Control & indication
Switches, contactors, relays, push
buttons & emergency lighting
This section provides a selection of Isolating, changeover and selector switches, push buttons,
indicator lights, delay timers, emergency lighting test packages, DIN socket outlets and contactors that
are used for isolation, installation monitoring and circuit control.
Isolating switches E.2
Contactors E.6
Indication
Control &
Indicator lights E.15
SBR163
SBR263
SBR399
SBR490
ESC080
E.2
Isolating switches
Characteristics
Electrical characteristics
Family SBRx40 SBRx63 SBRx80 SBRx90 SBR399
Number of poles 3P
Frame size Frame size 2 Frame size 3
Thermal current lth (40oC) 40A 63A 80A 100A 125A
Operational frequency 50Hz
Rated insulation voltage (Ui) 500V
Rated impulse withstand voltage Uimp 6kV
Protection degree 3
Working temperature -20 to 50oC
Storage temperature -40 to 80oC
Operational currents Ie
Load duty category Rated voltage
AC 21A
40A 63A 80A 100A 125A
AC 22B 400V AC
AC 22A
A category = Frequent operation B category = Infrequent operation
Indication
Control &
Prospective short circuit current (rms) 6kA
EN 60669 N/A
Associated fuse liks (gG) 40A 63A
Mechanical characteristics
Rigid cable section 25mm2 50mm2
Flexible cable section 16mm 2
35mm2
Tightening torque 2.8Nm 3.6Nm
IP protection degree 20
Mechanical endurance (number of cycles) 30,000 20,000
Electrical endurance @ AC22 (number of cycles) 5,000 2,500
Changeover Switches
Description Characteristics Width Cat ref.
Switch, 2 ways single pole 1 x 25A 250V~ 1 mod SFL125
1 3
SFM125 2
2 4
2 6
2 6
SF463
Four pole 4 x 63A 400V~ 8 mod SF463
E.4
Selector switches
Description Connection capacity: Conform to IEC947-3
To provide command signals - Rigid conductor: 1.5 to BS EN 60947-3
or program selection in 10mm2
electrical control schemes - Flexible conductor: 1 to Isolating voltage: 500V~
6mm2 Nominal current: 10-20A
Application
For domestic and
commercial installations
Selector Switches
Description Characteristics Width Cat ref.
1 pole selector switch 20A 400V~ 3 mod SK600
Non spring return
SK602
2 pole selector switch 20A 400V~ 3 mod SK601
Spring return
Indication
Control &
Voltmeter selector 20A 400V~ 3 mod SK602
3Ph&N
- 3 readings between phases
- 3 readings between phase &
neutral
- Null position (no reading)
SK603
E.5
Contactors
Contactors Night & Day override Output contacts Output AC3/AC7b (50Hz)
Remote switching allows the End User to set 1NO, 1NO+1NC, 2NO, 2NC, 8.5A, 25A, 32A
& control of power circuits output contact permanently 2NO+2NC, 3NO, 4NO, 4NC at 230V AC
suitable for lighting, heating, Off or temporarily On until next 880W, 2.6kW, 3.3kW
ventilation, pumps and home switching cycle. Output AC1/AC7a (50Hz) at 400V AC
automation. 25A, 40A, 63A 2.6kW, 7.8kW, 10kW
Specifications: at 230V AC
Manual override Coil Voltage: 4.6kW, 7.3kW, 11.6kW
to set output contacts 230V AC (50Hz) at 400V AC
permanently On or Off – 24V AC (50Hz) 13.8kW, 22kW, 35kW
Great for fault finding.
Contactors
Type Coil AC Override Rated output current Width Cat ref.
