Accessible and Usable
Buildings and Facilities
INTERNATIONAL
CODE COUNCIL®
ICC/ANSI Al17.1-1998
INTERNATIONAL
CODE COUNCIL®
ICC/ANSI
A 117.1-1998
Secretariat
ISBN 1-58001-029-6
Copyright © 1998
INTERNATIONAL
CODE COUNCIE9
ALL RIGHTS RESERVED. This Accessible and Usable Buildings and Facilities (ICC/ANSI AI17.1-1998) is a copyrighted work
owned by the International Code Council. Without advance written pennission from the copyright owner, no part of this book may
be reproduced, distributed or transmitted in any fonn or by any means, including, without limitation, electronic, optical or
mechanical means (by way of example and not limitation, photocopying, or recording by or in an infonnation storage and retrieval
system). For infonnation on pennission to copy material exceeding Dlir use, please contact: ICC Publications, 4051 West
Flossmoor Road, Country Club Hills, Illinois 60478-5795. (Phone 708-799-2300.)
Trademarks: "International Code Council," the ICC logo and "Accessible and Usable Buildings and Facilities (ICC/ANSI
A 117.1-1998)" are trademarks of the International Code Council, Inc.
iii
iv
FOREWORD
(This Foreword is not part of American National Standard A 117.1-1998.)
The 1961 edition of ANSI Standard A 117.1 presented the first criteria for accessibility to be
approved as an American National Standard and was the result of research conducted by
the University of Illinois under a grant from the Easter Seal Research Foundation. The Na-
tional Easter Seal Society and the President's Committee on Employment of People with Dis-
abilities became members of the Secretariat and the Standard was reaffirmed in 1971 .
In 1974, the U.S. Department of Housing and Urban Development joined the Secretariat and
sponsored needed research, which resulted in the 1980 edition. After further revision that
included a special effort to remove application criteria (scoping requirements), the 1986 edi-
tion was published and, when requested in 1987, the Council of American Building Officials
(CABO) assumed the Secretariat. Central to the intent of the change in the Secretariat was
the development of a standard that, when adopted as part of a building code, would be com-
patible with the building code and its enforcement. This edition has largely achieved that
goal. In 1998, CABO became the International Code Council (ICC).
This edition has been substantially reformatted. Illustrative figures are located adjacent to
corresponding text to simplify the use of the Standard. Unless specified otherwise, figures
are not part of the Standard. Should a figure appear to illustrate criteria that differ with the
text of the Standard, the criteria stated in the text govern.
Suggestions for improving this edition will be welcome. They should be sent to ICC, Secretar-
iat, ANSI A 117 Committee, Suite 708, 5203 Leesburg Pike, Falls Church, VA 22041.
This Standard was processed and approved for submittal to ANSI by the Accredited Stand-
ards Committee on Architectural Features and Site Design of Public Buildings and Residen-
tial Structures for Persons with Handicaps (A 117). Committee approval of the Standard does
not necessarily imply that all Committee members voted for its approval. At the time it ap-
proved this Standard, the A 117 Committee had the following members:
v
Bell Communications Research, Inc ................. William G. KHenan
Builders Hardware Manufacturers Association, Inc .. .. Dave Gilda
Richard Hudnut (Alt)
Building Officials and Code Administrators Inti, Inc .... Kenneth M. Schoonover, PE
Michael Pfeiffer, PE (Alt)
Building Owners and Managers Association Inti ...... Lawrence G. Perry, AlA
James C. Dinegar (Alt)
Disability Rights Education and Defense Fund . . . . . . .. Marilyn Goldl~n
Logan HoppE!r (Alt)
International Code Council ......................... Shahriar Amiri
International Conference of Building Officials ......... William D. Wall, PE
Rick Okawa, PE (Alt)
International Sign Association ...................... Teresa Cox
Bob Wallace (Alt)
Sharon Toji (Alt)
Little People of America, Inc ........................ Angela Van Etten, J.D.
National Apartment Association .................... Ronald G. Nickson
National Association of Home Builders .............. Jay Murdoch
Ron Burton (Alt)
National Association of the Deaf. . . . . . . . . . . . . . . . . . .. Don Sievers
Nancy J. Bloch (Alt)
National Conference of States on Building Codes
and Standards ................................... William E. O'I\leil
National Electrical Manufacturers Association ........ Rein Haus
National Elevator Industry, Inc ...................... Edward A. Donoghue
Ralph Droste (Alt)
George Kappenhagen (Alt)
National Federation of the Blind .................... James GashHI
Dr. Harold Snider (Alt)
National Fire Protection Association. . . . . . . . . . . . . . . .. Ron Cote, PE
National Institute for Tall People .................... Carlisle Bean
Paralyzed Veterans of America . . . . . . . . . . . . . . . . . . . .. Kim A. Beasley, AlA
Soy Williams (Alt)
Plumbing Manufacturers Institute ................... Jack Lancaster
Richard W. Church (Alt)
President's Committee of Employment of
People with Disabilities . . . . . . . . . . . . . . . . . . . . . . . . . . .. Maggie Roffee
Ellen D. Daly (Alt)
Self Help for Hard of Hearing People, Inc ............ Jack O'KeeffH
Society for Environmental Graphic Design ........... Kenneth A. Ethridge, Jr., AlA
Southern Building Code Congress
International, Inc ................................. Mark W. Wales, CBO
Richard Vognild, PE, CBO (Alt)
United Cerebral Palsy Associations ................. Robert Dale Lynch, FAIA
Michael Morris (Alt)
US Architectural and Transportation
Barriers Compliance Board ........................ Marsha K. Mazz
Scott Windley (Alt)
US Department of Agriculture ...................... Larry B. Fleming
Samuel Hodges, III (Alt)
US Department of Housing and
Urban Development .............................. Nelson A. Carbonell
Cheryl D. Kent (Alt)
Alan Rothman (Alt)
US Department of Veterans Affairs ...... ". . . . . . . . . . .. Dennis Hancher
World Institute on Disability ........................ Hale Zukas
vi
Individual Members
Brian D. Black
Patrick J. Higgins
Jake L. Pauls
Special recognition is provided to the following individuals who also contributed as members of the com-
mittee during this review cycle:
vii
viii
ICC/ANSI A 117.1-1998
Contents
ix
ICC/ANSI A117.1-1998
x
ICC/ANSI A117.1-1998
List of Figures
xi
ICC/ANSI A117.1-1998
xii
ICC/ANSI A117.1-1998 Chapter 1. Application and Administration
The specifications in Chapters 3 through 9, and Nothing in this standard is intended to prevent the
Sections 1002 and 1004 of this standard make use of designs, products, or technologies as alter-
sites, facilities, buildings and elements accessible natives to those prescribed by this standard, where
to and usable by p"eople with such physical disabili- equivalent or superior accessibility and usability are
ties as the inability to walk, difficulty walking, provided and such equivalency is approved by the
reliance on walking aids, blindness and visual administrative authority adopting this standard.
impairment, deafness and hearing impairment, in-
coordination, reaching and manipulation disabili- 104 Conventions
ties, lack of stamina, difficulty interpreting and react-
ing to sensory information, and extremes of physical 104.1 Dimensions. Dimensions that are not stated
size. The intent of these sections of the standard is as "maximum" or "minimum" are absolute. All
to allow a person with a physical disability to inde- dimensions are subject to conventional industry
pendently get to, enter, and use a site, facility, build- tolerances.
ing, or element.
