Introduction: electrician who hasn’t used a torque wrench has


experienced this at least once.
1. Loose electrical connections are common place • Over-Torque - damaging the threads, deforming
and can easily be identified and corrected when the hardware (stripping), or damaging the
addressed properly. current capacity of the conductor depending
2. The secret to making and keeping reliable upon conductor type (solid vs. stranded).
electrical connections is contained in two • Under-Torque - allowing a joint to come loose. It
elements: start with clean contact surfaces, and may also allow the joint to flex and thus fail
apply the correct force. under fatigue. Also results in high resistive
3. When it comes to electrical connections there connections.
are many. Some of which are; (a) solid • Brinelling – caused by poor quality washers,
connections (e.g., bus bars), (b) lug connections leading to a loss of clamp load and failure of the
(e.g., switchgears), (c) molded terminal joint. On solid connections such as buss bars,
connection (e.g., breakers), (d) screw terminals Belleville spring washers should used as they
(e.g., control panel terminal strip). are designed to help maintain proper tightness at
the joints of bus bars and cable connections as
General Rules which must be followed: the bus material expands and contracts under
load.
1. Never over torque a Fastener. To over-torque a • Corrosion – caused by the disintegration of an
Fastener can cause it to stretch beyond normal engineered material due to electrochemical
limits causing Fastener breakage, loosening of oxidation of metals in reaction with an oxidant
Fastener by stripping, and even conductor such as oxygen, this is why Fasteners must be
damage. lubricated unless stated by the equipment
2. Never under torque Fasteners because it can manufacturer. This is especially true between
cause the Fastener to loosen. Poor electrical aluminum and copper connections. Clean
connections can create electrical noise (power contact surfaces are a function of cleaning
quality issues) by vibrating and creating arc at procedures, which includes joint compounds
the connection. such as Alnox® (similar and dissimilar
3. Ensure you know the torque specification. All of materials), or NO-OX-ID (similar materials).
the major companies who manufacture
electrical components have Torque Definitions:
Specifications for their equipment, ask for it.
4. Ensure your electricians own and know how to Torque Wrench:
use a torque wrench. When all else fails read the
• A torque wrench is a tool used to precisely apply
instructions.
5. Use infrared thermography and a multi-meter to a specific torque to a fastener such as a nut or
check for possible loose connections (high Fastener.
resistive connections which can be measured • A torque wrench is used where the tightness of
will result in increased heat). Infrared screws and Fasteners is crucial.
thermography is a much safer and quicker • It allows the operator to measure the torque
method to verify.
applied to the fastener so it can be matched to
Fastener Failure Modes: the specifications for a particular application.
This permits proper tension and loading of all
• Overloading – Force exceeds Fastener parts.
strength, Fastener loosens or shears. Any • Torque Screwdriver is often need when making
electrical terminal connections and works off the
Page 1 of 2 GPAllied
4360 Corporate Road
Suite 110
www.gpallied.com Charleston, SC 29405
Office (843) 414-5760
Fax (843) 414-5779
How to Torque Electrical Connections?
“TOOL BOX TRAINING”

same principals as mentioned above for the


torque wrench.

How to Torque a Fastener?

Using the most common torque wrench which is a Step 2: Torque the Fastener to the point where the
“click type” follow these steps; desired torque is reached, signaling the desired
torque by causing a click sound (some torque
Step 1: Preset torque value on torque wrench as wrenches will not allow a Fastener to be torque
determined by the equipment manufacturer; or if not above the setting however some will, be sure and
available a common torque specification chart. (see purchase the best torque wrench/screwdriver
below) possible)

Note: When using lubrication make sure to use the If you have questions send me an email at
appropriate values as found in the tables below. rsmith@gpallied.com or you can contact Chris
Colson at colsonc@alliedreliability.com