You are on page 1of 6

Column1 Column2 Column3 Column4 Column5 Column6 Column7 Column1

TRANSFORMER #1 TRANSFORMER #2
Time #1 #2 #3 #4 #5 Time
kW kW kW kW kW TOT KW
5:00 7.95 1.71 7.35 8.37 2 27.38 5:00
5:15 9.09 2.19 7.35 9.16 1.96 29.75 5:15
5:30 7.7 1.78 7.53 8.19 2.06 27.26 5:30
5:45 8.75 4.03 7.25 8.93 1.91 30.87 5:45
6:00 9.24 2.43 7.5 9.27 2.1 30.54 6:00
6:15 7.05 1.78 7.58 7.74 1.93 26.08 6:15
6:30 9.69 2.21 7.6 9.58 2.07 31.15 6:30
6:45 7.5 9.11 8.52 8.05 1.96 35.14 6:45
7:00 11.1 9.79 6.79 10.57 1.98 40.23 7:00
7:15 12.99 8.94 6.67 11.89 2 42.49 7:15
7:30 9.07 4.49 6.25 9.15 9.57 38.53 7:30
7:45 10.94 2.67 5.59 10.46 10.59 40.25 7:45
8:00 11.33 2 5.1 10.73 7.43 36.59 8:00
8:15 7.23 1.85 5.75 7.86 2.66 25.35 8:15
8:30 8.75 5.13 5.41 8.93 3.84 32.06 8:30
8:45 9.71 1.97 5.07 9.6 3.31 29.66 8:45
9:00 6.39 1.74 4.89 7.27 5.32 25.61 9:00

The 15 minute kW demands for the 12 customers between the hours of 5:00 p.m. and 9:00 pm are given in the tables that follo
1.      Determine the maximum kW demand for each customer.
2.      Determine the average kW demand for each customer.
3.      Determine the kWH consumed by each customer in this time period.
4.      Determine the load factor for each customer.
5.      Determine the maximum diversified demand for each transformer.
6.      Determine the maximum non-coincident demand for each transformer.
7.      Determine the utilization factor (assume 1.0 power factor) tor each transformer.
8.      Determine the diversity factor of the load for each transformer.
9.      Determine the maximum diversified demand at node 1.
10.   Determine the rating of the transformers.

ANSWERS: #1 #2 #3 #4
1 MAXIMUM KW DEMAND 12.99 9.79 8.52 11.89
2 AVERAGE KW DEMAND 9.08705882 3.754118 6.6 9.16176471
3 KWH CONSUMED 38.62 15.955 28.05 38.9375
4 LOAD FACTOR 0.69954263 0.383465 0.774648 0.77054371
T1 T2
6 MAX NON-COINCIDENT DEMAND 53.78 101.69
5 MAX DIVERSIFIED DEMAND 42.49 89.95
7 UTILIZATION FACTOR 1.13306667 1.199333
8 DIVERSITY FACTOR 1.26570958 1.130517
9 MAX DIV. DEMAND @ N1 116.03
10 TRANSFORMER RATING (KVA) 37.5 KVA 75KVA
Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9
TRANSFORMER #2 0
#6 #7 #8 #9 #10 #11 #12 0
kW kW kW kW kW kW kW TOT KW
10.22 4.58 8.95 21.1 8.72 7.22 3.58 64.37
10.29 7.02 10.43 8.29 8.6 7.29 6.02 57.94
11.38 12.68 8.29 16.58 9.05 8.38 11.68 78.04
10.39 14.54 8.08 12.92 8.63 7.39 13.54 75.49
10.03 14.4 10.27 9.89 12.52 7.03 13.4 77.54
10.61 14.64 8.08 19.99 15.38 7.61 13.64 89.95
10.08 4.76 8.99 8.33 13.37 7.08 3.76 56.37
9.76 4.61 8.78 21.46 17.87 6.76 3.61 72.85
9.76 4.71 10.7 8.17 19.94 6.76 3.71 63.75
10.22 4.58 8.11 19.9 18.2 7.22 3.58 71.81
9.54 4.44 8.24 9.61 19.13 6.54 3.44 60.94
9.97 4.54 8.18 10.03 21.49 6.97 3.54 64.72
10.44 4.85 10.09 17.77 21.47 7.44 3.85 75.91
9.54 3.55 8.69 8.27 19.99 6.54 2.55 59.13
9.49 4.03 8.8 11.36 20.02 6.49 3.03 63.22
10.35 2.83 8.84 8.17 19.63 7.35 1.83 59
10.08 3.48 10.04 9.43 20.29 7.08 2.48 62.88

re given in the tables that follow. Assume a load power factor of 0.95 lagging.

45
40
35
30
25
20
15
10
5
#5 #6 #7 #8 #9 #10 #11 #12 0
10.59 11.38 14.64 10.7 21.46 21.49 8.38 13.64 1 2 3 4 5
3.68764706 10.1264706 6.72 9.03294118 13.0158824 16.1352941 7.12647059 5.72
15.6725 43.0375 28.56 38.39 55.3175 68.575 30.2875 24.31
0.34821974 0.88984803 0.45901639 0.84420011 0.60651828 0.75082802 0.85041415 0.419355
DIV. @ N1 DIV. @ N2 DIVERSIFIED DEMAND @ TAP
1 27.38 1 64.37 1 91.75
2 29.75 2 57.94 2 87.69
3 27.26 3 78.04 3 105.3
4 30.87 4 75.49 4 106.36
5 30.54 5 77.54 5 108.08
6 26.08 6 89.95 6 116.03
7 31.15 7 56.37 7 87.52
8 35.14 8 72.85 8 107.99
9 40.23 9 63.75 9 103.98
10 42.49 10 71.81 10 114.3
11 38.53 11 60.94 11 99.47
12 40.25 12 64.72 12 104.97
13 36.59 13 75.91 13 112.5
14 25.35 14 59.13 14 84.48
15 32.06 15 63.22 15 95.28
16 29.66 16 59 16 88.66
17 25.61 17 62.88 17 88.49

DIV. @ N1 TRANSFORMER2
45 90
40 80
35 70
30 60
25 50
20 40
15 30
10 20
5 10
0 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1 2 3 4 5 6 7 8 9 10 11

DIVERSIFIED DEMAD @ TAP


140

120

100

80

60

40

20

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
80

60

40

20

0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
TRANSFORMER 1 TRANSFORMER 2
TRANSFORMER2

4 5 6 7 8 9 10 11 12 13 14 15 16 17

13 14 15 16 17
13 14 15 16 17
2