104.2 Graphics. Unless specifically stated
Section 1003 of this standard provides technical cri- otherwise, figures included herein are not
teria for Type B dwelling units. These criteria are in- considered part of the standard and are provided for
tended to be consistent with the intent of only the informational purposes only.
technical requirements of the Federal Fair Housing
Act Accessibility Guidelines. These Type B dwelling 105 Referenced American National Standards
units are intended to supplement, not replace, ac-
cessible Type A dwelling units as specified in this
105.1 General. The American National Standards
listed in Section 105.2 are referenced in this docu-
standard.
ment. Where requirements in this standard differ
from those of these referenced standards, the re-
This standard is intended for adoption by govern- quirements of this standard shall apply.
ment agencies and by organizations setting model
codes to achieve uniformity in the technical design 105.2 Referenced Standards.
criteria in building codes and other regulations.
105.2.1 Power Operated Pedestrian Doors.
101.1 Applicability. Sites, facilities, buildings, and ANSI/BHMA A 156.10-1991.
elements required to be accessible shall comply
105.2.2 Power Assist and Low Energy Power
with the applicable provisions of Chapters 3 through
Operated Doors. ANSI/BHMA A 156.19-1997.
9.
EXCEPTIONS: 105.2.3 Safety Code for Elevators and Esca-
1. Type A dwelling units shall comply with Sec- lators. ASME/ANSI A17.1-1996.
tion 1002. 105.2.4 Audible Emergency Evacuation Sig-
2. Type B dwelling units shall comply with Sec- nal. ANSI S3.41-1990.
tion 1003.
3. Dwelling units required to have accessible 105.2.5 Installation, Maintenance, and Use
communication features shall comply with of Protective Signaling Systems. NFPA
Section 1004. 72-1996.
106 Definitions
102 Provisions for Adults
106.1 General. For the purpose of this standard, the
The specifications in this standard are based on terms listed in Section 106.5 have the indicated
adult dimensions and anthropometrics. meaning.
Chapter 1. Application and Administration ICC/ANSI A 117.1-1998
Convention Description
6
dimension for small measurements·
~
min minimum
max maximum
-----~ centerline
Fig. 104.2
Graphic Convention for Figlures
106.2 Terms Defined in Referenced Standards. accessible: Describes a site, building, facility, or
Terms not defined in this section, but specifically de- portion thereof that complies with this standard.
fined in a referenced standard, shall have the speci-
fied meaning from the referenced standard, unless accessible route: An interior or exterior circulation
otherwise stated. path that complies with this standard.
admini=:»trative authority: Ajurisdictional body that
106.3 Undefined Terms. The meaning of terms not adopts or enforces regulations and standards for
specifically defined in this document or in refer- the design, construction, or operation of buildings
enced standards shall be as defined by collegiate and facillities.
dictionaries in the sense that the context implies.
automatic door: A door operated with power
mechanisms and controls.
106.4 Interchangeability. Words, terms, and
phrases used in the singular includes the plural and Braille: A system which translates text into cells
the plural the singular. formed by raised dots.
2
ICC/ANSI A117.1-1998 Chapter 1. Application and Administration
cross slope: The slope that is perpendicular to the pictogram: A pictorial symbol which is recognized
direction of travel (see running slope). as representing activities, facilities, or concepts.
curb ramp: A short ramp cutting through a curb or power-assisted door: A door used for human pas-
built up to it. sage, with a mechanism that helps to open the door,
or to relieve the opening resistance of the door.
destination-oriented elevator system: An eleva-
ramp: A walking surface that has a running slope
tor system that provides lobby controls to select
steeper than 1:20.
destination floors, lobby indicators designating
which elevator to board, and a car indicator desig- running slope: The slope that is parallel to the
nating the floors at which the car will stop.
r element: An architectural or mechanical compo-
direction of travel (see cross slope).
3
I
4
ICC/ANSI A 117.1-1998 Chapter 2. Seoping
Chapter 2. Seoping
5
6
ICC/ANSI A 117.1-1998 Chapter 3. Building Blocks
301 General
predominant direction of trav~
301.1 Scope. The provisions of this chapter shall
apply where required by the scoping provisions
adopted by the administrative authority or by Chap-
ters 4 through 10.
Fig. 303.2
Vertical Changes in Leve!
.
1/4 -1/2
faces shall be of a size that does not permit the pas-
6.4-131~ ~
sage of a 1/2 inch (13 mm) diameter sphere, except
as allowed in Sections 407 and 408. Elongated
openings shall be placed so that the long dimension
is perpendicular to the dominant direction of travel.
7
Chapter 3. Building Blocks ICC/ANSI A 117.1-1998
304 Wheelchair Turning Space clude knee and toe clearance complying with
Section 306 only at the end of either the base or
304.1 General. A wheelchair turning space shall one arm.
comply with Section 304.
304.4 Doors. Unless otherwise specified, doors
304.2 Floor or Ground Surface. Floor or ground shall be permitted to swing into wheelchair turning
surfaces of a wheelchair turning space shall have a spaces.
slope not steeper than 1:48 and shall comply with
Section 302. 305 Clear Floor or Ground Space
304.3 Size~ Wheelchair turning space shall comply 305.1 General. Clear floor or ground space shall
with Section 304.3.1 or 304.3.2. comply with Section ,305.
60 min 305.2 Floor or Ground Surfaces. Floor or ground
1525 surfaces of a clear floor or ground space shall have
//---- .........
12 min 12 min
305 305
(b) T-shaped '
-'k-----L - - -....:... ~
Fig. 304.3 !< 30 min l
Size of Wheelchair Turning Space 1 760 1
(a) Forward
304.3.1 Circular Space. The wheelchair turn-
ing space shall be not less than 60 inches (1525
mm) diameter minimum. Wheelchair turning --I r--------l
space shall be permitted to include knee and c
I I
toe clearance complying with Section 306. ·E (0
a I I
a "- I I
M
304~3.2 T-Shaped Space. The wheelchair turn- I I
ing space shall be a T-shaped space within a -'fr----L __ - _____ J
60 inch (1525 mm) minimum square with arms
and base 36 inches (915 mm) wide ,minimum.
l
1
48 min l
1
1220
Each arm of the T shall be clear of obstructions
12 inches (305 mm) minimum in each direction (b) Parallel
and the base shall be clear of obstructions
24 inches (610 mm) minimum. T-shaped wheel- Fig. 305.5
chair turning spaces shall be permitted to in- Position of Clear Floor or Ground Space
8
ICC/ANSI A117.1-1998 Chapter 3. Building Blocks
305.6 Approach~ One full unobstructed side of the mm) above the floor or grol:Jnd shall be toe
clear floor or ground space shall adjoin or overlap an clearance and shall comply with Section 306.2.
accessible route or adjoin another clear floor or
ground space. 306.2.2 Maximum Depth. Toe clearance shall
be permitted to extend 25 inches (635 mm)
305.7 Maneuvering Clearance. If a clear floor or maximum under an element.
ground space is in an alcove or otherwise confined 306.2.3 Minimum Depth. Where toe clearance
on all or part of three sides, additional maneuvering is required at an element as part of a clear floor
clearances complying with Sections 305.7.1 and or ground space, the toe clearance shall extend
305.7.2 shall be provided. 17 inches (430 mm) minimum beneath the ele-
ment.
306.2.4 Additional Clearance. Space extend-
v 0
C\I
T'"
co ing greater than 6 inches (150 mm) beyond the
c:: 0 1\ available knee clearance at 9 inches (230 mm)
'E C\I
x x
1\
co C\I above the floor or ground shall not be included
v in toe clearance.
