Professional Documents
Culture Documents
D 58 PDF
D 58 PDF
1-7/16 3-11/16
1-1/4 [35.53] [93.66] Ø7/32 [5.56] HOLE
5/8
[31.75] [15.88]
5-29/32
4-25/32 [150.02]
[121.44]
25/32 4-23/32
[19.84] [119.86]
1-1/8
[28.58] 25/32 [19.84] 7/32 X 13/32
7-13/32 [188.12] [5.56 X 10.32]
2-1/4 MOUNTING SLOT
[57.15] MAX
Mark II #26, 28 and MM180 use blue gage fluid (specific gravity MAINTENANCE
1.9). Check fluid level regularly and adjust zero with zero adjust knob.
Be sure tubing connections are disconnected and gage is open
If additional fluid is required, call, fax or email the Dwyer office to atmosphere before adjusting zero.
listed at bottom of page.
Clean with mild soap and water. Avoid any cleaning fluids which
INSTALLATION may result in damaging the gage.
Position manometer on a vertical surface. Drill two 1/8˝ or 9/64˝
holes on a vertical line 3-15/16˝ apart. Loosely mount ACCESSORIES
manometer with self-tapping screws provided. Adjust gage until Each Mark II manometer includes two tubing connectors for 1/8˝
level bubble is centered in level vial, then secure the manometer pipe or sheet metal ducts, two mounting screws, 1 oz. bottle of
tightly. indicating fluid, red and green pointer flags, 8´ of double column
tubing and instructions.
For portable use, order optional A-612 Portable Stand.
FILLING
Turn the zero set knob counterclockwise until it stops, then turn Model Range Fluid Used
clockwise 3 full turns. This puts zero in approximately the middle Mark II 25 0-3 in w.c Red fluid, .826 s.g.
of the travel adjustment in either direction. Remove the fill plug Mark II 26 0-7 in w.c. Blue oil, 1.91 s.g.
and fill with gage fluid until fluid reaches zero on scale. Minor Mark II 27* 0-7000 fpm Red fluid, .826 s.g.
adjustments can be made to adjust zero by adjusting zero knob. Mark II MM-80 0-80 mm w.c. Red fluid, .826 s.g.
Replace fill plug. If gage is overfilled, remove excess by inserting Mark II M-700PA 10-0-700 Pa Red fluid, .826 s.g.
pipe cleaner through the fill port to blot up excess fluid.
PITOT TUBE
(SECTION
ENLARGED
TO SHOW
DETAIL)
Pt Ps
FLOW
RANGOS
Modelo Rango Fluido
25 0~3˝ C.A. 0,826 rojo
26 0~7˝ C.A. 1,9 azul
M-80 0~80 mm C.A. 0,826 rojo
M-180 0~180 mm C.A. 1,9 azul
M-700 Pa 10~0~700 Pascal 0,826 rojo
27 * 0~7.000 pie./min. 0,826 rojo
28 * 0~10.500 pie./min. 1,9 azul
*Los modelos 27 y 28 requieren tubo
Pitot, con costo adicional.
PITOT TUBE
(SECTION
ENLARGED
TO SHOW
DETAIL)
Pt Ps
FLOW
©Copyright 2013 Dwyer Instruments, Inc. Printed in U.S.A. 5/13 FR# 67-440215-00 Rev. 14