Switch Zone 2
Sensor
Window Horizontal Zone 3
coverage
Zone 4
Zone 5
5 4 3 2 1
Order Information
CATALOG # VOLTAGE CURRENT COVERAGE
WPIR 24 VDC 14 mA up to 300 ft2 (28 m2)
All units are white and use Watt Stopper power packs
13 800.879.8585 • www.wattstopper.com
CX Pa s s i ve I n f ra re d S e n s o r
Choice of four coverage patterns Swivel mounting bracket for convenient corner
mounting to wall or ceiling
User-adjustable time delay and sensitivity
Built-in light level sensor (CX-100)
ASIC technology reduces components and
provides greater reliability Isolated relay for use with HVAC or other
control systems (CX-100)
Specifications Applications
• Time delay of 15 sec to 30 min • 3.3” x 3.3” x 2.1” (83.8mm x • Large offices • Open office spaces
• Built-in light level sensor 3 to 200 83.8mm x 53.3mm) • Warehouses • Classrooms
fc (32 - 2,152 lux) (CX-100) • UL and CUL listed, 5 year warranty • Computer rooms • High bays
• Units per power pack: CX-100 up to
6 (B), up to 8 (BZ); CX-105 up to 14
(B), up to 18 (BZ)
8ft
White (Neutral) t.
50f 0
16ft
N White Power Pack
Lighting
55ft.
Load 10ft
Hot Black Red (Load) Switch TOP
Wires
Red
33.5ft 33.5ft 0
Hot OFF switch Light Light 15ft 0
10 ft 0 10 ft 20 ft 30 ft 40 ft 50 ft
Level on
Level
Red (load) Lighting
Sensitivity
0
67ft 38ft 21ft 10ft 0 10ft 21ft 38ft 67ft One Sided Aisleway:
Load 1 2 3 4 5
N CX-100-4, CX-105-4
Time Delay DIP
Two Sided Aisleway: CX-100-3, CX-105-3 Narrow Aisle Lens (-4)
using MB-1 bracket
with maximum rotation
Coverages shown areLensmaximum.
Aisleway (-3)
pointed straight down
Under ideal conditions, coverage for half-step walking motion
(standard lens) can reach up to 2000 ft2 (185.8 m2), for desktop activity up to 1000 ft2 (92.9 m2).
Order Information
CATALOG # VOLTAGE CURRENT COVERAGE FEATURES
CX-100 24 VDC 19 mA up to 2000 ft2 (185.8 m2) light level, isolated relay
CX-100-1 24 VDC 19 mA up to 90 linear ft (27.4 m) light level, isolated relay
CX-100-3 24 VDC 19 mA up to 120 linear ft (36.6 m) light level, isolated relay
CX-100-4 24 VDC 19 mA up to 50 linear ft (15.2 m) light level, isolated relay
CX-105 24 VDC 8 mA up to 2000 ft2 (185.8 m2)
CX-105-1 24 VDC 8 mA up to 90 linear ft (27.4 m)
CX-105-3 24 VDC 8 mA up to 120 linear ft (36.6 m)
CX-105-4 24 VDC 8 mA up to 50 linear ft (15.2 m)
All units are white and use Watt Stopper power packs. Order the MB-1 Industrial Mounting Bracket
for installing the CX in industrial settings such as warehouses.
800.879.8585 • www.wattstopper.com 14
CI-200 Passive Infrared Sensor
Specifications Applications
• Time delay 15 sec to 30 min • 3.3” diameter x 2.2” total depth • Open or partitioned
• Built-in light level sensor 4 to 190 (83.8mm x 55.9mm) Extends office spaces
fc (43 to 2,045 lux) (CI-200) approx .36” from ceiling • Conference rooms
• SPDT isolated relay (CI-200) • UL and CUL listed, 5 year warranty • Computer rooms
• Units per power pack: CI-200 up to • Classrooms
5 (B), up to 7 (BZ); CI-205 up to 10
(B), up to 13 (BZ)
Red (Line)
N White Power Pack Lighting DIP Switch 8 ft
Load for Time Delay
Switch and Sensitivity Typical
Hot Black Red (Load) desk-top
level
44 ft
Isolated Relay Outputs Cable
Black
Blue
Red
Order Information
CATALOG # VOLTAGE CURRENT COVERAGE
CI-200 24 VDC 20 mA up to 1200 ft2 (111.5 m2)
CI-200-1 24 VDC 20 mA up to 500 ft2 (46.5 m2)
CI-205 24 VDC 11 mA up to 1200 ft2 (111.5 m2)
CI-205-1 24 VDC 11 mA up to 500 ft2 (46.5 m2)
All units are white and use Watt Stopper power packs.