306.2.5 Width. Toe clearance shall be 30 inch-
es (760 mm) wide minimum.
I
I
I
I
I 9
i-- I~
l- J :~
430
(b) Parallel Approach
Fig. 306.2
Fig. 305.7 Toe Clearance
Maneuvering Clearance in an Alcove
9
Chapter 3. Building Blocks ICC/ANSI A117.1-1998
8 min 4 max
~
I
I
I
I
I 9min
~
I
I I I
:~
c:>
: ~ ___LJ o
ro
(V)
c:>
y
/\1 C\I
x /\1
~<
C\I~
" 10
280 /\ /\
Fig. 306.3 x x
. Knee Clearance
10
ICC/ANSI A117.1-;1998 Chapter 3. Building Blocks
clearance is less than 80 inches (2030 mm) high. clear floor or ground space shall extend be-
Leading edge of such guardrail or barrier shall be neath the element for a distance not less than
27 inches (685 mm) maximum above the floor or the required reach depth over the obstruction.
ground. The high forward reach shall be 48 inches (1220
mm) maximum where the reach depth is
20 inches (510 mm) maximum. Where the
reach depth exceeds 20 inches (510 mm), the
high forward reach shall be 44 inches (1120
mm) maximum and the reach depth shall be
~LO 25 inches (635 mm) maximum.
Eoo
r-.... CD
C\I 0
00
v v
x
x
Fig. 307.4
Reduced Vertical Clearance
Fig. 308.2.2
Obstructed High Forward Reach
11
Chapter 3. Building Blocks ICC/ANSI A 117.1-1998
~ 0
E gj
.....- ..... __
Fig. 308.3.1
Unobstructed Side Reach
..}
~o ~~
E co
LO('t)
.....
~ 0
E C\I
C\I x
co .....
.q
«3 LO
E <.0
.q co
('t)
10 max. 24 max
255 610
(a) (b)
Fig. 308.3.2
Obstructed High Side Reach
308.3.2 Obstructed High Reach. Where a 309.2 CIE~ar Floor or Ground Space. A clear floor
clear floor or ground space allows a parallel ap- or ground space complying with Section 305 shall
proach to an object and the high side reach is be provided.
over an obstruction, the height of the obstruc-
tion shall be 34 inches (865 mm) maximum and 309.3 Heiight. Operable parts shall be placed within
the depth of the obstruction shall be 24 inches one or more of the reach ranges specified in Section
(610 mm) maximum. The high side reach shall 308.
be 48 inches (1220 mm) maximum for a reach EXCEPTIONS:
depth of 10 inches (255 mm) maximum. Where 1. Where the use of special equipment dictates
the reach depth exceeds 10 inches (255 mm), otherwise.
the high side reach shall be 46 inches (1170 2. Where electrical and communications sys-
mm) maximum for a reach depth of 24 inches tems receptacles are not normally intended
(610 mm) maximum. for use by building occupants.
12
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
401.1 Scope. Accessible routes required by the 403.1 General. Walking surfaces that are a part of
scoping provisions adopted by the administrative an accessible route shall comply with Section 403.
authority shall comply with the applicable provisions
of this chapter.
403.2 Floor or Ground Surface. Floor or ground
402 Accessible Routes surfaces shall comply with Section 302.
402.1 General. Accessible routes shall comply with 403.3 Slope. The running slope of walking surfaces
Section 402. shall not be steeper than 1:20. The cross slope of a
walking surface shall not be steeper than 1:48.
402.2 Components. Accessible routes shall con-
sist of one or more of the following components:
Walking surfaces with a slope not steeper than 1:20, 403.4 Changes in Level. Changes in level shall
doorways, ramps, curb ramps, elevators, and comply with Section 303.
wheelchair (platform) lifts. All components of an ac-
cessible route shall comply with the applicable por- 403.5 Clear Width. Clear width of an accessible
tions of this standard. route shall comply with Table 403.5.
48 min
1220
c: c:
'E LO 'E LO
C\I
("t)
co com
("t)
Fig. 403.5
Clear Width of an Accessible Route
13
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
Fig. 403.5.1
Clear Width at Turn
..
spaces shall be either a 60 inch (1525 mm) by
815
60 inch (1525 mm) minimum space, or an inter-
section of two walking surfaces which provide a
T-shaped turning space complying with Section
r
304.
(b) Sliding Door
14
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
404.2.4 Maneuvering Clearances at Doors. space at the latch side provided the door is
Minimum maneuvering clearances at doors 44 inches (1120 mm) wide minimum.
shall comply with Sections 404.2.4.1 through
404.2.4.7. 404.2.4.1 Swinging Doors. Swinging
EXCEPTION: Doors to hospital bedrooms doors shall have maneuvering clearances
shall be exempt from the requirement for complying with Table 404.2.4.1.
.!:
E
10
N
I I
I
18 min
445
12 min*
r-,------.,
II
I
II
I
<& II
I.!: 0
010 I I lEN
(OT"""
~ i I roN
~ I ~T"""
I
I I I
lllf1 -----.
t
___
,-------------,
II
I
c€> II
I
,---------------,
I~
I~ I
I
I I I
I .!: 10 I .!: 0
I E N I E ,....
010 ~C")
(OT""" 10 T"""
42 mini
1065 :
---------~--+
(c) Hinge Approach, Pull Side (d) Hinge Approach, Pull Side
Fig. 404.2.4~1
Maneuvering Clearance at Swinging Doors
15
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
*48 min where both closer and latch are provided *54 min where closer is provided
54 min
r
1370 -r - - - - - - -. - - --,
~:
i----------l
~: ~
I <?: I 24 min
c LO ~ .~ ~C\J I I 610
"E 0<0 I I I I
I I I I
I I I I
I I I I
~------ I: i- ----- ---~
i----------l
I~ I
I~ I ~C 10
I 24 min I'E :g
I 610 I C\J
I -.:t
I
--------.
(g) Latch Appr?8Ch, W
*48 min where closer
. Push Slde~ is provided
Fig. 404.2.4.1
Maneuvering Clearance at Swinging Doors (continued)
MINIMUM CLEARANCES
APPROACH DIRECTION PERPENDICULAR TO DOOR1 PARALLEL TO DOOR
From front 48 inches (1220 mm) o inches (0 mm)
From hinge side 42 inches (1065 mm) 54 inches (1370 mm)2
From latch side 42 inches (1065 mm) 24 inches (610 mm)2
1Maneuvering space shall include full width of doorway.
2From the latch side toward the approach direction.
16
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
r---<&---~
r 5~~~n
r----------l
r
i----------l
I I I~ I I /L-,I
I
I
I
I I~ Ie c I ~I
I I I I 'E ~ 'E ~ I 24 min I
I I I
I
I
I
C\I 0
~ 0 I 610 \ I
.------- r~J~~~~
-.:t
I I
I I I
L ~I ----- •
I
--- r - JI
(a) Front Approach (b) Pocket or Hinge Approach (c) Stop or Latch Approach
Fig. 404.2.4.2
Maneuvering Clearance at Sliding and Folding Doors
MINIMUM CLEARANCES
Approach Direction Perpendicular to Doorway1
From front 48 inches (1220 mm)
From side 42 inches (1065 mm)
1Maneuvering space shall include full width of doorway.
