User Manual: HGM9200/9300/9400 Series
User Manual: HGM9200/9300/9400 Series
(HGM9210/HGM9220/HGM9310/HGM9320/HGM9410/HGM9420)
USER MANUAL
Smartgen Technology
Chinese trademark
English trademark
Zhengzhou
Henan Province
P. R. China
Tel: 0086-371-67988888/67981888
0086-371-67991553/67992951
0086-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: sales@smartgen.cn
All rights reserved. No part of this publication may be reproduced in any material form
(include photocopying or storing in any medium by electronic means or other) without the
written permission of the copyright holder.
Applications for the copyright holder‟s written permission to reproduce any part of this
publication should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their
respective companies.
Smartgen Technology reserves the right to change the contents of this document without
prior notice.
Software Version
Date Version Note
2012-03-08 1.0 Original release
2012-6-11 1.1 Modify some parameters
2013-1-14 1.2 Modify some parameters
Clarification of notation used within this publication.
SIGN INSTRUCTION
Indicates error operation may cause death, serious injury and significant
WARNING! property damage.
HGM9200/9300/9400 Series Gen-set Controller
CONTENTS
1 SUMMARY ....................................................................................................................................................... 7
2 MODULES COMPARISON AND MODULES ABBREVIATION ................................................. 7
15.14 PERKINGS............................................................................................................. 61
15.19 YUCHAI.................................................................................................................. 63
HGM9200/9300/9400 Series Gen-set Controller Vision 1.2 2013-01-14 Page 5 of 65
HGM9200/9300/9400 Series Gen-set Controller
15.20 WEICHAI ................................................................................................................ 64
16 FAULT FINDING................................................................................................................................... 64
1 SUMMARY
HGM9200/9300/9400 series genset controllers are used for genset automation and monitor
control system of single unit to achieve automatic start/stop, data measure, alarm protection
and “three remote” (remote control, remote measuring and remote communication). The
controller adopts large liquid crystal display (LCD) and selectable Chinese, English or other
languages interface with easy and reliable operation.
HGM9200/9300/9400 controller adopts 32 bits micro-processor technology with precision
parameters measuring, fixed value adjustment, time setting and threshold adjusting and etc.
The majority of parameters can be set using front panel and all the parameters can be set
using PC (via USB port) and can be adjusted and monitored with the help of RS485 and Link
ports. It can be widely used in a number of automatic genset control system with compact
structure, simple connections and high reliability.
2.1MODULES COMPARISON
HGM HGM HGM HGM HGM HGM HGM HGM HGM HGM
9210 9220 9310 9320 9410 9420 9610 9620 9510 9520
L Dimen-
3.6” 4.3”
C sion
D pixel 132 x 64 320 x 200
AMF ● ● ● ● ●
BUS
●
Monitoring
Parallel
● ●
connection
Extension
● ●
module
Input Port
7 7 7 7 7 7 8 8 7 7
Number
Output port
8 8 8 8 8 8 8 8 8 8
Number
Sensor
5 5 5 5 5 5 5 5 5 5
number
Neutral
(earth) ● ●
current
Schedule
● ● ● ● ● ● ● ● ● ●
function
HGM9200/9300/9400 Series Gen-set Controller Vision 1.2 2013-01-14 Page 7 of 65
HGM9200/9300/9400 Series Gen-set Controller
ETHERNET ● ●
RS485 ● ● ● ● ● ● ● ●
GSM ● ● ● ● ● ●
J1939 ● ● ● ● ● ●
USB ● ● ● ● ● ● ● ● ● ●
LINK ● ●
Real-time
● ● ● ● ● ● ● ● ● ●
clock
Event log ● ● ● ● ● ● ● ● ● ●
SD card ● ●
NOTE:
(1) Two of the outputs are fixed: start output and fuel output.
(2)HGM9200/HGM9300/HGM9400‟s analog sensors are composed by 3 fixed sensors
(temperature, pressure, liquid level) and 2 configurable sensors.
NOTE: Functions of mentioned herein HGM9510/HGM9520/HGM9610/HGM9620
controllers can be changed, please check the corresponding user manual for accurate
information.