15 800.879.8585 • www.wattstopper.com
CI-300, CI-355 360° PIR Sensor
Architecturally appealing low profile Accepts low voltage switch input for manual-on
appearance operation (CI-300, CI-305)
SmartSet automatically selects optimal Line and low voltage models available
time delay and sensitivity
Walk-through mode increases
Depluggable terminal wiring for quick and savings potential
easy installation
Specifications Applications
• CI-300, CI-305: 24 VDC/VAC • Isolated relay with N/O and N/C • Units per power pack: CI-300 up • Open offices
• CI-355: 120/230/277/347 VAC, outputs rated for 1 Amp at 30 to 5 (B), up to 7 (BZ); CI-305 up to • Conference rooms
50/60 Hz VDC/VAC (CI-300) 12 (B), up to 16 (BZ) • Classrooms
• Time delays: SmartSet (automatic), • Mounting options: ceiling tile; 4 • 4.5” diameter x 1.02” (144.3mm x • Offices
fixed (5, 10, 15, 20, or 30 minutes), square junction box with double 25.9mm); (83.8mm x 55.9mm)
• Storage rooms
walk-through, test-mode gang mudring (CI-300, CI-305) extends approx .36” from ceiling
• Computer rooms
• Sensitivity adjustment: SmartSet • Mounting options: 4 square • UL and CUL listed, 5 year
(automatic) or reduced sensitivity junction box with double gang warranty
• Built-in light level sensor; 10 to mudring; 4 inch octagonal
300 fc (107 to 3,229 lux) (CI-300, junction box (CI-355)
CI-355)
Red (Line)
N White Power Pack
Lighting Extended Range Lens (Standard)
Hot Black Red (Load) Switch
load
CI-300, CI-305, CI-355
Black
Blue
12 ft 9 ft 7 ft 5 ft 3 ft 0 3 ft 5 ft 7 ft 9 ft 12 ft
CI-355 Wiring
Order Information
CATALOG # VOLTAGE CURRENT/LOAD REQ COVERAGE
CI-300 24 VDC 20 mA up to 1200 ft2 (111.5 m2)
CI-300-1 24 VDC 20 mA up to 500 ft2 (46.5 m2)
CI-305 24 VDC 9 mA up to 1200 ft2 (111.5 m2)
CI-305-1 24 VDC 9 mA up to 500 ft2 (46.5 m2)
CI-355 120 VAC, 50/60 Hz 0-800 W Ballast/Tungsten up to 1200 ft2 (111.5 m2)
230/277 VAC, 50/60 Hz 0-1200 W Ballast
347 VAC, 50/60 Hz 0-1500 W Ballast
CI-355-1 120 VAC, 50/60 Hz 0-800 W Ballast/Tungsten up to 500 ft2 (46.5 m2)
230/277 VAC, 50/60 Hz 0-1200 W Ballast
347 VAC, 50/60 Hz 0-1500 W Ballast
All units are white and low voltage models use Watt Stopper power packs.
For line voltage installations requiring an adapter plate, order cat # CA-1.