48 min 48 min
• •
1220 1220
~ ~
(a)
Fig. 404.2.6
Two Doors in Series
• • (b)
17
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
404.2.7 Door Hardware. Handles, pulls, 60 degrees from the horizontal shall not
latches, locks, and other operable parts on ac- be required to meet the 10 inch (255 mm)
cessible doors shall have a shape that is easy bottom rail height requirement.
to grasp with one hand and does not require 3.. Doors which do not extend to within
tight grasping, pinching, or twisting of the wrist 10 inches (255 mm) of the floor or
to operate. Such hardware shall be 34 inches ground.
(865 mm) minimum and 48 inches (1220 mm)
maximum above the floor or ground. Where 404.2.11 Vision Lites. Doors and sidelites ad-
sliding doors are in the fully open position, oper- jacent to doors containing one or more glazing
ating hardware shall be exposed and usable panE31s that permit viewing through the panels
from both sides. shall have the bottom of at least one panel
EXCEPTION: Locks used only for security 43 inches (1090 mm) maximum above the floor
or ground.
purposes and not used for normal operation
are permitted in any location. 404.3 Alutomatic Doors. Automatic doors and
404.2.8 Closing Speed. automatic gates shall comply with Sections
404.3.1 through 404.3.6. Full powered automatic
404.2.8.1 Door Closers. Door closers shall doors shall comply with ANSI/BHMA A 156.10. Low-
be adjusted so that from an open position of energy and power-assisted doors shall comply with
90 degrees, the time required to move the ANSI/BHMA A 156.19.
door to an open position of 12 degrees shall
be 5 seconds minimum. 404.3.1 Clear Opening Width. Doorways shall
havB a clear opening of 32 inches (815 mm) in
404.2.8.2 Spring Hinges. Door spring power-on and power-off mode. The minimum
hinges shall be adjusted so that from the clear width for automatic door systems shall be
open position of 70 degrees, the door shall basBd on the clear opening' provided by all leafs
move to the closed position in 1.5 seconds in the open position.
minimum, measured under ambient condi-
tions. 404.3.2 Maneuvering Clearances. Clear-
ances at power-assisted doors shall comply
404.2.9 Door-Opening Force. Fire doors shall with Section 404.2.4.
have the minimum opening force allowable by
the appropriate administrative authority. The 404.3.3 Thresholds. Thresholds and changes
maximum force for pushing open or pulling in level at doorways shall comply with Section
404.2.5.
open doors other than fire doors shall be as
follows: 404.3.4 Two Doors in Series. Doors in series
1. Interior hinged door: 5.0 pounds (22.2 N) shaH comply with Section 404.2.6.
2. Sliding or folding door: 5.0 pounds (22.2 N) 404.3.5 Control Switches. Control switches
These forces do not apply to the force required shaH comply with Section 309.
to retract latch bolts or disengage other devices 404.3.6 Signs. Labels and warnings for auto-
that hold the door in a closed position. matic doors shall comply with Section 703.4.
404.2.10 Door Surface. Door surfaces within
10 inches (255 mm) of the floor or ground mea- 405 Ramps
sured vertically shall be a smooth surface on the
405.1 General. Walking surfaces on accessible
push side extending the full width of the door.
routes with a running slope steeper than 1:20 are
Parts creating horizontal or vertical joints in
ramps and shall comply with Section 405.
such surface shall be within 1/16 inch (1.6 mm)
of the same plane as the other. Cavities created 405.2 Sllope. Ramp runs shall have a running slope
by added kick plates shall be capped. not steeper than 1: 12.
EXCEPTIONS: EXCEPTION: Ramps in or on existing buildings
1. Sliding doors. or facilities shall be permitted to have slopes
2. Tempered glass doors without stiles and steepler than 1: 12 complying with Table 405.2
having a bottom rail or shoe with the top WherE! such slopes are necessitated by space
leading edge tapered at no less than limitations.
18
ICC/ANSI A 117.1-1998 Chapter 4. Accessible Routes
405.3 Cross Slope. Cross slope of ramp runs shall 405.7.5 Doorways. Where doorways are adja-
not be steeper than 1:48. cent to a ramp landing, maneuvering clear-
ances required by Sections 404.2.4 and
405.4 Floor or Ground Surfaces. Floor or ground 404.3.2 shall be permitted to overlap the land-
surfaces of ramp runs shall comply with Section ing area.
302.
405.8 Handrails. Ramps with a rise greater than
405.5 Clear Width. The clear width of a ramp run 6 inches (150 mm) shall have handrails complying
shall be 36 inches (915 mm) minimum. with Section 505. Handrails shall not reduce the re-
quired clearances of a ramp run or landing.
405.6 Rise. The rise for any ramp run shall be
30 inches (760 mm) maximum. 405.9 Edge Protection. Edge protection complying
with Section 405.9.1 or 405.9.2 shall be provided on
405.7 Landings. Ramps shall have landings at bot- each side of ramp runs and at each side of ramp
tom and top of each run. Landings shall comply with landings.
Sections 405.7.1 through 405.7.5. EXCEPTIONS:
405.7.1 Slope. Landings shall have a slope not 1. Ramps not required to have handrails where
steeper than 1:48 and shall comply with Section sides complying with Section 406.4 are
302. provided.
2. Sides of ramp landings serving an adjoining
405.7.2 Width. Clear width of landings shall be ramp run or stairway.
at least as wide as the widest ramp run leading 3. Sides of ramp landings having a vertical
to the landing. drop-off of 1/2 inch (13 mm) maximum within
10 inches (255 mm) horizontally of the mini-
405.7.3 Length. Landing length shall be mum landing area.
60 inches (1525 mm) minimum clear.
405.9.1 Extended Floor or Ground Surface.
405.7.4 Change in Direction. Ramps that The floor or ground surface of the ramp run or
change direction at landings shall have a landing shall extend 12 inches (305 mm) mini-
60 inch (1525 mm) minimum by 60 inch (1525 mum beyond the inside face of a railing comply-
mm) minimum landing. ing with Section 505.
r 60 min
1525 r r
60 min
1525
60 min
1525 r
JI landing I ramp run landing ramp run
landing
LO
C\J
LO
(a)
ramp
run
Fig. 405.7
(b)
Ramp Landings
19
Chapter 4. Accessible Routes ICC/ANSI A 117.1-1998
12 min 12 min
305 305
x<4
x < 102
Fig. 405.9
Ramp Edge Protection
405.9.2 Curb or Barrier. A curb or barrier shall sides shall have a slope not steeper than 1: 12. Curb
be provided that prevents the passage of a ramps with returned curbs shall be permitted where
4-inch (102 mm) diameter sphere below a pedestrians would not normally walk across the
height of 4 inches (102 mm). ramp.
405.10 Outdoor Conditions. Outdoor ramps and 406.5 Width. Curb ramps shall be 36 inches (915
approaches to ramps shall be designed so that wa- mm) wide minimum, exclusive of flared sides.
ter will not accumulate on walking surfaces.
406.6 Flloor or Ground Surface. Floor or ground
surfaces of curb ramps shall comply with Section
406 Curb Ramps
302.
406.1 General. Curb ramps on accessible routes
406.7 Lc»cation. Curb ramps and their side flares
shall comply with Section 406.
shall not protrude into vehicular traffic lanes, park-
406.2 Slope. Slopes of curb ramps shall comply ing spac l3s, or into parking space access aisles.
with Section 405.2. 406.8 Obstructions. Curb ramps shall be located
406.3 Counter Slope. Counter slopes of adjoining or protected to prevent their obstruction by parked
gutters and road surfaces immediately adjacent to vehicles.
the curb ramp or accessible route shall not be steep- 406.9 Handrails. Handrails are not required on curb
er than 1:20. Transitions from ramps to walks, gut- ramps.
ters or streets shall be at the same level.