(50Hz) AC1/AC7a AC3/AC7b
1NO 230V AC Manual 25A 8.5A 1 mod ERC125
230V AC No 25A 8.5A 1 mod ESC125
1NO+1NC 230V AC No 25A 8.5A 1 mod ESC227
24V AC No 25A 8.5A 1 mod ESD227
ERC225 2NC 230V AC No 25A 8.5A 1 mod ESC226
2NO 230V AC Manual 25A 8.5A 1 mod ERC225
24V AC Manual 25A 8.5A 1 mod ERD225
230V AC Night & Day 25A 8.5A 1 mod ETC225
230V AC No 25A 8.5A 1 mod ESC225
230V AC No 40A 25A 3 mod ESC240
230V AC No 63A 32A 3 mod ESC263
24V AC No 25A 8.5A 1 mod ESD225
3NO 230V AC No 25A 8.5A 2 mod ESC325
ESC425 230V AC No 40A 25A 3 mod ESC340
230V AC Night & Day 40A 25A 3 mod ETC340
2NO+2NC 230V AC No 25A 8.5A 2 mod ESC427
230V AC No 63A 32A 3 mod ESC465
4NC 230V AC No 40A 25A 3 mod ESC441
230V AC No 63A 32A 3 mod ESC464
4NO 230V AC Manual 25A 8.5A 2 mod ERC425
230V AC No 25A 8.5A 2 mod ESC425
230V AC No 40A 25A 3 mod ESC440
ESC463 230V AC No 63A 32A 3 mod ESC463
Accessories
LZ060
E.6
Hum-free contactors
Hum-free contactors Manual override Specifications: Output AC1/AC7a (50Hz)
designed to provide customers to set output to contacts Coil Voltage: 25A, 40A, 63A
with a good nights sleep. permanently On or Off – Great 230V AC (50Hz) at 230V AC
for fault finding 4.6kW, 7.3kW, 11.6kW
Remote switching Output contacts at 400V AC
& control of power circuits Night & Day override 1NO+1NC, 2NO, 2NC, 13.8kW, 22kW, 35kW
suitable for lighting, heating, allows the End User to set 2NO+2NC, 3NO, 3NO+1NC,
ventilation, pumps and home output contact permanently 4NO, 4NC Output AC3/AC7b (50Hz)
automation Off or temporarily On until next 8.5A, 25A, 32A
switching cycle at 230V AC
880W, 2.6kW, 3.3kW
at 400V AC
2.6kW, 7.8kW, 10kW
Type Coil AC (50Hz) Override Rated output current Width Cat ref.
or DC AC1/AC7a AC3/AC7b
2NO 230V AC No 25A 8.5A 1 mod ESC225S
230V AC No 40A 25A 3 mod ESC240S
230V AC No 63A 32A 3 mod ESC263S
ESC425S 3NO 230V AC Manual 25A 8.5A 2 mod ESC325S
230V AC No 40A 25A 3 mod ESC340S
3NO+1NC 230V AC No 25A 8.5A 2 mod ESC428S
4NC 230V AC No 25A 8.5A 2 mod ESC426S
4NO 230V AC No 25A 8.5A 2 mod ESC425S
230V AC No 40A 25A 3 mod ESC440S
Indication
Control &
230V AC No 63A 32A 3 mod ESC463S
ESC463S
Accessories
LZ060
1 Mod
A2 2 A2 2 4 A2 2 4 A2 2 4
A1 1 3 5 A1 1 3 5 7 A1 1 3 5 7 A1 1 3 5 7 A1 1 3 5 7
2 Mod
A2 2 4 6 A2 2 4 6 8 A2 2 4 6 8 A2 2 4 6 8 A2 2 4 6 8
A1 1 7 A1 1 3 5 A1 1 3 5 7 A1 1 3 5 7 A1 1 3 5 7
3 Mod
A2 2 8 A2 2 4 6 A2 2 4 6 8 A2 2 4 6 8 A2 2 4 6 8
11 13
Aux Module
12 14
Electrical Characteristic
Type ERxxxx, ESxxxx, ETCxxx ESC080
Description Modular contactor
Aux. contact
Standard conformity IEC/EN 61095
Number of module 1 2 3 ½
o
Thermal current lth (40 C) 25A 25A 40A 63A 6A
Rated frequency 50Hz 50Hz 50Hz 50Hz 50Hz
Rated insulation voltage (Ui) 250V 440V 440V 440V 250V
Rated impulse withstand voltage (Uimp) 4kV 4kV 4kV 4kV 4kV
Protection degree (IP rating) 2 2 2 2 2
Power dissipation
Power dissipation per current path 1.5W 3.2W 5W 0.4W
Connection
rigid 1...10mm2 4...25mm2 1...16mm2
Main contact cable section
flexible 1...6mm2 4...16mm2 1...16mm2
Type M3.4 M5 M3.4
Main contact connection screw Posidrive PZ2 PZ2 PZ2
Max. tight. torque 1.2Nm 3.5Nm 1.2Nm
rigid 1...10mm2 1...10mm2
Coil connection cable section
flexible 1...6mm2 1...6mm2
Type M3.5 M4 -
Coil connection screw Posidrive PZ2 PZ2
Max. tight. torque 1.2Nm 2.5Nm
Heating applications
The choice of the contactor is based on the electrical heating load, and the targeted life time.
