User Manual
Issue 02
Date 2018-09-30
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: http://www.huawei.com
Email: support@huawei.com
Issue 02 (2018-09-30) i
Copyright © Huawei Technologies Co., Ltd.
DPU30A, DPU30D, DPU40D, DBU20B, DBU25B, and
DBU40B Distributed Power System
User Manual About This Document
Purpose
This document describes the distributed power system in terms of overview, components,
maintenance, and technical specifications.
Figures provided in this document are for reference only.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided, could
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to personal injury.
Calls attention to important information, best practices and tips.
NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 02 (2018-09-30)
Modified 2.3 System Configuration.
Added 3.6 Lithium Battery (DBU25B-N12A1) and 3.7 Lithium Battery (DBU40B-N12A2).
Software versions: SMU V500R002C50 and LIVE APP V100R001C70
Issue 01 (2018-06-30)
This is the first official release.
Contents
2 Overview......................................................................................................................................... 6
2.1 Introduction .................................................................................................................................................................. 6
2.2 Features ......................................................................................................................................................................... 8
2.3 System Configuration ................................................................................................................................................... 9
3 Components ................................................................................................................................. 12
3.1 PSU (DPU30A-N06A1) ............................................................................................................................................. 12
3.2 PSU (DPU30D-N06A1) ............................................................................................................................................. 17
3.3 PSU (DPU40D-N06A1) ............................................................................................................................................. 22
3.4 Lithium Battery (DBU20B-N12A1) ........................................................................................................................... 28
3.5 Lithium Battery (DBU20B-N12A2) ........................................................................................................................... 31
3.6 Lithium Battery (DBU25B-N12A1) ........................................................................................................................... 35
3.7 Lithium Battery (DBU40B-N12A2) ........................................................................................................................... 38
3.8 DC Distribution Box (DOU-DCD01) ......................................................................................................................... 41
5 Maintenance ................................................................................................................................. 48
5.1 Preventive Maintenance .............................................................................................................................................. 48
5.1.1 Exterior .................................................................................................................................................................... 48
5.1.2 Distributed Power Unit ............................................................................................................................................ 49
5.1.3 Lithium Battery ........................................................................................................................................................ 50
5.1.4 Monitoring Parameters ............................................................................................................................................ 51
5.1.5 Cable ........................................................................................................................................................................ 52
5.2 Rectifying Common Faults ......................................................................................................................................... 53
1 Safety Precautions
When installing or removing power cables, ensure that the corresponding circuits are
disconnected to prevent electric arcs or sparks.
Note that the load may power off during maintenance or fault location if the power
system is not connected to a battery or if battery capacity is insufficient.
Store cables for at least 24 hours at room temperature before laying out them if they were
previously stored at sub-0ºC.
If screws or bolts used to secure the equipment are not tightened to the required torque,
the equipment may fall off the mounting kits.
Routinely check installed equipment and perform maintenance according to the user
manual; replace faulty components quickly to ensure that the device works properly.
After the equipment is installed, ensure that the output is not short-circuited. A short
circuit may burn the fuse.
The equipment installation direction and cable diameter must comply with the
requirements in the quick guide. Otherwise, water may seep into the equipment or cables
and damage the equipment.
The power system is powered by hazardous voltage. Direct or indirect contact (through
damp objects) with the voltage power may result in danger.
Non-standard and improper operations may result in fire and electric shock.
Before electrical connections, turn off the upstream protection switch for the device.
Before connecting the AC power supply, ensure that electrical connections are complete.
Before you connect cables to loads or battery cables, check cable and terminal polarities,
preventing reverse connections.
Battery short circuits will generate high transient currents and release a great deal of energy,
which may cause personal injury.
If conditions permit, disconnect the batteries in use before performing any other operations on
them.
Drilling Holes
Do not drill holes on the module without permission. Non-standard drilling may affect
electromagnetic shielding performance of the module and damage the internal cables, and
metal scraps generated during drilling may short-circuit a circuit board.
Before drilling holes on the module, remove the cables inside the rack.
Wear goggles and protective gloves when drilling holes.
After drilling, clean up metal shavings.
2 Overview
2.1 Introduction
The distributed power system includes the power supply units (PSUs) (DPU30A-N06A1,
DPU30D-N06A1, and DPU40D-N06A1) and the lithium batteries (DBU20B-N12A1,
DBU20B-N12A2, DBU25B-N12A1 and DBU40B-N12A2). It is an indoor or outdoor
wall-mounted power solution that is highly efficient, compact, lightweight, easy to install, and
does not require parameter configuration or maintenance. The power system is designed for
wireless base stations and supports online capacity expansion.
When the AC input of the DPU30A-N06A1 is normal, the AC output port supplies power to
loads through the bypass and the DC output port supplies stable 48 V DC power to charge
batteries. If the AC input is abnormal, the DC input voltage is converted into stable 220 V AC
power which is then supplied to loads.