406.10 ILocation at Marked Crossings. Curb
406.4 Sides of Curb Ramps. Where pedestrians ramps at marked crossings shall be wholly con-
must walk across a curb ramp, the ramp shall have tained within the markings, excluding any flared
flared sides. Slope of flares shall not be steeper than sides.
1: 10. Where the width of the walking surface at the
top of the ramp and parallel to the run of the ramp 406.11 Diagonal Curb Ramps. Diagonal or corner-
is less than 48 inches (1220 mm) wide, the flared type curb ramps with returned curbs or other
adjoining surface
maximum slope
Fig. 406.3
Counter Slope of Surfaces Adjacent tCt Curb Ramps
20
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
x < 48
x < 1220
it it 11
v v
I
~r
V
-'r- I
c 0 .-'~
'E C\I
C\I _\
I--CO T""
-.:t
~ '\
~::..
~
"'::..
7
/ J
/
/ ~ '\. /
/ /
I
I ~
""'"
area
/
area
/ I
flared sides 1 :10 max slope flared sides 1 :12 max slope retu rn ed c urb/
(a) (b) (c)
Fig. 406.4
Sides of Curb Ramps
planting
area
48 min 48 min
1220 1220
(a) (b)
Fig. 406.11
Diagonal Curb Ramps
well-defined edges shall have the edges parallel to ramps at both sides, and a level area 48 inches
the direction of pedestrian flow. Bottoms of diagonal (1220 mm) long minimum by 36 inches (915 mm)
curb ramps shall have 48 inches (1220 mm) mini- wide minimum, in the part of the island intersected
mum clear space, measured parallel to the running by the crossing.
slope. Diagonal curb ramps provided at marked
crossings shall provide the minimum clear space
within the markings. Diagonal curb ramps with 407 Elevators
flared sides shall have a segment of straight curb
24 inches (610 mm) long minimum on each side of 407.1 General. Elevators required to be accessible
the curb ramp and within the marked crossing. shall comply with Section 407.2. Destination-
oriented elevators required to be accessible shall
406.12 Islands. Raised islands in crossings shall comply with Section 407.3. Limited use/limited ap-
be cut through level with the street or have curb plication elevators required to be accessible shall
21
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
.
''\ 36 min
/
~ / 915
/
'\ -tr" 48 min
","-
32/36 min
815/915
",'"
I
I
I
:V
I
1220
'"
(Section 403.5) -
/ i\
// ~
..1..1....-----~t~~
(a) (b)
Cut through at Island Curb Ramp at Island
Fig. 406.12
Islands
comply with Section 407.4. Altered elements of ex- 407.2.2 Call Buttons. Call buttons in elevator
isting elevators shall comply with Section 407.5. lobbies and halls shall be 35 inches (890 mm)
minimum and 48 inches (1220 mm) maximum
407.2 Elevators. Elevators shall comply with Sec-
above the floor or ground, measured to the
tions 407.2.1 through 407.2.13 and ASME/ANSI
centBrline of the buttons. A clear floor or ground
A 17.1. They shall be passenger elevators.
space complying with Section 305 shall be pro-
407.2.1 Automatic Operation. Elevator opera- vided. Such call buttons shall have visual sig-
tion shall be automatic. Each car shall be nals to indicate when each call is registered and
equipped with a self-leveling feature that will au- when each call is answered. Call buttons shall
tomatically bring and maintain the car at floor be 3/4 inch (19 mm) minimum in their smallest
landings within a tolerance of 1/2 inch (13 mm) dimension. The button that designates the up
under rated loading to zero loading conditions. direction shall be above the button that
I J I I
I I I I
Fig. 407.2.2 Fig. 407.2.3.2.1
Elevator Call Buttons Height of Elevator Visible Signals
22
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
designates the down direction. Buttons shall be measured from the baseline of the characters.
raised or flush. Objects beneath hall call buttons A tactile star shall also be provided on both
shall protrude 1 inch (25 mm) maximum. jambs at the main entry level. Such characters
shall be 2 inches (51 mm) high and shall comply
407.2.3 Hall Signals. A visible and audible sig- with Section 703.2.
nal shall be provided at each hoistway entrance
to indicate which car is answering a call and the
direction of travel, except that signals in cars,
visible from the floor area adjacent to the hall
call buttons, and complying with the require-
*1~
ments of this subsection, shall be permitted.
~--+O V
Calls. The minimum acceptable time from noti-
fication that a car is answering a call until the
door starts to close shall be calculated by the
following equation, but shall not be less than
Fig. 407.2.3.2.2 5 seconds:
Size of Elevator Visible Signals
T = 0/1 .5 ft/s (0/455 mm/s)
407.2.3.2.3 Visibility. Signals shall be where T = total time in seconds and 0 = dis-
visible from the floor area adjacent to tance in feet (millimeters) from the point in the
the hall call button. lobby or corridor 60 inches (1525 mm) directly
in front of the farthest call button controlling that
407.2.4 Tactile Characters on Hoistway En- car to the centerline of its hoistway door. For
trances. Tactile character and Braille floor des- cars with in-car signals, T begins when the sig-
ignations shall be provided on both jambs of nal is visible from the point 60 inches (1525 mm)
elevator hoistway entrances and shall be directly in front of the farthest hall call button and
60 inches (1525 mm) above the floor or ground, the audible signal is sounded.
23
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
407.2.7 Door Delay for Car Calls. Elevator 407 . 2.8 Inside Dimensions of Elevator Cars.
doors shall remain fully open in response to a The clear width of elevator doors and the inside
car call for 3 seconds minimum. dimensions of elevator cars shall comply with
Table 407.2.8.
42 min
1065
(a) Centered Door Location (b) Off-Centered Door Location
54 min
24
ICC/ANSI A117.1-1998 Chapter 4. Accessible Routes
407.2.9 Floor Surfaces. Floor surfaces in ele- phone keypad arrangement, buttons shall
vator cars shall comply with Section 302. The be arranged with numbers in ascending
horizontal clearance between the edge of the order. Where two or more columns of but-
car platform sill and the edge of the landing sill tons are provided they, shall read from left
shall be 11/4 inches (32 mm) maximum. to right.
407.2.10 Illumination Levels. The level of illu- 407.2,.11.2 Button Designations. Except
mination at the car controls, platform, and car where provided in a standard telephone
threshold and landing sill shall be 5 footcandles keypad arrangement, control buttons shall
(54 lux) minimum. be identified by tactile characters comply-
ing with Section 703.2. Tactile characters
407.2.11 Car Controls. Elevator controls shall and Braille shall be placed immediately to
comply with Sections 407.2.11.1 through the left of the button to which they apply.
407.2.11.4. The control button for the main entry floor,
407.2.11.1 Buttons. Buttons shall be and control buttons other than remaining
3/4 inch (19 mm) minimum in their smallest buttons with floor designations, shall be
dimension. Buttons shall be raised or flush. identified with tactile symbols complying
Except where provided in a standard tele- with Table 407.2.11.2. Buttons with floor
designations shall be provided with visible
indicators to show that a call has been reg-
istered. The visible indication shall extin-
guish when the car arrives at the desig-
3/4 min nated floor.
19
Telephone-style keypads shall be in a
standard telephone keypad arrangement,
and shall be identified by characters com-
plying with Section 703.4. The number five
key shall have a single raised dot. The dot
shall be 0.11B inch (3 mm) to 0.120 inch
(3.05 mm) base diameter and in other as-
pects comply with Table 703.5. Characters
shall be centered on the corresponding
raised~or
flush
keypad button. A display shall be provided
...-----------,1 in the car with visible indicators to show reg-
~~------~ ! I istered car destinations. The visible indica-
tion shall extinguish when the car arrives at
the designated floor. A standard five-
Fig. 407.2.11.1 pOinted star shall be used to indicate the
Elevator Car Control Buttons main entry floor.
