Professional Documents
Culture Documents
HEAT
Installation Methods HEAT
LOAD
’AMOT’
THERMOSTAT
REMOVAL
There are several ways of installing Amot thermostatic
valves, but the two most common applications are B C
A
“mixing” and “diverting”. When diverting the fluid,
temperature into the valve is being controlled. When
mixing the fluid, temperature from the valve is
controlled. In mixing mode the valve may run at 1-2˚C PUMP
(1.8-3.6˚F) higher than the normal set temperature.
All Amot internally sensed valves have the same port
identification, ie, A,B and C.
Flange Gaskets – Use full face gaskets.
Salt Water – For direct sea water cooled applications, A system in which the valves have been properly
bronze valves with plated elements should be used. selected for the anticipated flows should operate very
closely to the valve’s nominal temperature rating.
Venting – If the valve is mounted at the high point of
the system, then care must be taken to ensure that the Water cooling systems will usually operate at or slightly
system is properly vented to prevent trapping air at the below the nominal temperature. Lubricating oils and
elements. A leak hole within the unit may be necessary. most other higher viscosity fluids may operate at or
slightly above the nominal temperature.
Environmental Conditions – Ensure protection
against frost and direct sunlight. In any system where the indicated temperatures are
more than 3˚C (5˚F) from the nominal temperature, then
Overtemperature – Ensure maximum continuous an effort should be made to locate the cause.
temperatures of element assemblies are not exceeded;
this can increase risk of premature failures. Any system operating at an indicated
6˚C (10˚F) or more from the nominal anticipated
Pipe Alignment – Ensure good alignment of pipes temperatures is probably malfunctioning and the cause
prior to tightening of all connections. No pipe strain or should be located and rectified immediately. (See
loading should be applied to the valve body. trouble-shooting guide over page for possible causes.)
13
TROUBLE-SHOOTING
In the event that the cooling system does not operate close to the desired temperature, the following guide may help to identify
or locate the problem.
System temperature too cold System temperature too hot
1 Insufficient heat transferred to coolant to maintain 1 Cooling capacity of system inadequate.
temperature. 2 Thermostatic valve too small for flow rate causing high
2 Wrong nominal element temperature selected. pressure drops and possible cavitation problems.
3 Thermostatic valve greatly oversized or cooling capacity of 3 Valve installed backwards, reducing flow to cooler as
system much greater than required. temperature increases.
4 Thermostatic valve installed backwards, thus sending water 4 By-pass will not close due to worn or pitted seats, sliding
to cooler at low temperatures. valve, seals, etc.
5 Worn or leaking O-rings allowing leakage to cooler. 5 Elements may have suffered sufficient over-temperature
6 Excessive pressure drops across the valve. to prevent full movement, thus preventing full cooling.
7 Foreign matter preventing closure of elements. 6 Solids building up on element sliding valve preventing
8 Bi-metallic type thermometers will indicate low if calibrated correct operation.
in oil. 7 Foreign matter stuck between sliding valve and seat.
HYSTERESIS
The gap found between the upstroke
(SEE INDIVIDUAL DATA SHEET)
HYSTERESIS
FULL OPEN TEMP.
CURVE
The curve illustrates the movement of
MIN.
the element assembly in relation to
CRACK OPEN
WORKING
TEMP.
HEIGHT temperature.
WORKING
TEMP. RANGE
10˚C
FULL TEMP. RANGE
TYPICALLY 15˚C
PRESSURE CONVERSION
PSI Bar KG/cm2 Atm KPa In. water In. merc
1 PSI = ***** 0.069 0.070 0.068 6.89 27.6 2.04
1 Bar = 14.50 ***** 1.020 0.987 100.00 401.4 29.5
1 KG/cm2 = 14.22 0.981 ***** 0.968 98.0 393.6 28.9
1 Atm = 14.70 1.013 1.033 ***** 101.3 406.7 29.9
1 Kpa = 0.145 0.010 0.0102 0.0098 ***** 4.01 0.295
1 In. water = 0.036 0.0025 0.0025 0.0025 0.25 ***** 0.07
1 In. merc = 0.490 0.034 0.035 0.033 3.39 13.60 *****
14
FLOWRATE CONVERSION
m3/hr Litre/min IMP Gallon/min US Gallon/min
6B
227 (1000) [3788]
5H 205 (900) [3410]
5B 182 (800) [3030]
159 (700) [2652]
4H
136 (600) [2273]
4B
114 (500) [1893]
91 (400) [1515]
33B
68 (300) [1137]
3B
21/2B
45 (200) [758]
2B
11/2B 23 (100) [378]
21 (90) [342]
18 (80) [303] FLOW
11/2E
16 (70) [265]
14 (60) [227]
11 (50) [190]
11/4CCM
9 (40) [152]
7 (30) [113]
11/4-11/2C
1C
3/4C
1/2C
5 (20) [77]
3/4J
* SELECT VALVE TO GIVE PRESSURE DROP OF 0.14-0.48 Bar (2-7 PSI) AND REFER TO SPECIFIC VALVE MODEL PAGE.