2.2MODELES ABBREVIATION
Abbreviation Description
HGM9X20 All HGM9000 series AMF controllers
HGM9X10 All HGM9000 series ASM(Auto Start Module) controllers
HGM9X10, Auto Start Module. It controls gen-set to start or stop automatically by remote start
signal.
HGM9X20, Auto Main Failure, updates based on HGM9X10, especially for automatic system
composed by gens and mains.
Main characteristics,
♦ With ARM-based 32-bit MCU, highly integrated hardware, new reliability level;
♦ 132x64 LCD with backlight, multilingual interface (including English, Chinese or other
languages) which can be chosen at the site, making commissioning convenient for factory
personnel;
♦ Improved LCD wear-resistance and scratch resistance due to hard screen acrylic;
HGM9200/9300/9400 Series Gen-set Controller Vision 1.2 2013-01-14 Page 8 of 65
HGM9200/9300/9400 Series Gen-set Controller
♦ Silicon panel and pushbuttons for better operation in high-temperature environment;
♦ RS485 communication port enabling remote control, remote measuring, remote
communication via ModBus protocol; (controller with RS485 port only);
♦ Equipped with SMS (Short Message Service) function. When gen-set is alarming,
controller can send short messages via SMS automatic to max. 5 telephone numbers.
User can control or check gen-set by sending Short Message (controller with GSM port
only);
♦ Equipped with CANBUS port and can communicate with J1939 genset. Not only can users
monitoring frequently-used data (such as water temperature, oil pressure, speed, fuel
consumption and so on) of ECU machine, but also control starting up, shutdown , raising
speed and speed droop via CANBUS port. (controller with CAN BUS port only);
♦ Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire
systems with voltage 120/240V and frequency 50/60Hz;
♦ Collects and shows 3-phase voltage, current, power parameter and frequency of generator
or mains.
Mains Gens
Line voltage (Uab, Ubc, and Uca) Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc) Phase voltage (Ua, Ub, and Uc)
Phase sequence Phase sequence
Frequency: Hz Frequency: Hz
Load
Current IA, IB, IC
Each phase and total active power: KW
Each phase and total reactive power: KVar
Each phase and total apparent power: KVA
Each phase and average power factor: PF
Accumulate total gens power: kWh, kVarh, kVAh
♦ For Mains, controller has over and under voltage, over and under frequency, loss of phase
and phase sequence wrong functions; For generator, controller has over and under
voltage, over and under frequency, loss of phase, phase sequence wrong, over and
reverse power, over current functions;
♦ 3 fixed analog sensors (temperature, oil pressure and liquid level);
♦ 2 configurable sensors can be set as sensor of temperature, pressure or fuel level;
♦ Precision measure and display parameters about Engine,
Temp. (WT) °C/°F both be displayed
4 SPECIFICATION
Items Contents
Operating Voltage DC8.0V to DC35.0V, Continuous Power Supply.
Power Consumption <4W (standby ≤2W)
Alternator Input Range
3-Phase 4-Wire AC15V-AC360V (ph-N)
3-Phase 3-Wire AC30V - AC620V (ph-ph)
Single-Phase 2-Wire AC15V - AC360V (ph-N)
2-Phase 3-Wire AC15V - AC360V (ph-N)
Alternator Frequency 50/60Hz
Speed sensor voltage 1.0V to 24.0V (RMS)
Speed sensor Frequency 10,000 Hz (max.)
Start Relay Output 16 Amp DC28V
Fuel Relay Output 16 Amp DC28V
Programmable Relay Output (1) 7 Amp DC28V
Programmable Relay Output (2) 7 Amp DC28V
Programmable Relay Output (3) 7Amp DC28V
Programmable Relay Output (4) 7Amp AC250V voltage free output
Programmable Relay Output (5) 7 Amp AC250V voltage free output
Programmable Relay Output (6) 7 Amp AC250V voltage free output
Case Dimension 266mm x182mm x45mm
Panel Cutout 214mm x160mm
C.T. Secondary 5A rated
Working Conditions Temperature: (-25~+70)°C; Humidity: (20~93)%RH
Storage Condition Temperature: (-30~+80)°C
IP55: when waterproof rubber seal installed between
controller and panel fascia.