25
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
Proportions
Open circles indicate
Control Button Tactile Symbol Brailll~ Message
unused dots within each
Braille Cell
II ~ ~.. I..~~Em~~~
+
~.--- :
• • ••• •
• • •
I •••
. 0 • • 00
0 • • 0 .0
DOOR OPEN OIP"EN" .0 .0 o•
• • ••• •
• •••• •
• • •
REAR/SIDE DOOR OPEN
• • •
REAR/SliDE OP"EN"
• . 0 • • 00
o • • 0 .0
. 0 . 0 O.
.. ..•• ••..•
•
DOOR CLOSE
•
•• •• • • • • • •
•• •
CLOSE
•• •• • • • • • •
•
• • • 0 . 0 O • •0
00 . 0 oe . 0
00 . 0 . 0 . 0 00
O.
· ..•••.
•• ••
••
REAR/SIDE DOOR CLOSE
•• •
REAR/SIDE CLOSE •
• • • 0 . 0 O • •0
00 . 0 oe .0
00 . 0 . 0 .0 00
O.
*
•••
•
MAIN
•
e
*
•• •
• MA"IN"
• •
• • • • 0 00
00 00 O.
. 0 00 eo
••: • ••
ALARM
...
• •• •• ••
• • •
AL"AR"M •.0 .0 O • • •
00 .0 O. 00
00 . 0 8 0 eo
c c ••• • • ••
:•• •.....
PHONE
e • ••
•
PH"ONE"
••• eo 00 .0
eo •• oe O.
eo 0000 eo
•••.e:••
EMERGENCY STOP
(WHEN PROVIDED)
X on face of octagon is not
required to be tactile "ST"OP
• oe .0 ••
00 O • •0
.0 .0 .0
26
ICC/ANSI A 117.1-1998 Chapter 4. Accessible Routes
407.2.11.3 Height. Buttons with floor des- be limited to voice communication. If instruc-
ignations shall be 48 inches (1220 mm) tions for use are provided, essential information
maximum above the floor or ground. Emer- shall be presented in both tactile and visual form
gency controls, including the· emergency complying with Section 703.
alarm, shail be grouped at the bottom of the
panel. Emergency control buttons shall 407.3 New Destination-Oriented Elevators. Des-
have their centerlines 35 inches (890 mm) tination-oriented elevators shall also comply with
minimum above the floor or ground. Sections 407.3.1 through 407.3.6 and 407.2.13.
Such elevators shall also comply with Sections
EXCEPTION: Where the elevator
407.3.1 through 407.3.6 and ASME/ANSI A17.1.
serves more than 16 openings and par-
They shall be passenger elevators.
allel approach is provided, buttons with
floor designations shall be 54 inches 407.3.1 Call Buttons. Call buttons shall be
(1370 mm) maximum above the floor or 35 inches (890 mm) minimum and 48 inches
ground. (1220 mm) maximum above the floor or ground,
measured to the centerline of the buttons. A
407.2.11.4 Clear Floor or Ground Space. clear floor or ground space complying with Sec-
A clear floor or ground space complying tion 305 shall be provided. Call buttons shall be
with Section 305 shall be provided at 3/4 inch (19 mm) minimum in their smallest di-
controls.
mension. Buttons shall be raised or flush. Ob-
jects beneath hall call buttons shall protrude
407.2.12 Car Position Indicators. In elevator
1 inch (25 mm) maximum into the clear floor or
cars, both audible and visible indicators shall be
ground space. Destination-oriented elevator
provided to identify the floor location of the car.
. systems shall have a keypad or other means for
407.2.12.1 Visible Indicators. Indicator the entry of destination information. Keypads, if
shall be above the car control panel or provided, shall be in a standard telephone key-
above the door. Numerals shall be 1/2 inch pad arrangement, and shall be identified by
(13 mm) high minimum. As the car passes characters complying with Section 703.4. The
or stops at a floor served by the elevator, the number five key shall have a single raised dot.
corresponding character shall illuminate. The dot shall be 0.118 inch (3 mm) to 0.120 inch
(3.05 mm) base diameter, and in other aspects
407.2.12.2 Audible Indicators. The audi- comply with Table 703.5. Destination-oriented
ble signal shall be 10 dBA minimum above elevator systems shall be provided with visual
ambient, but shall not exceed 80 dBA maxi- and audible signals which indicate which eleva-
mum, measured at the annunciator. The tor car to enter. Characters shall be centered on
signal shall be an automatic verbal an- the' corresponding keypad button. A display
nouncement which announces the floor at shall be provided in the car with visible indica-
which the car has stopped. tors to show registered car destinations. The
visible indication shall extinguish when the car
EXCEPTION: For elevators that have a arrives at the designated floor. A standard five-
rated speed of 200 fpm (1 m/s) or less, pOinted star shall be used to indicate the main
an audible signal with a frequency of entry floor.
1500 Hz maximum which sounds as the
car passes or stops at a floor served by 407.3.2 Hall Signals. A visible and audible sig-
the elevator shall be permitted. nal shall be provided to indicate a car destina-
tion corresponding with Section 407.3.1. The
407.2.13 Emergency Communications. audible tone and verbal announcement shall be
Emergency two-way communication systems the same as those given at the call button or call
between the elevator car and a point outside the button keypad, if provided. Each elevator in a
hoistway shall comply with ASME/ANSI A 17.1. bank shall have audible and visual means for
The highest operable part of a two-way commu- differentiation.
nication system shall comply with Section
308.3. If the device is in a closed compartment, 407.3.2.1 Visible Signals. Visible signals
the compartment door hardware shall comply shall comply with Sections 407.3.2.1.1
with Section 309. Tactile symbols and charac- through 407.3.2.1.3.
ters complying with Section 703.2 shall be pro-
vided adjacent to the device. If the system uses 407.3.2.1.1 Height. Hall signal fixtures
a handset, the cord from the panel to the hand- shall be 72 inches (1830 mm) minimum
set shall be 29 inches (735 mm) long minimum. above the floor or ground, measured to
The car emergency signaling device shall not the centerline of the fixture.
27
Chapter 4. Accessible Routes ICC/ANSI A117.1-1998
407.3.2.1.2 Size. The visible signal ele- be 2 inches (51 mm) high and shall comply with
ments shall be 21/2 inches (64 mm) Section 703.2.
minimum in their smallest dimension.
407.3.6 Door and Signal Timing for Hall
407.3.2.1.3' Visibility. Signals shall be Call:s. The minimum acceptable time from noti-
visible from the floor area adjacent to ficat~on of the car assigned at the keypad until
the hOistway entrance. the door starts to close shall be calculated by
the following equation, but shall not be less than
407.3.3 Car Controls. Emergency controls, in- 5 seconds: .
cluding the emergency alarm,· shall have their
centerlines 35 inches (890 mm) minimum and T = D/1.5 ft/s (D/455 mm/s)
48 inches (1220 mm) maximum above the floor
or ground. Buttons shall be 3/4 inch (19 mm) where T = total time in seconds' and D = dis-
minimum in their smallest dimension. Buttons tanoe in feet (millimeters) from the keypad to the
shall be raised or flush. Controls shall accom- cent,erline of the assigned hoistway door.
modate a forward reach or side reach comply-
ing with Section 308. 407.4 L.imited-Use/Limited-Application Eleva-
tors. Limited-use/limited-application elevators shall
407.3.4 Car Position Indicators. In elevator , comply with Sections 407.4.1 through 407.4.10 and
cars, audible and visible car location indicators ASME/ANSI A 17.1, Part XXV.
shall be provided.