15
PRESSURE GAUGE
INSTALLATION,
OPERATION AND
MAINTENANCE
a Halliburton company
Figure 6
Trip and Reset Adjustment
The design and construction of Bulletin 836 Styles A and C controls provide a typical
repeat accuracy of + 0.5% or better. Repeat accuracy is based on percent of maximum
range, evaluated from test data and calculated using the formula per ICS 2-225 standards.
Repeat accuracy and mechanical life of bellows type controls is graphically illustrated in
Figure 7. For general applications, controls selected where the contacts operate between
30…80% of the operating range and where the maximum line and surge pressures do not
exceed the specified values will provide excellent life and repeat accuracy. For more
specific applications, it is important to note that the controls are designed to operate
below or above these values. However, there may be a small trade-off between the
ii
CONTENTS
2.0 Temperature
2.1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.2 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.3 Steam service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.4 Hot lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.5 Cold service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.6 Diaphragm seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2.7 Autoclaving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.0 Installation
3.1 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.2 Gauge reuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.3 Tightening of gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.4 Process isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.5 Surface mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.6 Flush mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.0 Operation
4.1 Frequency of inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.2 In-service inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.3 When to check accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.4 When to recalibrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.5 Other considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.6 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
iii
CONTENTS
Page
7.0 Diaphragm Seals
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
7.5 Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
9.0 Resources
9.1 Training Videos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.2 Pressure Instrument Testing Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.3 Tools & Tool Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
9.4 Sales Bulletins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
iv
sive to the process sensing element; (b) con-
1.0 SELECTION & APPLICATION tain heavy particulates (slurries) or (c) are
very viscous including those that harden at
Users should become familiar with ASME room temperature. Additionally, diaphragm
B40.1 (Gauges – Pressure Indicating Dial seals with flexible line assemblies should be
Type – Elastic Element) before specifying considered for applications involving hot lines
pressure measuring instruments. That docu- (see page 2) or significant levels of vibration
ment – containing valuable information and/or pulsation.
regarding gauge construction, accuracy, safe-
ty, selection and testing – may be ordered 1.4 Oxidizing media – It is extremely impor-
from The American Society of Mechanical tant that when specifying gauges for use on
Engineers, 345 East 47th Street, New York, oxidizing media the appropriate gauge clean-
N.Y. 10017. liness level per ASME B40.1 be included in
the gauge specification. Gauges containing
WARNING: To prevent misapplication, pres- significant amounts of hydrocarbon contami-
sure gauges should be selected considering nation inside the pressure system will often
media and ambient operating conditions. rupture explosively in such service.
Improper application can be detrimental to
the gauge, causing failure and possible per- 1.5 Pulsation/Vibration – Severe service
sonal injury, property damage or death. The applications are characterized by the pres-
information contained in this manual is ence of significant levels of pressure pulsation
offered as a guide in making the proper selec- and/or vibration. Gauges should be protected
tion of a pressure gauge. Additional informa- from severe pressure pulsation by the inclu-
tion is available from Dresser Instrument sion of a dampener such as a throttle
Division. plug/screw or porous metal snubber. If the
pulsation is extreme, a liquid filled gauge,
The following is a highlight of some of the with dampener should be used. A liquid filled
more important considerations: gauge will also last significantly longer than a
1.1 Range – The range of the instrument comparable dry gauge when vibration is pre-
should be approximately twice the maximum sent. If the vibration levels are extreme the
operating pressure. Too low a range may only solution may be to remotely mount the
result in (a) low fatigue life of the elastic ele- gauge away from the source of vibration. In
ment due to high operating stress and (b) sus- that case flexible tubing may be used to con-
ceptibility to overpressure set due to pressure nect the gauge to the pressure source.