800.879.8585 • www.wattstopper.com 16
CI-12,CI-24 Sensor for HVAC, BAS
Ceiling mount 360° sensor Four-level Fresnel lens offers superior desktop
detection
Interfaces directly with EMS or HVAC system
through internal isolated relay Advanced PIR technology
User adjustable time delay and sensitivity via ASIC technology reduces components and
DIP switch enhances reliability
Specifications Applications
• Time delay 30 seconds to 30 • 3.3” diam x 2.2” depth (83.8mm x • Open or partitioned • Computer rooms
minutes 55.9mm) extends approx .36” from office spaces • Classrooms
• Isolated relay rated for 1 Amp at 24 ceiling • Conference rooms
VAC/VDC • UL and CUL listed, 5 year warranty
PIR occupancy sensor for areas of extreme Choice of three coverage patterns
low temperature
Convenient DIP switch adjustments for time
Watertight enclosure prevents moisture and delay and sensitivity
dust from affecting detection
Isolated relay contact for use with HVAC or
other control systems
Specifications Applications
• Time delay 15 sec to 10 min • 3.94”x3.74”x2.36” (100.1mm x • Cold storage and • Unconditioned
• Temperature range -40°F to +95°F 95.0mm x 60.0mm) freezers spaces
• Units per power pack: up to 5 (B); • UL and CUL listed, 5 year warranty
up to 7 (BZ) Wiring Diagram
White / Neutral
Blue
Red
Switch
Units are beige; Dense Wide Angle lens is standard; Add-1 to Cat# for Long
Range, -3 for Two Sided Aisle way
17 800.879.8585 • www.wattstopper.com
W Ultrasonic Occupancy Sensor
Specifications Applications
• Ultrasonic technology with 25KHz • Adjustable sensitivity • Open and partitioned • Storage areas
frequency • Units per power pack: up to 7 (B); spaces • Conference rooms
• Temperature and humidity resistant up to 9 (BZ) • Restrooms • Hallways
receivers • 4.5” x 4.5” x 1.25” (114.3mm x
• Logic key/ON bypass 114.3mm x 31.8mm)
• LED indicator • UL and CUL listed, 5 year warranty
**W-2000H coverage is
Red
10'
Switch
12' not drawn to scale
20'
sensor
Occupancy Sensor
Order Information
CATALOG # VOLTAGE CURRENT COVERAGE
W-500A 24 VDC 16 mA 360°, 500 ft2 (46.5 m2)
W-1000A 24 VDC 16 mA 360°, 1000 ft2 (92.9 m2)
W-2000A 24 VDC 16 mA 360°, 2000 ft2 (185.8 m2)
W-2000H 24 VDC 16 mA 360°, 90 linear ft (27.4 m)
All units are white and use Watt Stopper power packs.
800.879.8585 • www.wattstopper.com 18
WT Ultrasonic Occupancy Sensor
Ultrasonic technology with 32 KHz frequency User-adjustable DIP switch time delay and
sensitivity settings
Utilizes advanced, omni-directional,
Doppler technology 600, 1100, 2200 sq ft and hallway
coverages available
Advanced Signal Processing automatically
Isolated relay allows sensor to interface with
adjusts detection threshold
building control systems
Specifications Applications
• Ultrasonic technology with 32 KHz • Units per power pack: • Open and partitioned spaces
frequency WT-605 up to 4 (B), 5 (BZ); WT-600 • Restrooms
• Time delay 15 sec to 30 min up to 3 (B), 4 (BZ); WT-1105, WT- • Storage areas
• Isolated relay with N/O and N/C 2205, WT-2255 up to 3 (B), 5 (BZ);
• Conference rooms
outputs; rated for 1 amp @ 30 WT-1100, WT-2200, WT-2250 up to
VDC/VAC 2 (B), 3 (BZ) • Hallways
• 4.8” diam x 1.5” depth (121.9mm x • UL and CUL listed, 5 year warranty
38.1mm)
White (Neutral)
45' 26' 22' 0' 22' 26' 45'
Red (Line)
White
21'
N Lighting Transducers WT-2200/2205
Power Pack Load
Black Red (Load) Switch
Hot 14'
WT-1100/1105 WT-600/605
Isolated Relay Outputs Cable
DIP switch
Black
Blue
Red
14'
Common 8 Gra
Coverage shown
21' represents half-step,
walking motion
Order Information
CATALOG # VOLTAGE CURRENT COVERAGE FEATURE
WT-605 24 VDC 27 mA 360° one-sided, 600 ft2 (55.7 m2)
WT-600 24 VDC 37 mA 360° one-sided, 600 ft2 (55.7 m2) isolated relay
WT-1105 24 VDC 30 mA 360° two-sided, 1100 ft2 (102.2 m2)
WT-1100 24 VDC 40 mA 360° two-sided, 1100 ft2 (102.2 m2) isolated relay
WT-2205 24 VDC 30 mA 360° two-sided, 2200 ft2 (204.4 m2)
WT-2200 24 VDC 40 mA 360° two-sided, 2200 ft2 (204.4 m2) isolated relay
WT-2255 24 VDC 30 mA 360° two-sided, 90 linear ft (27.4 m)
WT-2250 24 VDC 40 mA 360° two-sided, 90 linear ft (27.7 m) isolated relay
All units are white and use Watt Stopper power packs.