407.4.1 Automatic Operation. Elevator opera-
407.3.4.1 Visible Indicators. Indicators tion shall be automatic. Each car shall automati-
shall be above the car control panel or, cally stop at a floor landing within a tolerance of
above the door. Numerals shall be 1/2 inch 1/2 inch (13 mm) under rated loading to zero
(13 mm) high minimum. The visible indica- loading conditions.
tors shall extinguish when the car arrives at
the designated floor. 407.4.2 Call Buttons. Call buttons. in elevator
lobbies and halls shall be 35 inches (890 mm)
407.3.4.2 Audible Indicators. An auto- minimum and 48 inches (1220 'mm) maximum
matic verbal announcement which an- above the floor or ground, measured to the
nounces the floor at which the car has centl3rline of the buttons. Such call buttons shall
stopped shall be provided. The announce- haVE! visual signals to indicate when each call is
ment shall be 10 dBA minimum above am- registered and when each call is answered. Call
bient and 80 dBA maximum, measured at buttons shall be 3/4 inch (19 mm) minimum in
the annunciator. , their smallest dimension, and shall be raised or
flush. The button that designates the up direc-
407.3.5 Elevator Car Identification. In addi- tion shall be above the button that designates
tion to the tactile signs required by Section the down direction. Objects beneath hall call
407.2.4, a tactile elevator car identification shall buttons shall protrude 1 inch (25 mm)
be placed immediately below the hoistway en- maximum.
trance floor designation. The characters'shall
407.4.3 Hall Signals. A visible and audible sig-
nal complying with Section 407.2.3 shall be pro-
vided in. the car or at the hoistway entrance to
indicate the direction of travel.
28
ICC/ANSI A117.1-1998 Ch~pter 4. Accessible Routes
15 feet 2 min
1.35 m2
32 min
815
J J 32 min l
815
(a) New Construction (b) Existing Buildings
Fig. 407.4.6
Inside Dimensions of Limited Use/limited Applicatjon (lULA) Elevator Cars
cally. Horizontally sliding type hoistway and car 407.4.8 Illumination levels. The level of illu-
doors shall comply with Section 407.2.5. Swing- mination at the car controls, platform, and car
ing hOistway and car doors shall comply with threshold and landing sill shall be 5 footcandles
Section 404. Swinging doors shall be low ener- (54 lux) minimum.
gy power-operated and shall comply with ANSI/
BHMA A 156.19. POwer operated swinging 407.4.9 Car Controls. Elevator car controls
doors shall remain open for 20 seconds mini- shall comply with Sections 407.4.9.1 through
mum when activated. 407.4.9.4.
407.4.9.1 Buttons. Control buttons shall
407.4.6 Inside Dimensions of Elevator Cars. be 3/4 inch (19 mm) minimum in their small-
Elevator cars shall provide a clear width of est dimension. Control buttons shall be
42 inches (1065 mm) minimum and a clear raised or flush. Control buttons shall be ar-
depth of 54 inches (1370 mm) minimum. Car ranged with numbers in ascending order.
doors shall be positioned at the narrow end(s)
of the car and shall provide a clear width of 407.4.9.2 Identification. Control buttons
32 inches (815 mm) minimum. shall be identified by tactile characters
complying with Section 703.2. Tactile char-
EXCEPTION: For installations in existing acters shall be placed immediately to the
buildings, elevator cars shall provide a clear left of the button to which they apply. The
width of 36 inches (915 mm) minimum, a control button for the main entry floor shall
clear depth of 54 inches (1370 mm) mini- be identified with a tactile symbol complying
mum, and a net clear platform area of 15 with Table 407.2.11.2. Buttons with floor
square feet (1.35 m2) minimum. designations shall be provided with visible
indicators to show that a call has been reg-
407.4.7 Floor lOr Ground Surfac"es. Floor or
istered. The visible indication shall extin-
ground surfaces in elevator cars shall comply guish· when the car arrives at the desig-
with Section 302. The horizontal distance be-
nated floor.
tween the car platform sill and the edge of any
hoistway landing shall be 11/4 inches (32 mm) 407.4.9.3 Height. Buttons with floor desig-
maximum. " nations shall be 48 inches (1220 mm) maxi-
29
Chapter 4. Accessible Routes ICC/ANSI A 117.1-1998
mum above the floor. Emergency controls, that in-car signals complying with Section
including the emergency alarm, shall be 407 . 2.3 shall be permitted. Audible signals shall
grouped at the bottom of the panel. Emer- sound once for the up direction and twice for the
gency control buttons shall have their cent- down direction, or shall have verbal annuncia-
erlines 35 inches (890 mm) minimum tors that state the word "up" or "down." If new
above the floor. hall signals are provided, they shall comply with
Section 407.2.3.
407.4.9.4 Location. Controls shall be on a
side wall and a clear floor or ground space 407.5.4 Doors. Doors shall comply with Section
complying with Section 309.2 shall be 407.5.4.1 or 407.5.4.2.
provided.
407.5.4.1 Power Operated Doors. Power
407.4.10 Emergency Communications. operated horizontally sliding car and hoist-
Emergency two-way communication systems way doors opened and closed by automatic
between the elevator car and a point outside the means shall comply with Section 407.2.5.
hoistway shall comply with ASME/ANSI A17.1.
407.5.4.2 Manually Operated Doors. Ex-
The highest operable part of a two-way commu-
iisting manually operated hoistway swing-
nication system shall comply with Section
ing doors shall comply with Sections
308.3. If the device is in a closed compartment,
404.2.3 and 404.2.9. A power operated car
the compartment door hardware shall comply
door that opens and maintains a
with Section 309. Tactile symbols and charac-
:32 inch (815 mm) minimum clear width shall
ters complying with Section 703.2 shall be pro-
be provided. Closing of the car door shall
vided adjacent to the device. If the system uses
not be initiated until the hoistway door is
a handset, the cord from the panel to the hand-
closed. Car gates are prohibited.
set shall be 29 inches (735 mm) long minimum.
The car emergency Signaling device shall not 407.5.5 Inside Dimension of Elevator Cars.
be limited to voice communication. If instruc- The inside dimension of elevator cars shall
tions for use are provided, essential information comply with Section 407.2.8.
shall be presented in both tactile and visual form
EXCEPTION: Existing car configurations
complying with Section 703.
that provide a clear floor area of 16 square
407.5 Existing Elevators. Accessible elements of feet (1.45 m2) minimum, and provide
existing elevators shall comply with Sections 407.5, 48 inches (1220 mm) minimum inside clear
407.2.4, 407.2.6, 407.2.7, 407.2.9, 407.2.10, and depth and a 36 inch (915 mm) minimum
407.2.13. They shall be passenger elevators as clear width.
classified by ASME/ANSI A 17.1. 407.S.6 Car Controls. Elevator controls shall
EXCEPTION: Destination-oriented elevators comply with Sections 407.5.6.1 through
which comply with Section 407.3. 407.~5.6.4.