transients that exceed the normal operating 1.6 Gauge fills. – Once it has been determined
pressure. Too high a range may yield insuffi- that a liquid filled gauge is in order, the next
cient resolution for the application. step is selecting the type of fill. Glycerin sat-
1.2 Temperature – Refer to page 2 of this isfies most applications. While being the least
manual for important information concerning expensive fill, its usable temperature range is
temperature related limitations of pressure 0/250°F. Silicone filled gauges have a broad-
gauges, both dry and liquid filled. er service range: –40/250°F. Oxidizing media
require the use of a compatible gauge fill such
1.3 Media – The material of the process sens- as Halocarbon, with a service range of
ing element must be compatible with the –50/250°F .
process media from a corrosion point of view.
Consult the Corrosion Guide available on the 1.7 Mounting – Users should predetermine
website: www.dresserinstruments.com or how the gauge will be mounted in service:
Dresser Instrument Division. Use of a stem (pipe), wall (surface) or panel (flush).
diaphragm seal with the gauge is recom- Ashcroft wall or panel mounting kits should
mended for process media that (a) are corro- be ordered with the gauge.
1
1/2˝ piping (or smaller diameter flexible tub-
2.0 TEMPERATURE ing) between the hot line and the gauge. The
slow rate of heat transfer through the added
2.1 Ratings – To ensure long life and accurate
pipe wall and dead-ended process fluid will
readings, pressure gauges should not be
generally protect the gauge from damage.
exposed to process or ambient temperatures
over 150°F. This is especially true of gauges 2.5 Cold Service – The minimum recom-
with liquid filled cases due to thermal expan- mended operating temperature for all gauges
sion of the case fill fluid. Long term exposure is –50°F. A hermetically sealed gauge case is
to temperatures in excess of 150°F may cause recommended to minimize condensate freez-
discoloration of dials and fill fluids, as well as ing on the movement, thus hindering its
hardening of elastomeric case seals and possi- action. Gauges filled with silicone oil will pro-
ble fill leakage. Soft soldered, silver brazed vide maximum resistance to the effects of
and welded pressure joints are rated at 250°F operating in freezing conditions. While glyc-
maximum, 450°F maximum and 750°F maxi- erin filled gauges can be safely stored at tem-
mum respectively. Plastic gauge cases, includ- peratures down to –50°F , their operation is
ing phenolic, should not be exposed to tem- impeded at temperatures below +20°F due to
peratures in excess of 250°F. Maximum rec- the marked increase in the viscosity of the
ommended service temperatures for gauge glycerin.
windows are as follows: 350°F for plain glass;
300°F for polysulfone; 270°F for polycarbon- 2.6 Diaphragm seals – Diaphragm seals
ate; 200°F for laminated safety glass; and (isolators) with filled, flexible line assemblies
180°F for acrylic. are another good solution to the problem of
hot liquid and gas lines. Due to the small
2.2 Accuracy – Heat and cold affect accuracy diameter of the flexible line (capillary) a five
of indication. A general rule of thumb for dry foot line length will usually assure that the
gauges is 0.5% of full scale change for every temperature of the gauge connection does not
40°F change from 75°F. Double that al- exceed 150°F. Even one foot of capillary often
lowance for gauges with hermetically sealed will prevent the high temperature of the seal
or liquid filled cases, except for Duragauge® from reaching the gauge. This solution is also
gauges where no extra allowance is required superior to a siphon on steam service where
due to the elastomeric, compensating back. the water filled siphon might freeze. Refer to
Above 250°F there may exist very significant sales bulletin DS-1 for a listing of service tem-
errors in indication. perature ranges by type of fill.
2.3 Steam service – In order to prevent live 2.7 Autoclaving – Sanitary gauges with
steam from entering the bourdon tube, a clamp type connections are frequently steam
siphon filled with water should be installed sterilized in an autoclave. Gauges equipped
between the gauge and the process line. with polysulfone windows will withstand
Siphons can be supplied with ratings up to more autoclave cycles than those equipped
4,000 psi at 1,000°F. If freezing of the conden- with polycarbonate windows. Gauges
sate in the loop of the siphon is a possibility, a equipped with plain glass or laminated safety
diaphragm seal should be used to isolate the glass should not be autoclaved. Gauge
gauge from the process steam. Siphons should cases should be vented to atmosphere (remov-
also be used whenever condensing, hot vapors ing the rubber fill/safety plug if necessary)
(not just steam) are present. before autoclaving to prevent the plastic
window from cracking or excessively distort-
2.4 Hot lines – When a gauge is installed on a
ing. If the gauge is liquid filled, the fill should
process line containing hot liquid or gas, one
also be drained from the case before autoclav-
solution is to simply include an extra foot
ing.