Protection Level
IP42: when waterproof rubber seal is not installed
between the controller and panel fascia.
Object: input/output/power
Insulating Intensity Quote standard: IEC688-1992
Test way: AC1.5kV/1min leakage current: 3mA
5 OPERATION
5.1INDICATOR LIGHT
HGM9X20
HGM9X10
Auto Mode Press this key and controller enters in Auto mode.
1) Screen scroll;
Left
2) Left move cursor in setting menu.
1) Screen scroll;
Right
2) Right move cursor in setting menu.
1. Enters help menu;
2. Pressing and holding for more than 3 seconds
Set/Confirm
enters parameter configuration menu;
3. In settings menu confirms the set value.
1)Return to main menu; 2) Return to previous
Exit
menu in setting menu
If you forget it, please contact Smartgen services and send all information in the controller page
of “ABOUT” to us.
5.3LCD DISPLAY
5.3.1MAIN DISPLAY
Main screen is divided into left and right separate viewing areas. Both viewing areas show
Remark:
P stands for active power
Q stands for reactive power
Power
Conditions Active power Inactive power Remark
factor
Load is inductive resistance.
COS>0L P>0,Q>0 Input Input
Including as following,
★Mains settings
★Timer settings
★Engine settings
★Generatorsettings
★Load settings
★Switch settings
★Analog sensor settings
★Digital input settings
★Relay output settings
★Module settings
★Scheduling and maintenance settings
★GSM settings
Example,
Advanced Parameters
Form1: Use to scroll settings, to enter settings
>Mains
>Timers (form2), to exit settings menu.
>Engine
>Generator
Generator Form 2:
>Return Use to scroll settings (Form3); Select” Return” and
>AC System
>Poles press back to previous menu(form 1) back to
>Rated Voltage previous menu.( form 1 )
NOTE: Long time pressing can exit setting directly during setting.
1. MANUAL START: Press , controller enters into Manual mode and its indicator lights.
Press to start generator, can automatically detect crank disconnected, and
generator accelerates to high-speed running automatically. With high temperature, low oil
pressure and abnormal voltage during generator running, controller can protect genset to
stop quickly. Press ( HGM9X20) or and ( HGM9X10) to control switch on or
off. (please refer to No.4~9 of Auto start operation for detail procedures, the procedure is
same, except for switch open ways and close ways are different)
2. MANUAL STOP: Press can stop the running generators. (please refer to No.3~8 of
Auto stop operation for detail procedures).
NOTE: In “manual mode”, the procedures of ATS please refer to corresponding contents in
this manual.
Press generator switch on or off key , if generator has taken load, will send unload signal; if
taken no load, generator will send load signal; if mains has taken load, mains will unload, and
then generator will take load.
Press mains switch on or off key ,if mains has taken load, will send unload signal; if taken no
load, mains will send load signal; if generator has taken load, generator will unload, and then
mains will take load.
B. If “Open breaker detect” is “SELECT Enable”
To transfer load from mains to generator need to press mains switch off key firstly. After
switch off delay, press generator switch on key ,and generator will take load (there is no
action when pressing switch on key directly).
The way to transfer from generator to mains is as same as above.
Auto transfer procedures:
When controller is in AUTO Test, switch control procedures will start through automatic transfer.
1. If input port is connected with closing breaker signal
A. If “Open breaker detect” is “SELECT Enable”
When transferring load from mains to gens, controller begins detecting “fail to transfer”, then the
open delay and transfer rest delay will begin. When detecting time out, the gens will not switch
on if switch open failed, otherwise, gens switch on. Detecting transfer failure while gens switch
on. When detecting time out, if switch on fail, it is need to wait for gens to switch on. If transfer
failed and warning “SELECT Enable”, there is alarming signal whatever switch on or off failure.
The way to transfer from gens load to mains load is as same as above.