The DPU30D-N06A1/DPU40D-N06A1 converts AC or HVDC power into stable 48 V DC
power.
The lithium battery supplies backup power to communications equipment.
2.2 Features
Modular hardware
− The PSU integrates power rectification, monitoring, power distribution, and surge
protection.
− The lithium battery integrates a battery management system (BMS), power
distribution, and surge protection.
− Fan-less design, natural cooling
− Compact and lightweight
Diverse installation scenarios
− Mounting on a pole, wall, channel steel, or angle steel
− Side or flush mounting
Flexible to combine
− Interconnected PSUs
− PSU plus lithium battery
− PSU plus RRU
Easy to operate
3 1 0 0 0 0
6 2 0 0 0 0
3 1 1 960 1200 1920
3 1 2 1920 2400 3840
3 1 3 2880 3600 5760
3 1 0 0 0 0
6 2 0 0 0 0
3 1 1 960 1200 1920
3 1 2 1920 2400 3840
3 1 3 2880 3600 5760
6 2 2 1920 2400 3840
6 2 3 2880 3600 5760
9 3 3 - 3600 5760
9 3 4 - 4800 7680
9 3 5 - 6000 9600
12 4 5 - 6000 9600
12 4 6 - 7200 11520
12 4 7 - 8400 13440
11 4 8 - 9600 15360
PSU (DPU30D-N06A1):
− When one PSU is configured, the maximum output power of the PSU is 1500 W.
− When two PSUs are configured, the maximum output power of the PSUs is 2800
W.
− When three or four PSUs are configured, the maximum output power of the PSUs is
1500 W x number of PSUs x 0.8.
PSU (DPU40D-N06A1):
− When one PSU is configured, the maximum output power of the PSU is 2000 W.
− When two PSUs are configured, the maximum output power of the PSUs is 3800
W.
− When three or four PSUs are configured, the maximum output power of the PSUs is
2000 W x number of PSUs x 0.8.
Lithium battery (DBU20B-N12A1):
− When one lithium battery is configured, the maximum output power of the lithium
battery is 1000 W.
− When more than one lithium battery is configured, the maximum output power of
the lithium batteries is 1300 W.
Lithium battery (DBU20B-N12A2):
− When one lithium battery is configured, the maximum output power of the lithium
battery is 2000 W (single port: 1600 W; dual ports: 2000 W).
− When more than one lithium battery is configured, the maximum output power of
the lithium batteries is 2200 W.
Lithium battery (DBU25B-N12A1/DBU40B-N12A2):
− When one lithium battery is configured, the maximum output power of the lithium
battery is 2000 W.
− When two lithium batteries are configured, the maximum output power of the
lithium batteries is 3800 W.
− When three or more lithium batteries are configured, the maximum output power of
the lithium batteries is 2000 W x number of lithium batteries x 0.8.
The maximum load power of the DC system is the smaller value between the output
power of the PSU minus the charging power and the output power of the lithium battery.
The maximum load power of the AC system is the smaller value between the output
power of the PSU and the output power of the lithium battery x 0.93.
If the BAT ports of PSUs (DPU30A-N06A1 and DPU30D-N06A1) and lithium batteries
(DBU20B-N12A1 and DBU20B-N12A2) are not occupied, they can be used as LOAD
ports (maximum load current: 5 A). The LOAD1–LOAD3 ports should be used first.
3 Components
Exterior
Indicators
Ports
(1) Power input port (2) Load output port 1 (3) Load output port 2
(4) Load output port 3 (5) Battery output port (6) COM_DIN port
(7) COM_ALM port (8) Ground screw
Power Ports
Communication Ports
Output Features
Appearance
Indicators
Run indicator Green Off The PSU has no power input or is faulty.
Blinking The PSU is running properly and
slowly communicating with the host properly.
(0.5 Hz)
Blinking The PSU is running properly but is not
fast (4 communicating with the host properly.
Hz)
Alarm indicator Yellow Off There is no PSU alarm.
Steady on There is a PSU alarm.
Blinking The PSU fails to communicate with its
slowly monitoring unit.
(0.5 Hz)
Fault indicator Red Off The PSU is proper.
Steady on The PSU is faulty.
Ports
(1) Power input port (2) Load output port 1 (3) Load output port 2
(4) Load output port 3 (5) Battery output port (6) COM_DIN port
(7) COM_ALM port (8) Ground screw
Power Ports
Communications Ports
13 Reserved Reserved
14 CANH CAN data transmission and reception H
15 CANL CAN data transmission and reception L
Output Feature
Appearance
Indicators
Ports
(1) Power input port (2) Load output port 1 (3) Load output port 2
(4) Load output port 3 (5) Battery output port (6) COM_DIN port
(7) COM_ALM port (8) Ground screw
Power Ports
Communications Ports
Output Characteristics
Appearance
Indicators
Ports
(1) Battery output port 1 (2) COM_IN port (3) COM_OUT port
(4) Battery output port 2 (5) Ground screw
Power Ports
Communications Ports
Appearance
Indicators
Run indicator RUN Green Off The lithium battery has no power
input or is faulty.