Single phase Three phase supply
U R
U R R U R
U R
Indication
63A 7.6 10.2 22.6 30 35
Control &
No. of operations 600 000 300 000 150 000 100 000 60 000
(# see note)
#NOTE: 1 opening +1 closing contact = 2 operations. *On three phase configuration the maximum load per phase corresponds to the
values stated divided by 3.
L1 U U
L1
M L2 V M
L2 V W
L3
Indication
Control &
180 2 5 6
35 24 30 50
50 15 22 34
70 12 18 28
High Pressure sodium lamps 110 10 14 22
(Low power factor <0.9) 150 8 10 16
250 5 6 10
400 2 4 6
1000 1 2 3
35 18 31 50
50 18 22 35
70 12 16 25
High Pressure sodium lamps 110 8 13 21
(High power factor >0.9) 150 6 8 13
250 4 7 11
400 2 5 8
1000 1 2 3
35 30 42 55
70 17 26 36
Metal - Halide Lamp 150 12 14 20
(Low power factor <0.9) 250 8 9 14
400 4 6 9
1000 0 3 5
35 18 22 39
70 13 22 39
Metal - Halide Lamp 150 8 12 22
(High power factor >0.9) 250 7 9 16
400 2 5 7
1000 1 2 3
LED’s
4 - 12 54 86 135
17 - 22 40 63 101
LED 230V integrated Driver, Non dimmable, E27 / GU10
30 - 40 28 44 70
50 22 35 55
4 - 12 120 159 250
LED
17 - 22 88 118 185
230V integrated driver
30 - 40 62 82 130
Dimmable, GU 10
50 48 65 102
100 5 6 9
LED high bay lighting
150 3 4 6
230V integrated driver
200 2 4 6
1-5 120 180 220
LED
7 - 10 120 160 200
12V external driver Dimmable
15 88 160 200
Delay ON
Control Cd
Characteristics Width Cat ref.
1 c/o contact 1 mod EZN001
Output S 8A AC1 contact rating
T
Time delay T: 0.1s to 10hr
EZN001
1 Delay OFF
Control Cd
Characteristics Width Cat ref.
1 c/o contact 1 mod EZN002
Output S 8A AC1 contact rating
T Time delay T: 0.1s to 10hr
EZN002
Adjustable time ON
Timer
Symmetrical flasher
Multifunction
E.12
Time lag switches
Description
Time lag switches provide
control of lighting circuits with
automatic switch-off after a
preset time. (e.g. for staircase,
corridors lighting). Compact
design with a two position
switch permanent/timed lighting
implementation facility.
2300W incandescent
halogen and fluorescent
EMN001
Indication
Control &
Interface relays
Contact
max. 5A 230V~ -
A2 2 4
EN145 min. 10mA - 12V DC
E.13
Push buttons
Description Connection capacity
2 versions: - 10mm2 rigid cables
- Impulse push buttons - 6mm2 flexible cables
- Latching push buttons
Standard conformity:
These versions with indicator IEC60947-5-1 for push buttons
lights are equipped with green IEC62094-1 for indicator lights
or red diffuser. (LED technology)
SVN311M
Contacts: 1NO+1NC 1 mod SVN391M
(stop/start)
SVN413M
E.14
Indicator lights
Description Connection capacity Standard conformity:
These products are used for - 10mm2 rigid cable IEC62094-1 for indicator lights
remote controlling signalisation - 6mm2 flexible cable
of any event in any electric
installation (domestic, tertiary
& industrial)LED technology
providing longer life, new design
and integrated label holder.