B. If “Open breaker detect” is “SELECT Disable”
Mains load is transferred into gens load, after the delay of switch off and transfer interval, gens
switch on. Detecting transfer fail while gens switch on. After detecting time out, if switch on fail,
then wait for gens switch on. If transfer fail and warning “SELECT Enable”, there is alarming
signal.
2. If input port is not connected with closing breaker input
Mains load be transferred into gens load, after switch off and transfer interval delay, gens switch
on.
The way to transfer gens load to mains load is as same as above.
Press generator switch on key , generator will output load signal. Press gens switch off
6 PROTECTION
6.1WARNINGS
When controller detects the warning signal, alarm only and not stop gen-set.
Warnings as following,
No. Type Description
When controller detects the speed is higher than the set
1 Over Speed Warn
value, it will send warn signal.
When controller detects the speed is lower than the set value,
2 Under Speed Warn
it will send warn signal.
When controller detects the speed is 0 and the action select
3 Loss of Speed Warn
“Warn”, it will send warn signal.
Over Frequency When controller detects the frequency is higher than the set
4
Warn value, it will send warn signal.
Under Frequency When controller detects the frequency is lower than the set
5
Warn value, it will send warn signal.
When controller detects the voltage is higher than the set
6 Over Voltage Warn
value, it will send warn signal.
When controller detects the voltage is lower than the set
7 Under Voltage Warn
value, it will send warn signal.
When controller detects the current is higher than the set
8 Over Current Warn
value, it will send warn signal.
9 Fail to Stop When generator not stops after the “stop delay” is over.
When controller detects the charger voltage is lower than the
10 Charge Alt Fail
set value, it will send warn signal.
When controller detects the battery voltage is higher than the
11 Battery Over Voltage
set value, it will send warn signal.
Battery Under When controller detects the battery voltage is lower than the
12
Voltage set value, it will send warn signal.
When count down time is 0 and the action select “Warn”, it will
13 Maintenance Due
send warn signal.
When controller detects the reverse power value (power is
14 Reverse Power
negative) is lower than the set value, it will send warn signal.
When controller detects the reverse power value (power is
15 Over Power
positive) is higher than the set value, it will send warn signal.
6.2SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to stop the generator.
Shutdown alarms as following,
No. Type Description
When controller detects emergency stop signal, it will send a
1 Emergency Stop
stop signal.
When controller detects the speed value is higher than the set
2 Over Speed
value, it will send a stop signal.
When controller detects the speed value is lower than the set
3 Under Speed
value, it will send a stop signal.
Loss Of Speed When controller detects speed value equals to 0, and the
4
Signal action select “Shutdown”, it will send a stop alarm signal.
When controller detects the frequency value is higher than
5 Over Frequency
the set value, it will send a stop signal.
When controller detects the frequency value is lower than the
6 Under Frequency
set value, it will send a stop signal.
When controller detects the voltage value is higher than the
7 Over Voltage
set value, it will send a stop signal.
When controller detects the voltage value is lower than the
8 Under Voltage
set value, it will send a stop signal.
If genset start fail within setting of start times, controller will
9 Fail To Start
send a stop signal.
When controller detects the current value is higher than the
10 Over Current
set value, it will send a stop signal.
When count down time is 0 and the action select “Shutsown”,
11 Maintenance Due
it will send a stop alarm signal.
When controller gets stop signal from engine via J1939, it will
12 ECU shutdown
send a stop signal.
When controller NOT gets data from engine via J1939, it will
13 ECU Com Fail
send a stop signal.
When controller detects reverse power value (power is
Reverse Power
14 negative) is lower than the set value, and the reverse power
Shutdown
action select “shutdown”, it will send a stop alarm signal.
6.4TRIP ALARM
When controller detects stop alarm, it will break close generator signal quickly, but genset not
stop.
Trip and not stop alarm as following,
No. Type Description
When controller detects the value is higher than the set value,
1 Over Current
and the action select “trip”, it will send trip signal.
When controller detects reverse power value (power is
2 Reverse Power negative) is lower than the set value, and the action select
“trip”, it will send a trip signal.
When controller detects the over power value (power is
3 Over Power positive) is higher than the set value, and the action select
“trip”, it will send a trip signal.
