Manual control for operating temporary cooling water system

No. Tag no. Initial filling Start-up Normal Op. Shut down
1. BV 01 Open Open Open Open
2. BV 02 Open Open Open Open
3. BV 03 Closed Open Open Open
4. BV 04 Closed Open Open Open
5. BV 05 Open Closed Closed Closed
6. BV 06 Closed Closed Closed Closed
7. Chiller A Stop Start Start Stop
8. Chiller B Stop Start Start Stop
9. Water Cooling Pump Stop Stop Start Stop
10. Water Chiller Pump Start Start Start Stop