(200°F process) to 4 feet (600°F process) of
2
pressure relieving back and the mounting
3.0 INSTALLATION surface.
3.1 Location – Whenever possible, gauges 3.6 Flush mounting – Also known as panel
should be located to minimize the effects of mounting. The applicable panel mounting
vibration, extreme ambient temperatures and cutout dimensions can be found in Ashcroft
moisture. Dry locations away from very high sales bulletins – see item 9.4 RESOURCES
thermal sources (ovens, boilers etc.) are pre- on page 14 of this manual. These dimensions
ferred. If the mechanical vibration level is are also on Ashcroft® gauge general dimension
extreme, the gauge should be remotely locat- drawings which can be obtained from the
ed (usually on a wall) and connected to the Customer Service department in Stratford,
pressure source via flexible tubing. Connecticut.
3.2 Gauge reuse – ASME B40.1 recommends
that gauges not be moved indiscriminately 4.0 OPERATION
from one application to another. Whereas the
cumulative number of pressure cycles on an 4.1 Frequency of inspection – This is quite
in-service or previously used gauge is gener- subjective and depends upon the severity of
ally unknown, it is generally safer to install a the service and how critical the accuracy of
new gauge whenever and wherever possible. the indicated pressure is. For example, a
This will also minimize the possibility of a monthly inspection frequency may be in order
reaction with previous media. for critical, severe service applications.
3.3 Tightening of gauge – Torque should Annual in-spections, or even less frequent
never be applied to the gauge case. Instead, schedules, are often employed in non-critical
an open end or adjustable wrench should applications.
always be used on the wrench flats of the 4.2 In-service inspection – If the accuracy of
gauge socket to tighten the gauge into the fit- the gauge cannot be checked in place, the user
ting or pipe. NPT threads require the use of a can at least look for (a) erratic or random
suitable thread sealant, such as pipe dope or pointer motion; (b) readings that are suspect
teflon tape, and must be tightened very – especially indications of pressure when the
securely to ensure a leak tight seal. user believes the true pressure is 0 psig.
CAUTION: Torque applied to a diaphragm 4.3 When to check accuracy – Obviously any
seal or its attached gauge, that tends to suspicious behavior of the gauge pointer war-
loosen one relative to the other, can cause loss rants a full accuracy check be performed.
of fill and subsequent inaccurate readings. Even if the gauge is not showing any symp-
Always apply torque only to the wrench flats toms of abnormal performance, the user may
on the lower seal housing when installing want to establish a frequency of bench type
filled, diaphragm seal assemblies or removing inspection.
same from process lines.
4.4 When to recalibrate – This depends on the
3.4 Process isolation – A shut-off valve criticality of the application. If the accuracy of
should be installed between the gauge and a 3-2-3% commercial type gauge is only 0.5%
the process in order to be able to isolate the beyond specification, the user must decide
gauge for inspection or replacement without whether it’s worth the time and expense to
shutting down the process. bring the gauge back into specification.
Conversely if the accuracy of a 0.25% test
3.5 Surface mounting – Also known as wall gauge is found to be 0.1% out of specification
mounting. Gauges should be kept free of pip- then obviously the gauge should be recalibrat-
ing strains. The gauge case mounting feet, if ed.
applicable, will ensure clearance between the
3
4.5 Other considerations – These include (a) f. Gauges showing significant friction error
bent or unattached pointers due to extreme and/or wear of the movement and linkage
pressure pulsation; (b) broken windows which (assuming the movement cannot be
should be replaced to keep dirt out of the replaced).
internals; (c) leakage of gauge fill; (d) case
damage – dents and/or cracks; (e) any signs of g. Gauges having damaged sockets, especial-
service media leakage through the gauge ly damaged threads.
including its connection; (f) discoloration of h. Liquid filled gauges showing loss of case
gauge fill that impedes readability. fill.