Steady on The lithium battery is powered on.
Blinking The lithium battery is communicating
slowly properly with upstream monitoring
(0.5 Hz) equipment.
Blinking The lithium battery fails to
fast (4 communicate with upstream
Hz) monitoring equipment.
Alarm ALM Red Off There is no alarm.
indicator
Steady on The lithium battery has generated a
fault alarm and should be replaced.
Blinking The lithium battery has generated a
slowly protection alarm, which can be
(0.5 Hz) cleared.
Ports
(1) Ground screw (2) COM_IN/OUT port (3) Battery output port 1
(4) Battery output port 2
Power Ports
Communications Port
Appearance
Indicators
Run indicator RUN Green Off The lithium battery has no power
input or is faulty.
Steady on The lithium battery is powered on.
Blinking The lithium battery is communicating
slowly properly with upstream monitoring
(0.5 Hz) equipment.
Blinking The lithium battery fails to
fast (4 communicate with upstream
Hz) monitoring equipment.
Alarm ALM Red Off There is no alarm.
indicator
Steady on The lithium battery has generated a
fault alarm and should be replaced.
Blinking The lithium battery has generated a
slowly protection alarm, which can be
Ports
(1) Ground screw (2) COM_IN/OUT port (3) Battery output port 1
(4) Battery output port 2
Communications Port
Appearance
Indicators
Run indicator RUN Green Off The lithium battery has no power
input or is faulty.
Steady on The lithium battery is powered on.
Blinking The lithium battery is
slowly (0.5 communicating properly with
Hz) upstream monitoring equipment.
Blinking The lithium battery fails to
fast (4 Hz) communicate with upstream
monitoring equipment.
Alarm ALM Red Off There is no alarm.
indicator
Steady on The lithium battery has generated a
fault alarm and should be replaced.
Blinking The lithium battery has generated a
slowly (0.5 protection alarm, which can be
Ports
(1) Ground screw (2) COM_IN/OUT port (3) Battery output port 1
(4) Battery output port 2
Communications Port
Appearance
Ports
(1) Load output port 1 (2) Load output port 2 (3) Load output port 3
(4) Load output port 4 (5) Load output port 5 (6) Battery output port 1
(7) Battery output port 2 (8) Ground screw
Power Ports
4 LIVE APP
Procedure
Step 1 Use a browser to scan the QR code or access Google Play app store
----End
Procedure
Step 1 Register user information.
Tap Later if there is no need to log in to the LIVE Server to download the upgrade file or individual file.
1. Tap the LIVE icon and Yes to access the LIVE APP user registration screen.
Scan the QR code: The administrator sends the project QR code to the user by email. The user scans the
QR code and enters information. After the administrator approves registration information, the user taps
Activate to finish registration.
Step 3 Tap Bluetooth connection in the Select a connection method drop-down list box on the
LIVE APP login screen to search for power equipment with Bluetooth nearby. (The power
equipment SN and Bluetooth name have the same last six digits.)
Step 4 Enter the correct user name (initial value: liveapp) and password (initial value:
Changeme_123).
Step 5 Tap Login to access Main Function Menu and view the operating parameters of the power
equipment.
----End
Follow-up Procedure
For details about how to use the LIVE APP, see the LIVE APP Infographics available at the
support website.
5 Maintenance
5.1.1 Exterior
Table 5-1 Device exterior maintenance
During paint repair, polish any rusty or corroded area with sandpaper and then apply antirust aluminum
spray paint. If there is no rust or corrosion, directly apply the antirust aluminum spray paint.
5.1.5 Cable
Table 5-6 Cable maintenance
Solution
1. Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
2. Check whether the AC input circuit breaker is OFF. If yes, rectify the back-end circuit
fault and switch on the circuit breaker.
3. Check whether the AC input power cable is loose. If yes, secure the input power cable.
5.2.2 AC Overvoltage
Possible Causes
The grid power is unstable.
The AC overvoltage alarm threshold is incorrectly set.
Solution
1. Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
2. Check whether the AC overvoltage alarm threshold is correctly set. If not, adjust it based
on site requirements.
5.2.3 AC Undervoltage
Possible Causes
The grid power is unstable.
The AC undervoltage alarm threshold is incorrectly set.
Solution
1. Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
2. Check whether the AC undervoltage alarm threshold is correctly set. If not, adjust it
based on site requirements.
5.2.4 DC Overvoltage
Possible Causes
The rectifier is faulty.