19 800.879.8585 • www.wattstopper.com
UT-300, UT-355 360° Ultrasonic Sensor
Architecturally appealing low Accepts low voltage switch input for manual-on
profile appearance operation (UT-300, UT-305)
Specifications Applications
• UT-300, UT-305: 24 VDC/VAC • Isolated relay with N/O and N/C mudring; 4 inch octagonal • Restrooms
• UT-355: 120/230/277/347 VAC, outputs rated for 1 Amp at 30 junction box (UT-355) • Large Offices
50/60 Hz VDC/VAC (UT-300) • Units per power pack: UT-300 • Open Offices
• Time delays: SmartSet • Built-in light level sensor; 10 to up to 2 (B), up to 3 (BZ); UT-305
(automatic), fixed (5, 10, 15, 20, 300 fc (107 to 3,229 lux) (UT- up to 3 (B), up to 4 (BZ)
or 30 minutes), walk-through, 300, UT-355) • 4.5” diameter x 1.02” (144.3mm
test-mode • Mounting options: ceiling tile; 4 x 25.9mm) (83.8mm x 55.9mm)
• Sensitivity adjustment: square junction box with double Extends approx .36” from ceiling
SmartSet (automatic) or gang mudring (UT-300, UT-305) • UL and CUL listed, 5 year
reduced sensitivity • Mounting options: 4 square warranty
• Ultrasonic frequency of 40 kHz junction box with double gang
10' UT-300-1
Blue
Red
20'
25'
obstacles.
Order Information
CATALOG # VOLTAGE CURRENT/LOAD REQ COVERAGE
UT-300-X 24 VDC 43 mA see diagram
UT-305-X 24 VDC 37 mA
UT-355-X 120 VAC, 50/60 Hz 0-800 W
230/277 VAC, 50/60 Hz Ballast/Tungsten
347 VAC, 50/60 Hz 0-1200 W Ballast
0-1500 W Ballast
X = 1 for 500 ft2 of coverage; -2 for 1000 ft2; -3 for 2000 ft2.
All units are white and low voltage models use Watt Stopper power packs.
For line voltage installations requiring an adapter plate, order cat # CA-1.
800.879.8585 • www.wattstopper.com 20
DT-200 Dual Technology Sensor
Trouble-free lighting control in applications Accepts low voltage switch input for
difficult for single technology sensors manual-on operation
Specifications Applications
• 24 VDC/VAC • SPDT isolated relay (DT-200) • 4.4" x 3.4" x 2" (111.8mm x • Classrooms
• Ultrasonic frequency of 40 kHz • Isolated relay with N/O and N/C 86.4mm x 50.8mm) • Conference and training
• Time delays: SmartSet outputs rated for 1 Amp at 24 • UL and CUL listed, 5 year rooms
(automatic), fixed (5, 10, 15, 20, VDC/VAC (DT-200) warranty • Large offices
or 30 minutes), walk-through, • Built-in light level sensor; 2 to
test-mode 200 fc (21 to 2,152) lux) (DT-200)
• Sensitivity adjustment: • Units per power pack: DT-200
SmartSet (automatic) or up to 3 (B), up to 4 (BZ); DT-205
reduced sensitivity up to 4 (B), up to 5 (BZ)
Red (Line)
N White Power Pack
Lighting
load
Hot Black Red (Load) Switch
PIR
Blue
Red
0 7 ft 15 ft 25 ft 55ft
All units are white and use Watt Stopper power packs.
21 800.879.8585 • www.wattstopper.com
DT-300 360° Dual Technology Sensors
Architecturally appealing low profile Accepts low voltage switch input for manual-on
appearance operation (DT-300, DT-305)
SmartSet™ automatically selects optimal Depluggable terminal wiring for quick and easy
settings for each space installation
Specifications Applications
• DT-300, DT-305: 24 VDC/VAC • Isolated relay with N/O and N/C mudring; 4 inch octagonal • Classrooms
• DT-355: 120/230/277/347 VAC, outputs rated for 1 Amp at 30 junction box (DT-355) • Open office spaces
50/60 Hz VDC/VAC (DT-300) • Units per power pack: DT-300 • Computer rooms
• Time delays: SmartSet • Built-in light level sensor; 10 to up to 2 (B), up to 3 (BZ); DT-305
(automatic), fixed (5, 10, 15, 20, 300 fc (107 to 3,229 lux) (DT-300, up to 3 (B), up to 4 (BZ)
or 30 minutes), walk-through, DT-355) • 4.5” diameter x 1.02” (144.3mm
test-mode • Mounting options: ceiling tile; 4 x 25.9mm) Extends approx .36”
• Sensitivity adjustment: SmartSet square junction box with double from ceiling
(automatic) or reduced gang mudring (DT-300, DT-305) • UL and CUL listed, 5 year
sensitivity • Mounting options: 4 square warranty
• Ultrasonic frequency of 40 kHz junction box with double gang
Red (Line)
N White Power Pack
Lighting
load
Hot Black Red (Load) Switch
Black
Blue
Red
Order Information
CATALOG # VOLTAGE CURRENT/LOAD REQ COVERAGE
DT-300 24 VDC 43 mA up to 1000 ft2 (92.9 m2)
DT-305 24 VDC 35 mA up to 1000 ft2 (92.9 m2)
DT-355 120 VAC, 50/60 Hz 0-800 W Ballast/Tungsten up to 1000 ft2 (92.9 m2)
230/277 VAC, 50/60 Hz 0-1200 W Ballast up to 1000 ft2 (92.9 m2)
347 VAC, 50/60 Hz 0-1500 W Ballast up to 1000 ft2 (92.9 m2)
All units are white and low voltage models use Watt Stopper power packs.