4.6 Spare parts – As a general rule it is rec- NOTE: ASME B40.1 does not recommend
ommended that the user maintain in his moving gauges from one application to anoth-
parts inventory one complete Ashcroft instru- er. This policy is prudent in that it encourages
ment for every ten (or fraction thereof) of that the user to procure a new gauge, properly tai-
instrument type in service. lored by specification, to each application that
arises.
5
TYPICAL CALIBRATION CHART
INDICATED VALUE (PSI)
True Value – Increasing – Increasing – Decreasing – Decreasing –
PSI Without RAP With RAP Without RAP With RAP
0 –.4 0 –.4 0
40 +.8 +1.0 +1.4 +1.1
80 +.4 +.5 +1.2 +1.0
120 –.4 –1.0 +.8 +.6
160 –.8 –.5 +.6 +.4
200 +.4 +.8 +.4 +.4
1.0
Fig. 1
0.5
Error (% of Full Scale)
0.0
–1.0
0 20 40 60 80 100
% of Range
6
factors of repeat accuracy and mechanical life.
Figure 7
Repeat Accuracy Versus Mechanical Life Graph
Standard Contacts
Non-Inductive Ratings
5 A, 240V
3 A, 600V
Single-Pole Double-Throw
Note: NEMA does not rate contacts to switch low voltage and current.
6.1 Calibration – Rotary Movement Gauges movement should be rotated counter clock-
– Inspect gauge for accuracy. Many times wise. Rotating the movement one degree
gauges are simply “off zero” and a simple will change this error by approximately
pointer adjustment using the micrometer 0.25%. Rotating the movement often
pointer is adequate. If inspection shows the affects span and it should be subsequently
gauge warrants recalibration to correct span rechecked and readjusted if necessary
and/or linearity errors, proceed as follows: according to step 6.1e and 6.1f.
a. Remove ring, window and, if solid front h. While recalibrating the gauge, the friction
case, the rear closure assembly. error – difference in readings taken with
and without rap – should be noted. This
b. Pressurize the gauge once to full scale and error should not exceed the basic accuracy
back to zero. of the gauge. If the friction error is exces-
c. Refer to Figure 2 on page 8 for a view of a sive, the movement should be replaced.
typical Ashcroft system assembly with One possible cause of excessive friction is
component parts identified. improper adjustment of the hairspring.
The hairspring torque,or tension, must be
d. For solid front gauges, adjust the microm- adequate without being excessive. The
eter pointer so that it rests at the true zero hairspring should also be level, unwind
position. For open front gauges the pointer evenly (no turns rubbing) and it should
and dial must also be disassembled and never tangle.
the pointer should then be lightly pressed
onto the pinion at the 9:00 o’clock position. NOTES:
1 For operation of test gauge external zero
e. Apply full scale pressure and note the reset, refer to Figure 3 on page 8.
magnitude of the span error. With open 2 For test gauge calibration procedure,
front gauges, ideal span (270 degrees) will refer to Figure 4 on page 9.
exist when at full scale pressure the point-
er rests exactly at the 6:00 o’clock position. 6.2 Calibration – 1009 Duralife® Gauge –
Inspect gauge for accuracy. Many times
f. If the span has shifted significantly (span gauges are simply “off zero” and a simple
error greater than 10%), the gauge should pointer adjustment using the adjustable
be replaced because there may be some pointer is adequate. If the inspection shows
partial corrosion inside the bourdon tube that the gauge warrants recalibration to cor-
which could lead to ultimate failure. If the rect span and/or linearity errors, proceed as
span error exceeds 0.25%, loosen the lower follows:
link screw and move the lower end of the
link toward the movement to increase Remove ring, window, gasket and pointer
span or away to decrease span. An adjust- using Ashcroft tool kits 1205T and 1206T.
ment of 0.004 inch will change the span by Positive Pressure Ranges –
approximately 1%. This is a repetitive pro-
cedure which often requires more than one a. Remove dial and lightly press pointer onto
adjustment of the link position and the pinion at 9:00 o’clock position.
subsequent rechecking of the errors at zero
b. Apply full scale pressure and rotate span
and full scale pressure.
block as shown in Figure 5a on page 11
g. Apply midscale pressure and note error in until pointer rests at 6:00 o’clock position.
reading. Even though the gauge is accu-
c. Fully exhaust pressure and check that
rate at zero and full scale, it may be inac-
pointer still is at 9:00 o’clock position. If
curate at the midpoint. This is called lin-
not repeat steps 1 and 2 until span is
earity error and is minimized by rotating
correct.