The DC overvoltage alarm threshold is incorrectly set.
Solution
1. Check whether the indicator on the rectifier is red. If so, replace the rectifier.
2. Check whether the DC overvoltage alarm threshold is correctly set. If not, adjust it based
on site requirements.
5.2.5 DC Undervoltage
Possible Causes
The battery voltage is below the DC undervoltage alarm threshold.
The DC undervoltage alarm threshold is incorrectly set.
The DC output is short-circuited.
Solution
1. Measure the AC input voltage. If the voltage is abnormal, rectify the power grid fault.
2. Check whether the DC undervoltage alarm threshold is correctly set. If not, adjust it
based on site requirements.
3. Remove the load and battery cables one by one and check whether the alarm is cleared.
If so, rectify the short circuit. If the battery fuse is blown or a cable is loosely connected,
check and rectify the fault.
Solution
Check whether the parallel communications or power cable between rectifiers is loose. If so,
secure the cable.
Solution
Check whether the rectifier communications cable is loose. If so, secure the cable.
Solution
1. Check whether the parallel power cable between rectifiers is loose. If so, secure the
cable.
2. Check whether the system output voltage is excessively high. If so, disconnect the
parallel cable, check the output voltage of each rectifier, locate the rectifier with
abnormally high output voltage, and replace it.
Solution
1. Check whether an input cable and terminal is short-circuited. If so, switch off the
upstream input circuit breaker, rectify the fault, and switch on the circuit breaker.
2. Check whether the upstream input circuit breaker for the rectifier has the appropriate
capacity. If not, replace the circuit breaker.
Solution
1. Check whether the output is short-circuited. If so, rectify the fault.
2. Check whether the load power exceeds the maximum output power of the module (see
the appendix "Technical Specifications"). If so, adjust the load based on site
requirements.
Solution
1. Check whether the communications cable of the module is loose. If so, secure the cable.
2. Check whether the output is short-circuited. If so, rectify the fault.
3. Check whether the load power exceeds the maximum output power of the module (see
the appendix "Technical Specifications"). If so, adjust the load based on site
requirements.
4. Check whether the remaining battery capacity is more than 10%. If not, charge the
battery to above 10% and check whether the alarm is cleared.
Solution
Replace the faulty module.
Solution
Check whether the communications cable between the battery and PSU is loose. If so, secure
the cable.
Solution
Check whether the battery communications cable is loose. If so, secure the cable.
Solution
Replace the faulty module.
Solution
Check whether there is a battery heater fault alarm on the app. If the alarm exists, replace the
battery. If the alarm does not exist, wait for a certain period and check whether the battery
temperature rises to above 0°C. If yes, no further action is required. If not, replace the battery.
Solution
1. Check whether the battery is located in the heat dissipation area of other equipment. If so,
isolate the heat source or relocate the battery.
2. Check whether the discharge time in the high-temperature environment meets
requirements. If not, replace the battery.
Solution
Check whether the battery is located in the heat dissipation area of other equipment. If so,
isolate the heat source or relocate the battery.
Solution
1. Check whether the equalized and float charge voltages are correctly set (see the appendix
"Technical Specifications"). If not, adjust the settings based on site requirements.
2. Check whether the PSU output voltage is excessively high. If it is higher than the
configured equalized or float charge voltage and cannot be adjusted, replace the PSU.
Solution
Check the cause of the AC power failure and rectify the fault.
Solution
Replace the faulty module.
Solution
1. Check whether the load exceeds the maximum power of the lithium battery (see the
appendix "Technical Specifications"). If so, expand the lithium battery capacity or
reduce the load of the power system.
2. Check whether the load is short-circuited. If so, rectify the fault.
Solution
Replace the faulty module.
Solution
Check whether the battery communications or power cable is loose. If so, secure the cable.
Replacing a main component requires power disconnection from certain loads. Obtain the
customer's consent before doing so. Take measures to avoid power disconnection for
primary loads. For example, switch primary loads to a proper PSU.
Do not uncover the PSU because high voltage exists inside it. Send a faulty PSU to the
maintenance office where professionals will repair it.
Do not connect or disconnect the quick connectors of the PSU and lithium battery with
power on. Do not contact any port inside by bare hand.
To replace a PSU, switch off the upstream input circuit breaker.
After replacing a module, use the quick connectors on the new module to prepare cables.
For details, see 5.3.6 Replacing a Quick Connector.
The PSU and lithium battery can be mounted on a small or large pole, wall, channel steel, or
angle steel.
The following figure shows the mounting kits.
(1) Pole mounting kit A (2) Pole mounting kit B (3) Pole mounting kit C
(4) Pole mounting kit D (5) Large-pole installation kit (6) Connecting kit
(7) Hanging kit A (8) Hanging kit B
Procedure
Step 1 Put on the protective gloves.