When digital input port is set as “trip”, and the action is active,
4 Digital Input Ports
it will send a trip signal.
7 WIRINGS CONNECTION
Timer Setting
Time from mains abnormal or remote
1 Start Delay (0~3600)s 1
start signal is active to start gen-set.
Time from mains normal or remote
2 Stop Delay (0~3600)s 1
start signal is inactive to gen-set stop.
Preheat Time of pre-powering heat plug before
3 (0~3600)s 0
Delay starter is powered up.
Cranking
4 (3~60)s 8 Time of starter power up
Time
Crank Rest The waiting time before second power
5 (3~60)s 10
Time up when engine start fail.
Alarms for low oil pressure, high
Safety On temperature, under speed, under
6 (0~3600)s 10
Delay frequency/voltage, charge fail are
inactive.
Start Idle Idle running time of genset when
7 (0~3600)s 0
Time starting.
Warming Up Warming time between genset switch
8 (0~3600)s 10
Time on and high speed running.
Radiating time before genset stop,
9 Cooling Time (0~3600)s 10
after it unloads.
Stop Idle
10 (0~3600)s 0 Idle running time when genset stop.
Time
ETS
Stop electromagnet‟s power on time
11 Solenoid (0~3600)s 20
when genset is stopping.
Hold
Time between over of genset idle
delay and stopped when “ETS time” is
Fail to Stop set as 0;
12 (0~3600)s 0
Delay Time between over of ETS hold delay
and stopped when “ETS Hold output
time” is not 0.
After Stop Time between genset stopped and
13 (0~3600)s 0
Time standby
Engine Setting
Default: Conventional genset (not
J1939)
1 Engine Type (0~39) 0
When connected to J1939 engine,
choose the corresponding type.
Flywheel Tooth number of the engine, for
2 (10~300) 118
Teeth judging of starter separation
Reverse 0: Disable
6 (0~1) 0
Power 1: Enable.
Switch Setting
Interval time from mains switch off to
Transfer
1 (0~7200)s 5 generator switch on; or from generator
Time
switch off to mains switch on.
Pulse width of mains/generator switch
2 Close Time (0~20.0)s 5.0 on. When it is 0, means output
constantly.
3 Open Time (0~20.0)s 3.0 Pulse width of mains/generator switch
Defined Period output is composed by 2 parts, period output S1 and condition output S2.
18 Auto Mode Invalid Auto mode. key and simulate auto key
input does not work.
19 Reserved
20 Reserved
All shutdown alarms are prohibited except
21 Inhibit Alarm Stop emergence stop.(Means battle mode or override
mode)
22 Aux Instrument Mode All outputs are prohibited in this mode.
23 Reserved
Controller will set maintenance time and date as
24 Reset Maintenance
default when input is active.
25 Reserved
Connected sensor digital input.
26 Aux. High Temp
8.4SELECTION OF SENSORS
Form4
No. Content Description Remark
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
Defined resistance‟s
Temperature 5 VOLVO-EC
1 range is 0~6KΩ,
Sensor 6 DATCON
default is SGX sensor.
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS Defined resistance‟s
2 Pressure Sensor 5 VOLVO-EC range is 0~6KΩ,
6 DATCON 10Bar default is SGX sensor.
7 SGX
8 SGD
9 SGH
10~15 Reserved
9 PARAMETERS SETTING
In HGM9x10 series controller, there are no items of mains in setting and also no mains items in
configurable ports of input/output.
CAUTION: Please change the controller parameters when generator is in standby mode
only (e. g. Start conditions selection, configurable input, configurable output, various delay),
otherwise, alarming to stop and other abnormal conditions may happen.
NOTE: Maximum set value must over minimum set value in case that the condition of too
high as well as too low will happen.
NOTE: When setting the warning alarm, please set the correct return value; otherwise,
maybe there is abnormal alarm. When setting the maximum value, the return value must less
than setting; When setting the minimum value, the return value must over setting.
NOTE: Please set the generator frequency value as low as possible when cranking, in order
to make the starter be separated quickly as soon as crank disconnect.