the movement. If the error is positive, the (Continued on page 10)
7
Fig. 2 ASHCROFT SYSTEM ASSEMBLY
TIP HAIRSPRING
LINK PINION
ROTARY MOVEMENT
BACKPLATE
SOCKET
B RING
A
9
d. Remove pointer and reassemble dial and h. Repeat steps 4 through 8 until span is
dial screws (finger tight). correct.
e. Lightly press pointer onto pinion. i. Remove the pointer.
f. Check accuracy at full scale. If error j. With 25 inches of Hg vacuum applied,
exceeds 1% return to step 1, otherwise pro- reassemble dial, dial screws (finger tight)
ceed. and pointer.
g. Check accuracy at midscale. If error k. Apply 15 inches of Hg vacuum and note
exceeds 1% slide dial left or right to com- accuracy of indication. If required, slide
pensate. dial left or right to reduce error to
1% maximum.
h. Continue at * below.
l. Continue at * below.
Vacuum range –
a. Using a pencil, refer to dial and mark the
* Now complete calibration of the gauge as
follows:
0 and 25 inch of Hg positions on the case
flange. a. Firmly tighten dial screws.
b. Remove the dial. b. Firmly tap pointer onto pinion, using brass
back-up tool from Ashcroft kit 1205T if
c. Apply 25 inches of Hg vacuum. gauge has rear blow-out plug. If gauge has
d. Lightly press pointer onto pinion carefully top fill hole no back-up is required.
aligning it with the 25 inch of Hg vacuum c. Recheck accuracy at zero, midscale and
mark on case flange. full scale points (Figures 5a & 5b on
e. Release vacuum fully. page 11).
f. Note agreement of pointer to zero mark on d. Reassemble window, gasket and ring.
case flange.
g. If span is high or low, turn span block as
shown in Figure 5b on page 11.
10
1009 DURALIFE® PRESSURE GAUGE CALIBRATION
PRESSURE VACUUM
25
Span Block
7/64 Open End Wrench
0
Decrease Increase Increase
Decrease
Mid-scale mark
15
25
Fig. 5a
Fig. 5a Fig. 5b
Fig. 5b
11
ment/diaphragm seal assembly be properly
7.0 DIAPHRAGM SEALS filled prior to being placed in service. Ashcroft
diaphragm seal assemblies should only be
7.1 General – A diaphragm seal (isolator) is a
filled by a seal assembler certified by Dresser
device which is attached to the inlet connec-
Industries. Refer to section 3.3 for a caution-
tion of a pressure instrument to isolate its
ary note about not applying torque on either
measuring element from the process media.
the instrument or seal relative to the other.
The space between the diaphragm and the
instrument’s pressure sensing element is 7.3 Operation – All Ashcroft diaphragm seals,
solidly filled with a suitable liquid. with the exception of Type 310 mini-seals, are
Displacement of the liquid fill in the pressure continuous duty. Should the pressure instru-
element, through movement of the ment fail, or be removed accidentally or delib-
diaphragm, transmits process pressure erately, the diaphragm will seat against a
changes directly to a gauge, switch or any matching surface preventing damage to the
other pressure instrument. When diaphragm diaphragm or leakage of the process fluid.
seals are used with pressure gauges, an addi-
tional 0.5% tolerance must be added to the 7.4 Maintenance – Clamp type diaphragm
gauge accuracy because of the diaphragm seals – Types 100, 200 and 300 – allow for
spring rate. replacement of the diaphragm or diaphragm
capsule, if that ever becomes necessary. The
Used in a variety of process applications Type 200 top housing must also be replaced
where corrosives, slurries or viscous fluids with the diaphragm. With all three types the
may be encountered, the diaphragm seal clamping arrangement allows field disassem-
affords protection to the instrument where: bly to permit cleaning of the seal interior.
• The process fluid being measured would 7.5 Failures – Diaphragm failures are gener-
normally clog the pressure element. ally caused by either corrosion, high tempera-
tures or fill leakage. Process media build-up
• Pressure element materials capable of
on the process side of the diaphragm can also
withstanding corrosive effects of certain
require seal cleaning or replacement. Consult
fluids are not available.
Customer Service, Stratford CT for advice on
• The process fluid might freeze due to seal failures and/or replacement. Refer also to
changes in ambient temperature and dam- Product Information page ASH/PI-14C con-
age the element. taining drawing 96A121 Corrosion Data
Guide.