Step 2 Switch off the upstream input circuit breaker for the PSU.
Step 3 Remove the old PSU.
3. Disconnect the cables from the PWR, LOAD, BAT, and COM ports as well as the
ground cable in sequence. Insulate the cables.
4. (Optional) Remove the connecting kit.
5. Remove the old PSU.
6. Loosen the four screws on the hanging kit on the right side or rear of the PSU and take
off the hanging kit.
Step 4 Install the new PSU.
1. Secure the hanging kit to the right side or rear of the new PSU and tighten the four
screws.
2. Install the new PSU.
3. (Optional) Install the connecting kit.
4. Connect the ground cable as well as the cables to the COM, BAT, LOAD, and PWR
ports in sequence based on the recorded information.
5. Use waterproof tape to seal the cable connections.
Step 5 Switch on the upstream input circuit breaker for the PSU.
Step 6 Take off the protective gloves.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Put on the protective gloves.
Step 2 Switch off the upstream input circuit breaker for the PSUs.
Step 3 Remove the old PSUs.
1. Record the cable connection positions on the PSUs.
2. Use a flat-head screwdriver to pry the fastener on the quick connector and take off the
connector, as shown in the following figure.
3. Disconnect the cables from the PWR, LOAD, BAT, and COM ports as well as the
ground cable in sequence. Insulate the cables.
4. Remove the old PSUs.
5. Loosen the four screws on the hanging kit on the right side of the PSUs and take off the
hanging kit.
6. Loosen the four screws that secure the PSUs to the connecting kit, and take off the PSUs.
7. Loosen the four screws that secure the connecting kit to the PSU and take off the
connecting kit.
5. Connect the ground cable as well as the cables to the COM, BAT, LOAD, and PWR
ports in sequence based on the recorded information.
6. Use waterproof tape to seal the cable connections.
Step 5 Switch on the upstream input circuit breaker for the PSUs.
Step 6 Take off the protective gloves.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Put on the protective gloves.
Step 2 Switch off the upstream input circuit breaker for the PSU.
Step 3 Remove the old PSU.
1. Record the cable connection positions on the PSU.
2. Use a flat-head screwdriver to pry the fastener on the quick connector and take off the
connector, as shown in the following figure.
3. Disconnect the cables from the PWR, LOAD, BAT, and COM ports as well as the
ground cable in sequence. Insulate the cables.
4. Loosen the four screws that secure the PSU to the connecting kit, and take off the PSU.
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Put on the protective gloves.
3. Disconnect the cables from the BAT and COM ports as well as the ground cable in
sequence. Insulate the cables.
For an operating lithium battery, its run indicator will turn off about 3 minutes after cables are
disconnected from the BAT and COM ports.
4. (Optional) Remove the connecting kit.
5. Remove the old lithium battery.
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Put on the protective gloves.
Step 2 Switch off the upstream input circuit breaker for the PSU.
Step 3 Remove the old lithium battery.
3. Disconnect the cables from the PWR, LOAD, BAT, and COM ports as well as the
ground cable in sequence. Insulate the cables.
For an operating lithium battery, its run indicator will turn off about 3 minutes after cables are
disconnected from the BAT and COM ports.
4. Record the cable connection positions on the lithium battery. Disconnect the cables from
the BAT and COM ports as well as the ground cable in sequence. Insulate the cables.
5. Loosen the four screws that secure the PSU to the connecting kit, and take off the PSU.
6. Remove the old lithium battery.
7. Loosen the four screws that secure the lithium battery and connecting kit, and take off
the connecting kit.
Step 4 Install the new lithium battery.
1. Loosen the four screws on the hanging kit behind the new lithium battery, take off the
hanging kit, install it on the right side of the lithium battery, and tighten the four screws.
2. Install the connecting kit onto the right side of the new lithium battery and tighten the
four screws.
3. Install the new lithium battery and tighten the screws on the hanging kit.
4. Install the PSU onto the connecting kit on the right side of the new lithium battery and
tighten the four screws.
5. Connect the ground cable as well as the cables to the COM and BAT ports on the lithium
battery in sequence based on the recorded information.
6. Connect the cables to the PSU. Connect the ground cable as well as the cables to the
COM, BAT, LOAD, and PWR ports in sequence based on the recorded information.
7. Use waterproof tape to seal the cable connections.
Step 5 Switch on the upstream input circuit breaker for the PSU.
Step 6 Take off the protective gloves.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Put on the protective gloves.
Step 2 Switch off the upstream input circuit breaker for the PSU.
Step 3 Remove the old quick connector.
1. Record the cable connection position on the old PSU.
2. Remove the quick connector from the old PSU and remove the cable.
Follow-up Procedure
Pack the faulty component and return it to the local Huawei warehouse.