Indicator lights
Description Characteristics Width Cat ref.
With light 230V~ 1 x green 1 mod SVN121M
1 x red 1 mod SVN122M
1 x blue 1 mod SVN124M
1 x clear 1 mod SVN125M
3 x red 1 mod SVN127M
SVN122M, SVN125M, SVN124M
Indication
Control &
SVN121M, SVN122M, SVN127M
SNO15DA
E.15
Transformers, bells and buzzers
Description Connection capacity Note
Provide safety for extra - Cable clamp type The transformers have a higher
low voltage 8, 12, 24V~. no load voltage. The stated
Output voltages correspond to the
Technical data - Bells: 85dBA voltages at nominal load
- Secondary voltage: - Buzzers: 78dBA
8V, 12V, 24V When a bell transformer is
- Bell transformers are installed in an enclosure with
short circuit protected mains voltage equipment,
- Bells/buzzers: Maximum 230V cable should be used
continuous duty < 30min on the secondary side of the
transformer or extra low voltage
cable should be sheathed
within the enclosure.
*Please check availability with the Hager sales office at time of order
Safety transformers
Description Characteristics Width Cat. ref.
Frequency: 50/60Hz 25VA 4 mod ST312*
Primary voltage: 230V
Secondary voltage: 12 / 24V~
ST312
Bell transformers
Description Characteristics Width Cat. ref.
Frequency: 50/60Hz 2 mod ST303*
Primary voltage 230V~ 8VA
Secondary voltage: 8V~ 1A
12V~ 0.67A
Frequency: 50/60Hz 3 mod ST305*
Primary voltage 230V~ 16VA
ST303 Secondary voltage: 8V~ 2A
12V~ 1.33A
Bells
Description Characteristics Width Cat. ref.
8/12V~ 1 mod SU212*
4VA - 0.35A
SU212
Buzzers
Description Characteristics Width Cat. ref.
8/12V~ 1 mod SU214*
4VA - 0.35A
230V~ 1 mod SU215*
6.5VA - 0.03A
SU214
E.16
Transformers
Safety transformers
These transformers are designed to ensure personal safety,
their primary winding are electrically separated from their
secondary windings and they are intended to feed safety
extra low voltage (SELV) circuits < 50V. A thermal overload,
in the primary windings, ensures that if a short circuit or an
overload occurs in the output it will not damage the device.
Bell transformers
Bell transformers are similar to safety transformers but the
secondary voltages do not exceed 24 volts, they are also
similarly protected against short circuits and overloads,
by thermal protection in the primary winding.
Compliance with the standards
The bell and safety transformers conform with EN 61558 (BS
3535). Where transformers are to be used in a common enclosure
with other devices, heat dissipation inserts should be used.
Recommendation of Use
- To link only a secondary (never link both simultaneously)
- Do not connect (in series or in parallel)
secondaries of different transformers.
Technical specification
Indication
Control &
Nominal power 8VA 16VA 25VA 63VA
Designation Bell Bell Safety Safety
Primary voltage U1 230 volts 230 volts 230 volts 230 volts
Secondary voltage U2 8 volts 8 volts 12 volts 12 volts
In = 1A In = 2A In = 2.08A In = 5.25A
U3 12 volts 12 volts 24 volts 24 volts
In = 0.67A In = 1.33A In = 1.04A In = 2.63A
No load secondary U2 15 volts 12 volts 14 volts 14 volts
Voltage U3 22 volts 13 volts 29 volts 27 volts
Galvanic insulation 4kV 4kV 4kV 4kV
Max functional temperature 35°C 35°C 35°C 35°C
Insulation class H B B H
Overload and S/C protection Thermal cut out in the primary winding