NOTE: Configurable input could not be set as same items; otherwise, there are abnormal
functions. However, the configurable output can be set as same items.
10 SENSORS SETTING
1. When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if select the SGD (120°C resistor type), the temperature sensor curve
is SGD curve.
2. When there is difference between standard sensor curves and using sensor, user can adjust
it in “curve type”.
3. When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4. If select sensor type as “None”, sensor curve is not working.
5. If corresponding sensor has alarm switch only, user must set this sensor as “None”,
otherwise, maybe there is shutdown or warning.
6. The headmost or backmost values in the vertical coordinates can be set as same as below,
11 COMMISSIONING
12 TYPICAL APPLICATION
13INSTALLATION
Controller is panel built-in design; it is fixed by clips when installation. The controller‟s overall
dimensions and cutout dimensions for panel, please refers to as following,
WARNING! When there is load current, transformer‟s secondary side prohibit open circuit.
15.1CUMMINS ISB/ISBE
Terminals of
Connector B Remark
controller
Fuel relay output 39
Start relay output - Connect with starter coil directly.
Expand 30A relay,
Auxiliary output battery voltage of ECU power
port 1 01,07,12,13 is Set configurable output 1 as “ECU power”.
supplied by relay
Terminals of
9 pins connector Remark
controller
CAN communication shielding line(connect with
CAN GND SAE J1939 shield
ECU terminal only)
Impedance 120Ω connecting line is
CAN(H) SAE J1939 signal
recommended.
Impedance 120Ω connecting line is
CAN(L) SAE J1939 return
recommended.
Engine type: Cummins ISB
15.2CUMMINS QSL9
It is suitable for CM850 engine control module.
Terminals of
50 pins connector Remark
controller
Fuel relay output 39
Start relay output - Connect to starter coil directly.
Terminals of
9 pins connector Remark
controller
CAN GND SAE J1939 CAN communication shielding line(connect with
HGM9200/9300/9400 Series Gen-set Controller Vision 1.2 2013-01-14 Page 56 of 65
HGM9200/9300/9400 Series Gen-set Controller
shield-E ECU terminal only)
SAE J1939 Impedance 120Ω connecting line is
CAN(H)
signal-C recommended.
SAE J1939 Impedance 120Ω connecting line is
CAN(L)
return-D recommended.
Engine type: Cummins-CM850
15.4CUMMINS QSX15-CM570
It is suitable for CM570 engine control mode. Engine type is QSX15.
Terminals of
50 pins connector Remark
controller
Fuel relay output 38 Oil spout switch
Start relay output - Connect to starter coil directly.
Terminals of
9 pins connector Remark
controller
SAE J1939 CAN communication shielding line (connect
CAN GND
shield-E with ECU terminal only)
SAE J1939 Impedance 120Ω connecting line is
CAN(H)
signal-C recommended.
SAE J1939 Impedance 120Ω connecting line is
CAN(L)
return-D recommended.
Engine type: Cummins QSX15-CM570
15.6CUMMINS QSM11
Terminals of OEM connector Remark
controller
Fuel relay output 38
Start relay output - Connect with starter coil directly.
CAN communication shielding line(connect
CAN GND -
with controller‟s terminal only)
Impedance 120Ω connecting line is
CAN(H) 46
recommended.
Impedance 120Ω connecting line is
CAN(L) 37
recommended.
Engine type: J1939 common used
15.7CUMMINS QSZ13
Terminals of OEM connector of Remark
controller engine
Fuel relay output 45
Start relay output - Connect to starter coil directly.
Configurable 16&41 Set as idle speed control, normal open output.
output 1 Let 16 connect to 41during high speed running
15.9DEUTZ EMR2
Terminals of
F connector Remark
controller
Expand 30A relay,
battery voltage of 14
Fuel relay output
is supplied by relay.
Fuse is 16A.
Start relay output - Connect to starter coil directly.
- 1 Connect to battery negative pole.
CAN communication shielding line(connect in
CAN GND -
ECU this terminal only)
Impedance 120Ω connecting line is
CAN(H) 12
recommended.