Context
DC fuses are located inside the battery or load wiring terminals, as shown in the following
figure.
(1) Fuse
Procedure
Step 1 Put on the protective gloves.
Step 2 Record the quick connector for a BAT or LOAD port where the fuse should be replaced.
Step 3 Use a flat-head screwdriver to prize up the buckle on the quick connect terminal and remove
the terminal.
Step 4 Use an insulated flat-head screwdriver to remove the old fuse, as shown in the following
figure.
As shown in the preceding figure, when the flat-head screwdriver is turned to Open, the flat-head bolt
ejects. Then remove the fuse.
Step 5 Install the new fuse in a reverse order of the removal procedure.
Step 6 Connect the quick connector to the BAT or LOAD port based on the recorded information.
Step 7 Use waterproof tape to seal the cable connections.
Step 8 Take off the protective gloves.
----End
A Technical Specifications
Item Specifications
Operating Class C
environment
Operating DPU30A-N06A1, DPU30D-N06A1, DPU40D-N06A1,
temperature DBU20B-N12A2, DBU25B-N12A1, and DBU40B-N12A2:
With solar radiation: –40°C to +50°C
Without solar radiation: –40°C to +55°C
DBU20B-N12A1:
With solar radiation: –40°C to +45°C
Without solar radiation: –40°C to +55°C
Storage DPU30A-N06A1, DPU30D-N06A1, and DPU40D-N06A1:
temperature –40°C to +70°C
DBU20B-N12A1, DBU20B-N12A2, DBU25B-N12A1, and
DBU40B-N12A2: –40°C to +60°C
Operating 0%–95% RH (non-condensing)
humidity
Storage humidity 0%–95% RH (non-condensing)
Altitude DPU30A-N06A1, DPU30D-N06A1, DBU20B-N12A1,
DBU25B-N12A1, and DBU40B-N12A2: –60 m to 4000 m
(When the altitude ranges from 2000 m to 4000 m, high
temperature derating applies and the operating temperature
decreases by 1°C for each additional 200 m.)
DPU40D-N06A1, DBU20B-N12A2: –60 m to 5000 m (When the
altitude ranges from 3000 m to 5000 m, high temperature derating
applies and the operating temperature decreases by 1°C for each
additional 200 m.)
Others There should be no conductive dust, corrosive gas, or explosion
hazard.
Dust, corrosive substances, pests, molds, and other indicators should
be controlled in accordance with class 4.1 requirements in ETSI EN
Item Specifications
300 019-1-4 (V2.2.1).
Class C environments refer to sea environments or outdoor land environments (with simple shielding
measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt
water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal
mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber,
and galvanization industries, or 1 km away from light pollution sources, such as packing houses,
tanneries, and boiler rooms.
Item Specifications
Item Specifications
Regulated voltage ±3 V
precision
Total harmonic 1.5%, full rated load
distortion voltage
(THDv)
Output current peak Max. 3:1
factor
AC input surge Differential mode: 20 kA (L-N); common mode: 20 kA (L+N to
protection ground), 8/20 µs
AC output surge Differential mode: 20 kA (L-N); common mode: 20 kA (L+N to
protection ground), 8/20 µs
DC surge Differential mode: 3 kA; common mode: 5 kA (positive + negative to
protection ground), 8/20 µs
Protection level IP65
Bluetooth Frequency: 2.402–2.480 GHz; power: 4 dBm
frequency and
power
Safety design IEC/EN60950-1
Mean time 500,000 hours
between failures
(MTBF)
Item Specifications
Item Specifications
Default output With lithium batteries: –54.5 V DC
voltage Without lithium batteries: –53.5 V DC
Regulated voltage ≤ ±0.6% (output voltage: 48–55 V DC. The
precision output voltage is within the range of 53.5 V
DC±0.1 V DC when the load is 50%.)
