AA-036108 001 02 X 990 MATERIAL LIST NOTES:

REV. NO. SHT. NO. DRAWING NUMBER INDEX PLANT NO.


CODE SAMSS NO. DESCRIPTION 1. IF REQUIRED, SUBSTITUTE 1/2 " HARDWARE IN PLACE OF
THE 12mm SIZE HARDWARE. THREADS TO BE TAPPED
1 D/C ENCLOSURE: FIBERGLASS; NEMA 4x; 513mm x 514mm x 152mm
WILL THEN BE 1/2 " BY 13 THREADS/INCH.
2 14-084-679 BUS BAR: TINNED COPPER; 6mm x 100mm x 432mm
NAMEPLATE: 200mm x 100mm x 3mm LAMINATED 2. IF REQUIRED, SUBSTITUTE 5/16 " HARDWARE IN PLACE OF
3 D/C THE 8mm SIZE HARDWARE.
BAKELITE; WHITE LETTERS ON BLACK BACKGROUND
514
4 D/C PANEL: BLACK BAKELITE; 6mm x 432mm x 432mm 3. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
5 D/C PANEL MOUNTING HARDWARE: SIZE AS REQUIRED NOTED OTHERWISE.
432 41
TERMINAL CONNECTOR: TINNED COPPER; CRIMP TYPE; 4. CABLES AND LUGS SHOWN ARE TYPICAL. CALCULATE
394 19 6 14-198-134 TWO 13mm { HOLES; 44.5mm BETWEEN HOLES; THE ACTUAL CABLE AND LUG SIZE BASED ON VOLTAGE
DROP AND LOAD VALUES.
50mm 2 CABLE SIZE
386 23
TERMINAL CONNECTOR: TINNED COPPER; CRIMP TYPE;
7 14-198-144 TWO 13mm { HOLES; 44.5mm BETWEEN HOLES;
120mm 2 CABLE SIZE
8 D/C BOLT: BRASS; 12mm DIA. x 38mm LONG

41
9 05-333-623 NUT: BRASS; FOR 12mm DIA. BOLT
10 D/C WASHER: BRASS; ROUND FLAT; 12mm DIA. HOLE

23
SEE NOTE 2 16 15 14 13 12 11 D/C WASHER: BRASS; LOCK; 12mm DIA. HOLE
4
12 D/C BOLT: BRASS; 8mm DIA. x 64mm LONG
12 13 14 15 16
13 D/C NUT: BRASS; FOR 8mm DIA. BOLT
SEE DETAIL-1
2 14 47-819-828 WASHER: BRASS; ROUND FLAT; 8mm DIA. HOLE

121
8 9 10 11 (TYPICAL) 15 D/C WASHER: BRASS; LOCK; 8mm DIA. HOLE
SEE NOTE 1
16 D/C SPACER: 8mm THREADS; 25mm LONG

62
B B

432
386

513
7
6
TYP. OF TWO
TYP. OF SIX SEE NOTE 4
SEE NOTE 4

2
50mm 2 (1/0 AWG) CABLES TO 120mm (4/0 AWG)
WELL CONDUCTORS/CASINGS CABLES TO RECTIFIER
(TYPICAL) (TYPICAL)
A
SEE NOTE 4 521

(TYP.)
355

16
5

DOOR FASTENER
1

100
200

6
(TYP.)

SECTION A-A

513
12
(TYP.)
CATHODIC PROTECTION

6
100
OFFSHORE NEGATIVE TERMINAL

(TYP.)
JUNCTION BOX

580
548
DRILL 38mm DIA. DRILL 50mm DIA.
#8 STAINLESS STEEL
6 HOLES (TYP.) 2 HOLES 13 mm ENGRAVED WHITE
MOUNTING HARDWARE
LETTERS ON BLACK
BACKGROUND
38

3
152

HINGE MANUFACTURER’S

34
NAMEPLATE
A
51

152

195

99 39 39 39 39 39 78 99 11mm DIA. HOLES


(4 PLACES)

RIGHT SIDE VIEW OF ENCLOSURE


BOTTOM VIEW FRONT VIEW OF ENCLOSURE

DRAWING RESPONSIBILITY:
11
CATHODIC PROTECTION STANDARDS COMMITTEE
9
10
8
DRILL 8mm DIA. DRILL AND TAP FOR 12mm DIA. 13 12
2 13
2 HOLES EACH END NATIONAL COURSE THREADS-16 HOLES 12 EDSD
02 MAR99 REVISED NOTES AND MATERIAL LIST.
SEE NOTE 1 6 WED
2
15 15 ORIGINAL ORIGINAL ORIGINAL
19

ESSD ADDED NOTES ON SECTION A-A, NOTE 4


28

01 MAY94
RCR & REVISED NOTES ON MATERIAL LIST. SIGNED SIGNED SIGNED
14 14
REV. DATE BY JO/EWO DESCRIPTION CHKD. CERT. APPD.
44.5

NO.
102

62

SAUDI ARABIAN OIL COMPANY


14 14
DRAWN BY ESSD/RUDY CHECKED BY SCALE: NONE

DATE STARTED 10-20-90 DATE COMPLETED 10-21-90

19 39 39 39 39 39 39 78 39 19 14
OPR’G. DEPT. ENG. DEPT.

432 APP’D. FOR CONST.

16 10 4 16 THIS DRAWING IS NOT TO BE USED FOR CERTIFIED


CONSTRUCTION OR FOR ORDERING
MATERIAL UNTIL CERTIFIED AND DATED BY DATE

DETAIL-1 SECTION B-B CATHODIC PROTECTION


OFFSHORE NEGATIVE
TERMINAL JUNCTION BOX
STD. DWG. METRIC
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

990 X AA-036108 001 02


Saudi Aramco 2615 ENG. (3/91)

Copyright©Saudi Aramco 2009. All rights reserved. CADD-02