For line voltage installations requiring an adapter plate, order cat # CA-1.
800.879.8585 • www.wattstopper.com 22
Power Packs
Fully self-continued transformer and relay Two-relay output power pack that accepts signals
from multiple control devices (LC-100)
Many models of power pack products for
wide range of applications Daylighting control with photosensor (LC-100)
Power Packs
B120E-P 120VAC, 60Hz 20 13 1 24VDC; 150mA***
B277E-P 277VAC, 60Hz 20 - - 24VDC; 150mA***
B230E-P 220-240VAC, 50/60Hz 20 13 1 24VDC; 150mA***
B347D-P 347VAC, 60Hz 15 - 24VDC; 150mA***
BZ-100 120/277VAC, 60Hz 20 20 1 24VDC; 150mA†
LC-100 120/277 VAC; 50/60 Hz 20 20 1 24VDC; 150mA†
Auxiliary Packs
S120/277/ 120/277/347VAC 20/20/15 13/-/- 1/-/- -
347E-P
Form C Power Packs
A120C-P** 120VAC, 60Hz 8NO/5NC 5NO/3NC 1NO/2.5NC 24VDC; 100mA
A277C-P** 277VAC, 60Hz 6NO/3NC 5NO/2.5NC 2NO/.5NC 24VDC; 100mA
2 Relay Power Packs
C120E-P 120VAC, 60Hz 20* 13* 1* 24VDC; 150mA
C277E-P 277VAC, 60Hz 20* - - 24VDC; 150mA
Power Supplies
AT-120 120VAC, 60Hz - - - 24VDC; 800mA
AT-277 277VAC, 60Hz - - - 24VDC; 800mA
* Ratings per relay. ** Contain an isolated relay with normally open (NO) and normally closed (NC)
contacts. ***Output is 150mA before relay is connected and 114mA after relay is connected.
†Output is 150mA with relay connected.
23 800.879.8585 • www.wattstopper.com
Outdoor Motion Sensors
Optional model with lampholders Line and low voltage models available
Weatherproof and raintight for reliable 90 degree or long-range field of view (EN)
performance
Security override-ON option allows lights to be
Adjustable light level and time delay turned on for length of time delay
settings
Isolated relay enables interface with security
systems or other loads
EW Specifications EN Specifications
• Operating temperature range: - • Zero Crossing Circuitry • Operating temperature range: - • Manual override-ON allows
40°F to +130°F • 1/2’ threaded nipple fits 40°F to +130°F lights to be turned on for 4
• UL 773A rated raintight; UL 1571 standard NEMA weatherproof • UL 773A rated raintight; UL hours
rated for wet locations fixture fitting 1571 rated for wet locations • 3/4’ threaded nipple fits
• Adjustable time delay of 12 sec • Lamp holders us PAR 20 or 38 • Adjustable time delay of 12 sec standard NEMA weatherproof
to 16 min lamps, up to 150W each lamp fixture fitting
to 16 min
• Light level adjustment of .5 to • EW sensor: 6.7” x 3.2” x 2.2”
• Light level adjustment of .4 to • 4.3” x 3.0” x 2.3” (110mm x
200 fc (5 - 2152 lux) (170mm x 80mm x 55mm)
42 fc (4.3 - 452 lux) 77mm x 58mm)
• Isolated relay with NO/NC • UL and CUL listed, 5 year
outputs; rated for 1 Amp @ 30 warranty • SPDT isolated relay • UL and CUL listed, 5 year
VDC/VAC (EW-200) • Zero Crossing Circuitry warranty
Applications Applications
• Walkways and entranceways • Garages and yards • Walkways and entranceways • Doorways
• Dock lighting • Driveways • Dock lighting • Corridors
EW Order Information
CATALOG # VOLTAGE LOAD REQ/CURRENT * COVERAGE FEATURES
EW-200 - 120, - 277 VAC 0-1000 W ballast 270° Isolated relay
EWF-205 - 120 VAC 0-1000 W ballast 270° Lamp holders
EW-205-24 24 VDC 8 mA 270° Controls outdoor HIDs
EW-105-24 24 VDC 8 mA 180° Controls outdoor HIDs
EN Order Information
CATALOG # VOLTAGE LOAD REQUIREMENT* COVERAGE FEATURES
EN-100 - 120, - 277 VAC 0-1000 W ballast 90° Isolated relay
EN-200 - 120, - 277 VAC 0-1000 W ballast Long range Isolated relay
Specify voltage by adding -120 or -277 to Cat. #. Add -W to Cat. # for Arctic White, -G for
Architectural Grey
*For 120 VAC applications, tungsten loads are also acceptable.