Ripple and noise ≤ 200 mVp-p (output 48–55 V DC, 5%–100%
load)
Current sharing < ±5% (output 48–55 V DC, 20%–100%
imbalance load)
AC input AC input ≥ 300 V AC
protection overvoltage
protection threshold
AC input 290–300 V AC
overvoltage
recovery threshold
AC input ≤ 85 V AC
undervoltage
protection threshold
AC input 85–90 V AC
undervoltage
recovery threshold
DC input DC input ≥ 425 V DC
protection overvoltage
protection threshold
DC input 415–425 V DC
overvoltage
recovery threshold
DC input ≤ 85 V DC
undervoltage
protection threshold
DC input 85–90 V DC
undervoltage
recovery threshold
DC output DC output –56 V DC to –60 V DC
protection overvoltage Default voltage: –59.5 V DC
protection threshold
AC surge Differential mode: 20 kA (L-N); common mode: 20 kA (L+N to
protection ground), 8/20 µs
DC surge Differential mode: 10 kA; common mode: 20 kA (positive + negative
protection to ground), 8/20 µs
Protection level IP65
Item Specifications
Bluetooth Frequency: 2.402–2.480 GHz; power: 4 dBm
frequency and
power
Safety design IEC/EN60950-1
MTBF 500,000 hours (Telcordia SR-332 Issue 3 Method 1)
Item Specifications
AC input Input system 220 V single-phase, compatible with 110 V
dual-live wire
Input voltage 90–290 V AC
Input frequency 45–65 Hz (rated frequency: 50 Hz/60 Hz)
Power factor ≥ 0.90 (15%–30% load)
≥ 0.97 (30%–50% load)
≥ 0.98 (50%–100% load)
≥ 0.99 (100% load)
Total harmonic ≤ 5% (load ≥ 50%)
distortion (THD)
HVDC input Input voltage 90–400 V DC
DC output Output voltage –42 V DC to –58 V DC
range
Default output With lithium batteries: –54.5 V DC
voltage Without lithium batteries: –53.5 V DC
Regulated voltage ≤ ±0.6% (output voltage: 48–55 V DC. The
precision output voltage is within the range of 53.5 V
DC ±0.1 V DC when the load is 50%.)
Ripple and noise ≤ 200 mVp-p (output 48–55 V DC, 5%–100%
load)
Current sharing < ±5% (output 48–55 V DC, 20%–100%
imbalance load)
AC input AC input ≥ 300 V AC
protection overvoltage
protection threshold
AC input 290–300 V AC
overvoltage
recovery threshold
AC input ≤ 85 V AC
Item Specifications
undervoltage
protection threshold
AC input 85–90 V AC
undervoltage
recovery threshold
DC input DC input ≥ 410 V DC
protection overvoltage
protection threshold
DC input 400–410 V DC
overvoltage
recovery threshold
DC input ≤ 85 V DC
undervoltage
protection threshold
DC input 85–90 V DC
undervoltage
recovery threshold
DC output DC output –56 V DC to –60 V DC
protection overvoltage Default voltage: –59.5 V DC
protection threshold
AC surge Differential mode: 20 kA (L-N); common mode: 20 kA (L+N to
protection ground), 8/20 µs
DC surge Differential mode: 10 kA; common mode: 20 kA (positive + negative
protection to ground), 8/20 µs
Protection level IP65
Bluetooth Frequency: 2.402–2.480 GHz; power: 4 dBm
frequency and
power
Safety design IEC/EN60950-1
MTBF 500,000 hours (Telcordia SR-332 Issue 3 Method 1)
Item Specifications
Electromagnetic Conducted emission Input: class B, EN55022: 2010
interference (EMI) (CE) Output: class A1
Radiated emission Class B, EN55022: 2010
(RE)
Harmonic current IEC 61000-3-2: 2014
Item Specifications
Voltage fluctuation IEC 61000-3-3: 2013
and flicker
Electromagnetic ESD IEC 61000-4-2
susceptibility Contact discharge: 6 kV; air discharge: 8 kV
(EMS)
Electrical fast IEC 61000-4-4
transient (EFT) AC power port: ±2 kV; DC power port: ±2
kV; signal port: ±1 kV
Radiated IEC 61000-4-3
susceptibility (RS) 80 MHz to 1000 MHz: 10 V/m
1000 MHz to 2700 MHz: 10 V/m
Conducted IEC 61000-4-6
susceptibility (CS) Power port: 10 V; signal port: 10 V
Surge susceptibility IEC 61000-4-5
AC power port: 6 kV in differential mode,
6 kV in common mode, 1.2/50 µs
DC power port: 2 kV in differential mode,
4 kV in common mode, 1.2/50 µs
Signal port: 0.5 kV in differential mode, 1
kV in common mode, 1.2/50 µs
Voltage dip IEC 61000-4-11
Item Specifications
Electromagnetic Conducted emission Input: class B, EN55032: 2012
interference (EMI) (CE) Output: class A1
Radiated emission Class B, EN55032: 2012
(RE)
Harmonic current IEC 61000-3-2: 2014
Voltage fluctuation IEC 61000-3-3: 2013
and flicker
Electromagnetic ESD IEC 61000-4-2