CAN(L) 13 Impedance 120Ω connecting line is
15.10JOHN DEERE
Terminals of 21 pins connector Remark
controller
Fuel relay output G,J
Start relay output D
CAN communication shielding line(connect in
CAN GND -
ECU this terminal only)
Impedance 120Ω connecting line is
CAN(H) V
recommended.
Impedance 120Ω connecting line is
CAN(L) U
recommended.
Engine type: John Deere
15.11MTU MDEC
It is suitable for MTU engines, 2000 series and 4000series.
Terminals of X1 connector Remark
controller
Fuel relay output BE1
Start relay output BE9
CAN communication shielding line(connect
CAN GND E
with ECU terminal only)
Impedance 120Ω connecting line is
CAN(H) G
recommended.
Impedance 120Ω connecting line is
CAN(L) F
recommended.
Engine type: MTU-MDEC-303
15.12MTU ADEC
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of ADEC (X1port) Remark
controller
Fuel relay output X1 10 X1 Terminal 9 Connected to negative of
battery
Start relay output X1 34 X1 Terminal 33 Connected to negative of
battery
15.14PERKINGS
It is suitable for ADEM3/ ADEM4 engine control module. Engine type is 2306, 2506, 1106, and
2806.
Terminals of
Connector Remark
controller
Fuel relay output 1,10,15,33,34
Start relay output - Connect to starter coil directly.
CAN communication shielding line(connect in
CAN GND -
ECU this terminal only)
Impedance 120Ω connecting line is
CAN(H) 31
recommended.
Impedance 120Ω connecting line is
CAN(L) 32
recommended.
Engine type: Perkins
15.16VOLVO EDC3
Suitable engine control mode is TAD1240, TAD1241, and TAD1242.
Terminals of “Stand alone”
Remark
controller connector
Fuel relay output H
Start relay output E
Configurable P ECU power
output 1 Set configurable output 1as "ECU power"
15.17VOLVO EDC4
Suitable engine types are TD520, TAD520 (optional), TD720, TAD720 (optional), TAD721,
15.18VOLVO-EMS2
Volvo Engine types are TAD734, TAD940, TAD941, TAD1640, TAD1641, and TAD1642.
Terminals of
Engine‟s CAN port Remark
controller
Configurable 6 ECU stop
output 1 Set configurable output 1as “ECU stop”.
Configurable 5 ECU power
output 2 Set configurable output 1as “ECU power”.
3 Negative power
4 Positive power
CAN communication shielding line(connect
CAN GND -
to controller‟s this terminal only)
CAN(H) 1(Hi) Impedance 120Ω connecting line is
recommended.
CAN(L) 2(Lo) Impedance 120Ω connecting line is
recommended.
Engine type: Volvo-EMS2
NOTE: When this engine type is selected, preheating time should be set to at least 3
seconds.
15.19YUCHAI
Suit for Yuchai common rail electrically controlled engine.
Terminals of 42 pins connector Remark
controller of engine
Fuel relay output 1.40 Connect to ignition switch of engine.
Start relay output - Connect to starter coil directly.
CAN GND - CAN communication shielding line(connect with
HGM9200/9300/9400 Series Gen-set Controller Vision 1.2 2013-01-14 Page 63 of 65
HGM9200/9300/9400 Series Gen-set Controller
controller‟s this terminal only)
CAN(H) 1.35 Impedance 120Ω connecting line is
recommended.
CAN(L) 1.34 Impedance 120Ω connecting line is
recommended.
15.20WEICHAI
Suit for Weichai common rail electrically controlled engine.
Terminals of Connector Remark
controller
Fuel relay output 1.40 Connect to ignition switch of engine.
Start relay output 1.61
CAN GND - CAN communication shielding line(connect with
controller‟s this terminal only)
CAN(H) 1.35 Impedance 120Ω connecting line is
recommended.
CAN(L) 1.34 Impedance 120Ω connecting line is
recommended.
Engine type: GTSC1
NOTE: If there is any question of connection between controller and ECU communication,
please feel free to contact Smartgen service.
16FAULT FINDING