7.2 Installation – Refer to sales bulletin DS-1
for information regarding (a) seal configura- WARNING: All seal components should be
tions; (b) filling fluids; (c) temperature range selected considering process and ambient
of filling fluids; (d) diaphragm material pres- operating conditions to prevent misapplica-
sure and temperature limits; (e) bottom hous- tion. Improper application could result in fail-
ing material pressure and temperature lim- ure, possible personal injury, property
its; (f) pressure rating of seal assembly; (g) damage or death.
accuracy/temperature errors of seal assembly;
(h) diaphragm seal displacement. The volu- 8.0 DAMPENING DEVICES
metric displacement of the diaphragm must
at least equal the volumetric displacement of 8.1 General – Some type of dampening device
the measuring element in the pressure should be used whenever the pressure gauge
instrument to which the seal is to be may be exposed to repetitive pressure fluctu-
attached. ations that are fairly rapid, high in magni-
It is imperative that the pressure instru- tude and especially when transitory pressure
spikes exceeding the gauge range are present
12
(as with starting and stopping action of valves greater the compression of the felts the
and pumps). A restricted orifice of some kind greater the degree of dampening.
is employed through which pressure fluctua-
tions must pass before they reach the bourdon 8.4 Ashcroft Pulsation Dampener – Type
tube. The dampener reduces the magnitude of 1106 Ashcroft Pulsation Dampener is a mov-
the pressure pulse thus extending the life of ing pin type in which the restricted orifice is
the bourdon tube and movement. This reduc- the clearance between the pin and any one of
tion of the pressure pulsation as “seen” by the five preselected hole diameters. Unlike a sim-
pressure gauge is generally evidenced by a ple throttle screw/plug, this device has a self-
reduction in the pointer travel. If the orifice is cleaning action in that the pin moves up and
very small the pointer may indicate the aver- down under the influence of pressure fluc-
age service pressure, with little or no indica- tuations.
tion of the time varying component of the 8.5 Ashcroft Pressure Snubber – The heart
process pressure. of the Type 1112 pressure snubber is a thick
Commonly encountered media (e.g. – water porous metal filter disc. The disc is available
and hydraulic oil) often carry impurities in four standard porosity grades.
which can plug the orifice over time thus ren- 8.6 Campbell Micro-Bean® – Type 1110 Micro-
dering the gauge inoperative until the damp- Bean is a precision, stainless steel, needle
ener is cleaned or replaced. valve instantly adjustable to changing condi-
Highly viscous media and media that tend to tions of flow and viscosity. A very slight taper
periodically harden (e.g., asphalt) require a on the valve stem fits into tapered hole in the
diaphragm seal be fitted to the gauge. The body. The degree of dampening is easily
seal contains an internal orifice which damp- adjusted by turning the valve handle. A filter
ens the pressure fluctuation within the fill is built into the Micro-Bean to help prevent
fluid. plugging.
8.2 Throttle Screws & Plugs – These acces- 8.7 Ashcroft Needle Valves – Type 7001 thru
sories provide dampening for the least cost. 7004 steel needle valves provide varying
They have the advantage of fitting complete- degrees of dampening similar to the Campbell
ly within the gauge socket and come in three Micro-Bean but with a less precise and less
types: (a) a screwed-in type which permits costly adjustability. Like the Micro-Bean
easy removal for cleaning or replacement; (b) these devices, in the event of plugging, can
a pressed in, non-threaded design and (c) a easily be opened to allow the pressure fluid to
pressed in, threaded design which provides a clear away the obstruction.
highly restrictive, helical flow path. Not all 8.8 Chemiquip® Pressure Limiting Valves –
styles are available on all gauge types. Model PLV-255, PLV-2550, PLV-5460, PLV-
8.3 Ashcroft Gauge Saver – Type 1073 5500 and PLV-6430, available with and with-
Ashcroft Gauge Saver features an elastomer- out built-in snubbers, automatically “shut off”
ic bulb that fully isolates the process media at adjustable preset values of pressure to pro-
from the bourdon tube. In addition to provid- tect the gauge from damage to overpressure.
ing dampening of pressure pulses, the bour- They are especially useful on hydraulic sys-
don tube is protected from plugging and cor- tems wherein hydraulic transients (spikes)
rosion. The space between the bulb and bour- are common.
don tube is completely filled with glycerin.