susceptibility Contact discharge: 6 kV; air discharge: 8 kV
(EMS)
Electrical fast IEC 61000-4-4
transient (EFT) AC power port: ±2 kV; DC power port: ±2
kV; signal port: ±1 kV
Radiated IEC 61000-4-3
Item Specifications
susceptibility (RS) 80 MHz to 1000 MHz: 10 V/m
1000 MHz to 6000 MHz: 10 V/m
Conducted IEC 61000-4-6
susceptibility (CS) Power port: 10 V; signal port: 10 V
Surge susceptibility IEC 61000-4-5
AC power port: 6 kV in differential mode,
6 kV in common mode, 1.2/50µs
DC power port: 2 kV in differential mode,
4 kV in common mode, 1.2/50µs
Signal port: 0.5 kV in differential mode,
1 kV in common mode, 1.2/50µs
1 kV in common mode, 10/700µs
Voltage dip AC input: IEC 61000-4-11
DC input: IEC 61000-4-29
Item Specifications
Electromagnetic Conducted emission Class B, EN55032: 2012
interference (EMI) (CE)
Radiated emission Class B, EN55032: 2012
(RE)
Electromagnetic ESD IEC 61000-4-2
susceptibility Contact discharge: 6 kV; air discharge: 8 kV
(EMS)
Radiated IEC 61000-4-3
susceptibility (RS) 80 MHz to 1000 MHz: 10 V/m
1000 MHz to 2700 MHz: 10 V/m
Electrical fast IEC 61000-4-4
transient (EFT) Power port: ±1 kV/±2 kV
Surge susceptibility IEC 61000-4-5
Power port: 2 kV in differential mode, 4 kV
in common mode, 1.2/50 µs
Conducted IEC 61000-4-6
susceptibility (CS) Power port: 10 V
Item Specifications
Electromagnetic Conducted Class A, EN55032: 2012
interference (EMI) emission (CE)
Radiated emission Class B, EN55032: 2012
(RE)
Electromagnetic ESD IEC 61000-4-2
susceptibility (EMS) Contact discharge: 8 kV; air discharge: 15
kV
Radiated IEC 61000-4-3
susceptibility (RS) 80 MHz to 1000 MHz: 10 V/m
1000 MHz to 2700 MHz: 10 V/m
Electrical fast IEC 61000-4-4
transient (EFT) DC power port: ±2 kV; signal port: ±1 kV
Surge IEC 61000-4-5
susceptibility DC power port: 2 kV in differential
mode, 4 kV in common mode, 1.2/50 µs
Signal port: 1 kV in common mode,
10/700 µs
Conducted IEC 61000-4-6
susceptibility (CS) Power port: 10 V; signal port: 10 V
Note 1: This is a class A product. In a living environment, this product may cause radio interference.
Therefore, users may be required to take appropriate measures.
Item Specifications
Dimensions (H x 400 mm x 60 mm x 300 mm (excluding the protruding part)
W x D)
Weight < 7 kg
Efficiency Bypass efficiency ≥ 98% (peak point)
Battery inversion efficiency ≥ 93% (peak point)
Battery charging efficiency ≥ 94% (peak point)
Bypass AC output 2000 W (176–280 V AC)
power 2000–1000 W (linear derating at 176–90 V AC)
Inverter AC output 1500 W (at 220 V AC)
power
DC output power 1200 W (176–280 V AC)
Item Specifications
1200–600 W (linear derating at 176–90 V AC)
Item Specifications
Dimensions (H x 400 mm x 60 mm x 300 mm (excluding the protruding part)
W x D)
Weight < 7.5 kg
Efficiency ≥ 93% (230 V AC, 30% load)
≥ 96% (230 V AC, 50% load)
≥ 95% (230 V AC, 100% load)
Linear power 2000 W (176–290 V AC or 176–420 V DC)
derating 2000–1000 W (linear derating at 176–90 V AC or 176–90 V DC )
Item Specifications
Capacity 20 Ah
Maximum discharge power 1000 W
Maximum charge current 10 A
Equalized charge voltage 56.4 V DC
Float charge voltage 54.5 V DC
Disconnection voltage 47 V DC
Dimensions (H x W x D) 420 mm x 120 mm x 300 mm
Item Specifications
Weight 18 kg
Item Specifications
Capacity 20 Ah
Maximum discharge power Discharge from one load port: 1600 W
Discharge from two load ports: 2000 W
Maximum charge current 10 A
Equalized charge voltage 56.4 V DC
Float charge voltage 54.5 V DC
Disconnection voltage 47 V DC
Dimensions (H x W x D) 420 mm x 120 mm x 300 mm
Weight ≤ 21 kg
Item Specifications
Capacity 25 Ah
Maximum discharge power 2000 W
Maximum charge current 12.5 A
Equalized charge voltage 56.4 V DC
Float charge voltage 54.5 V DC
Disconnection voltage 47 V DC
Dimensions (H x W x D) 420 mm x 120 mm x 305 mm
Weight ≤ 25 kg
Item Specifications
Capacity 40 Ah
Maximum discharge power 2000 W
Item Specifications
Maximum charge current 20A
Equalized charge voltage 56.4 V DC
Float charge voltage 54.5 V DC
Disconnection voltage 47 V DC
Dimensions (H x W x D) 420 mm x 120 mm x 305 mm
Weight ≤ 25 kg
B Alarm Description