800.879.8585 • www.wattstopper.com 24
IT-200 InteliTimer Logger
Determines energy savings potential from IT-ProSoft Software provides single-step data
occupancy sensor use retrieval, storage, analysis, printing
Adjustable light pipe observes lighting level Logs when a space is occupied/ vacant and
when lighting is on/off
Logs when a space is occupied/ vacant and
when lighting is on/off Small and lightweight for ease of use
and portability
LEDs) 6 Mon, Aug 15, 1995 at12:15:00 PM Lights OFF Vacant OFF+Occupied: 0 hours 0.0%
Order Information
CATALOG # DESCRIPTION
IT-200 Occupancy and light logger, PC connector cable included
25 800.879.8585 • www.wattstopper.com
TS Digital Time Switches
Automatically turns lights off after Terminal style wiring for simplified installation
preset time
Digital operation and simple
Bright electroluminescent LCD shows pushbutton set-up
timer’s countdown
Time scroll features allows time to adjust
Optional audible or visual alerts before
up or down
lights turn off
Specifications Applications
• TS-400: 100-300 AC; 50/60 Hz • Optional visual warning: • TS-400-24 contains SPDT • Equipment rooms
• TS-400-24: 24 VAC/VDC/VAC flashes lights at 5 min and 1 isolated relay rated for 1 Amp • Storage areas
half-wave rectified input min prior to time-out @ 30 VDC • Closets
• Time out adjustments range • Optional audible warning: • 2.66” x 1.79” x 1.76” (67.5mm x
from 5 minutes to 12 hours (5 beeps every 5 sec at 1 min 45.5mm x 44.7mm)
minute increments to 1 hour, prior to time-out • UL and CUL listed, 5 year
then 15 minute increments to • Compatible with all electronic warranty
12 hours) ballasts and motor loads
Lighting
Neutral TS-400-24 +24V IN
COMM. (WHT)
Load White
Power
Load COMM.
N.C.
Neut RLY
COMM. PULSE OFF (BLK)
Pack ON
N.O.
Black Red 1
PULSE
ON
PULSE PULSE ON (RED)
OFF
Hot (Load)
Local #20/4
Load
OFF Switch
Blue
To Panel
1000' MAX.
Black
Ground
RLY COMM
Red
To circuit
COMM
ON
ON
1
N.O. On Off Comm 24VRect
1
+24V IN
Red Black White Blue
Line
TS-400-24 wiring with power pack TS-400-24 wiring with lighting control panel
Order Information
CATALOG # VOLTAGE LOAD REQ/CURRENT
TS-400 100/120 VAC or 0-800 Watt ballasts or
220/277 VAC; 50/60 Hz 0-1200 Watt ballast
TS-400-24 24 VAC/VDC/VAC rect. Current: 12mA DC/41mA AC
Add –I to Cat. # for Ivory, -W for White, -A for Light Almond; Single-gang cover plate ASP-211
included. Order ASP-422 for blank 2-gang cover plate, ASP-432 for 2-gang plate with switch option,
specify color.
800.879.8585 • www.wattstopper.com 26
Product Line Summary
WS-200 120/277 VAC; 60 Hz Automatic wall switch Passive infrared
WA-200 120/277 230/277 VAC, 50/60 Hz Automatic wall switch Passive infrared
WA-300 120/277 230/277 VAC, 50/60 Hz -with dual relays Passive infrared