Felt plugs located between the bulb and bour-
don tube are first compressed some amount to
restrict the flow of glycerin through an orifice
and thus provide a degree of dampening. The
13
Technical Data
Technical Terms
Adjustable Operating Range — Total span within which the contacts can be adjusted to
trip and reset.
Trip Setting — Higher pressure setting at which value the contacts transfer from their
normal state to a changed state.
Reset Setting — Lower pressure setting at which value the contacts return to their
normal state.
Minimum Differential — When the differential is set to the lowest pressure difference
between trip and reset.
Maximum Differential — When the differential is set to the widest pressure difference
between trip and reset.
Maximum Occasional Surge Pressure — Maximum surge pressure that can be applied
to the actuator. Surges or transients can occur during start-up and shut-down of a machine
or system. Expressed in milliseconds, complex electronic instrumentation is required to
measure the varying amplitude, frequency, and duration of this wave form. Extreme
surges that occur approximately 8 times in a 24-hour period are negligible.
Maximum Line Pressure — Maximum sustained pressure that can be applied to the
bellows without permanent damage. The control should not be cycled at this pressure.
• Reset Setting — Decreasing pressure setting when contacts return to their normal
state.
Vacuum (Negative Pressure) — Any pressure less than 0 psi, inches of mercury
vacuum. See Figure 2.
psi — Devices listed are in gauge pressure units which use atmospheric pressure as a
reference. Atmospheric pressure at sea level is approximately 14.7 psi or 30 in. Hg.
Operating Range Adjustment Screw — This screw is used to adjust the trip setting by
varying the force of the main spring.
Differential Adjustment Screw — This screw is used to adjust reset setting by varying
the force of the differential blade spring.
Pressure Media — There are many types of pressure media that are controlled.
Examples include air, water, hydraulic fluids and other types of gases and liquids. The
type of media and maximum system pressure will determine the type of actuator used for
the pressure control application. See page click here.
Figure 1
Graphics to illustrate Technical Terms
Figure 2
Positive Pressure or Vacuum
Bulletin 836 Styles A and C Pressure Controls are supplied with silver contacts. The
devices are designed to deliver high force snap action to the contacts. This provides
exceptional contact fidelity at 24V DC I/O card current level entry when the control is
protected in a suitable enclosure for the surrounding environment.
Special Controls
A large number of unlisted catalog modifications and complete devices are available for
specific and OEM applications.
Special controls and modification service is available to meet many applications unique
to the OEM market.
Consult factory for assistance with specific modified controls and accessories.
Temperature Range
The selection table below is an overview of the three types of Bulletin 836 Pressure
Controls Allen-Bradley offers. Each type of control is suitable for use on many types of
applications. Pressure ranges, pressure connections, enclosure types and the compatibility
of the actuator with different types of pressure media are given to assist in the selection of
which type of control to use.
Theory of Operation
Bulletin 836 Pressure Controls are designed to open or close electrical circuits in
response to changes in pneumatic (air or gas) or hydraulic (water or oil) pressure. Figure
3 is a simplified drawing of a pressure control. The system pressure is connected to the
control at the pressure connection. The system pressure is applied directly to the bellows.
As pressure rises, the bellows exerts force on the main spring. When the threshold force
of the main spring is overcome, it transfers the motion to the contact block causing the
contacts to actuate — this is referred to as the Trip Setting. As pressure decreases, the
main spring will retract, causing the secondary differential blade spring to activate and
return the contacts to their normal state - this is referred to as Reset Setting. Varying the
force of the main spring (by turning the operating range adjustment screw) determines
where the contacts will trip. Varying the force of the secondary differential blade spring
(by turning the differential adjustment screw) determines where the contacts will reset.
Figure 3
Basic Mechanical Structure
Applications for Control
Pressure controls can be used to either control or monitor a machine or process. Figure 4
shows a typical control application. Here, pressure is controlled within predetermined
high and low values. Figure 5 shows a typical monitoring application. Here, pressure is
monitored between a high and low value, signaling when a preset limit has been
exceeded.
Figure 4
Typical Control Application
Figure 5
Typical Monitoring Application
Control Settings
Allen-Bradley controls are designed for ease of setting to help minimize installation time.
Standard controls shipped from the factory are set at the maximum operating range and
minimum differential. By following this simple two-step process, the control can be set to
the specific requirements for each application. See Figure 6.
Corrosive liquids and gases compatible with Type 316 Stainless Steel.