407.5.1 Automatic Operation. Elevator opera- 407.5.6.1 Buttons. Car control buttons
tion shall be automatic. Each car shall be shall be 3/4 inch (19 mm) minimum in their
equipped with a self-leveling feature that will au- smallest dimension. Control buttons shall
tomatically bring and maintain the car at floor be raised, flush or recessed. Where the car
landings within a tolerance of 1/2 inch (13 mm) operating panel is changed, control buttons
under rated loading to zero loading conditions. shall comply with Section 407.2.11.1.
407.5.2 Call Buttons. Call buttons in elevator 407.5.6.2 Designations and Indicators
lobbies shall be 35 inches (890 mm) minimum for Control Buttons. All control buttons
and 48 inches (1220 mm) maximum above the shall comply with Section 407.2.11.2.
floor or ground, measured to the centerline of EXCEPTION: Where existing car oper-
the button, where the appropriate floor or ating panel construction precludes locat-
ground area complying with Section 305 is pro- ing tactile markings to the left of the con-
vided. The button that designates the up direc- trols, markings shall be placed as near to
tion shall be above the button that designates the control as possible.
the down direction. Keypad controls complying
with Section 407.2.2 shall be permitted. 407.5.6.3 Height. All buttons with floor des-
ignations shall be 54 inches (1370 mm)
407.5.3 Hall Signals. A visible and audible sig- maximum above the floor for parallel ap-
nal shall be provided at each hoistway entrance proach and 48 inches (1220 mm) maximum
to indicate which car is answering a call, except above the floor for forward approach.
30
ICC/ANSI A 117.1-1998 Chapter 4. Accessible Routes
16 feet2 min
1.45 m2
I I
! I
32 min
815
Where the panel is changed, it shall comply 408 Wheelchair (Platform) Lifts
with Section 407.2.11.3.
407.5.6.4 Operating Panels. Where a new 408.1 General. Wheelchair (platform) lifts shall
car operating panel complying with the re- comply with ASME/ANSI A17.1 and with Sections
quirements of Section 407.2.11 is provided, 302, 305, and 309. Wheelchair (platform) lifts shall
existing car operating panels not complying not be attendant-operated and shall provide unas-
with Section 407.2.11 are not required to be sisted entry and exit from the lift.
removed.
408.2 Doors and Gates. Lifts shall have low energy
407.5.7 Car Position Indicators. Where a new power-operated doors or gates complying with Sec-
car position indicator is provided, the indicator tion 404.3. Doors and gates shall remain open for
shall comply with Section 407.2.12. 20 seconds minimum. End doors shall be 32 inches
(815 mm) minimum clear width. Side doors shall be
407.5.8 Identification. Elevators that comply
with Section 407.5 shall be clearly identified 42 inches (1065 mm) minimum clear width.
with the International Symbol of Accessibility EXCEPTION: Lifts having doors or gates on
complying with Section 703.7, unless all eleva- opposite sides shall be permitted to have manual
tors in the building are accessible. doors or gates.
31
.. }'
32
ICC/ANSI A117.1-1998 Chapter 5. General Site and Building Elements
33
Chapter 5. General Site and Building Elements ICC/ANSI A117.1-1998
~ ~
~ Q)
()
~
~ ~
al
c..
rn
~ ~
Ol
c
:i:
~ Cii
~
~ -c..
0
..c
"5l
~
~ ~
c ~
~ ~ ~
~
Fig. 502.3
Parking Space Access Aisle
60 min
1525
Fig. 503.3
Passenger Loading Zone Access Aisle
504 Stairways
----±·7
102-1.80
504.1 General. Accessible stairs shall comply with
Section 504.
34
ICC/ANSI A117.1-1998 Chapter 5. General Site and Building Elements
504.3 Open Risers. Open risers shall not be per- 505.2 Location. Handrails shall be provided on
mitted. both sides of stairs and ramps.
504.4 Tread Surface. Stair treads shall comply with EXCEPTION: Aisle stairs and aisle ramps pro-
Section 302. vided with a handrail either at the side or within
the aisle width.
504.5 Nosings. The radius of curvature at the lead-
ing edge of the tread shall be 1/2 inch (13 mm) maxi-
mum. Nosings that project beyond risers shall have 505.3 Continuity. Handrails shall be continuous
the underside of the leading edge curved or bev- within the full length of each stair flight or ramp run.
eled. Risers shall be permitted to slope under the Inside handrails on switchback or dogleg stairs or
tread at an angle of 30 degrees maximum from verti- ramps shall be continuous between flights or runs.
cal. The permitted projection of the nosing shall be Other handrails shall comply with Sections 505.10
11/2 inches (38 mm) maximum beyond the tread and 307.
below. !
EXCEPTION: Handrails in aisles serving
seating.
504.6 Handrails. Stairs shall have handrails com-
plying with Section 505.
505.4 Height. Top of gripping surfaces of handrails
504.7 Outdoor Conditions. Outdoor stairs and shall be 34 inches (865 mm) minimum and
outdoor approaches to stairs shall be designed so 38 inches (965 mm) maximum vertically above stair
that water will not accumulate on walking surfaces. nosings and ramp surfaces. Handrails shall be at a
consistent height above stair nosings and ramp sur-
505 Handrails faces.
curved
Fig. 504.5
Stair Nosings
35
Chapter 5. General Site and Building Elements ICC/ANSI A117.1-1998
505.6 Gripping Surface. Gripping surfaces shall 505.7 Cross Section. Handrails shall have a circu-
be continuous, without interruption by newel posts, lar cross section with an outside diameter of 11/4
other construction elements, or obstructions. inch (32 mm) minimum and 2 inches (51 mm) maxi-
mum, or shall provide equivalent graspability com-
EXCEPTION: Handrail brackets or balusters at- plying with Section 505.7.1.
tached to the bottom surface of the handrail shall
not be considered obstructions provided they 505.7.1 Non-Circular Cross Sections. Hand-
comply with the following criteria: rails with other shapes shall be permitted pro-
1) not more than 20 percent of the handrail vided they have a perimeter dimension of
length is obstructed, 4 inches (102 mm) minimum and 61/4 inches
(160 mm) maximum, and provided their largest
2) horizontal projections beyond the sides of
cross-section dimension is 21/4 inches (57 mm)
the handrail occur 21/2 inches (64 mm) mini-
maximum.
mum below the bottom of the handrail, and
3) edges have a 1/8 inch (3.2 mm) minimum 505.8 Surfaces. Handrails, and any wall or other
radius. surfaces adjacent to them, shall be free of any sharp
36
ICC/ANSI A117.1-1998 Chapter 5. General Site and Building Elements
12 min
IL
/
12 min
305
Jr
~
- I .... ·······4
1 - ..-- - r---
CJ
,-
[0
-
- - --- -->
L----
,[
L---
r I
I r I
I
Fig. 505.10.1
Top and Bottom Handrail Extensions at Ramps
37
Chapter 5. General Site and Building Elements ICC/ANSI A117.1-1998
505.10.1 Top and Bottom Extension at surface, or shall be continuous to the handrail of
Ramps. Ramp handrails shall extend horizon- an adjacent stair flight.
tally 12 inches (305 mm) minimum beyond the
top and bottom of ramp runs. Such extension 506 Windows
shall return to a wall, guard, or the walking sur- Accessible windows shall have operable parts com-
face, or shall be continuous to the handrail of an - plying with Section 309 ..
adjacent ramp run.
505.10.2 Top Extension at Stairs. At the top of 507 Bus Stop Pads
a stair flight, handrails shall extend horizontally
above the landing for 12 inches (305 mm) mini- 507.1 General. Where a bus stop pad is provided at
mum beginning directly above the first riser nos- bus stops, bays, or other areas where a lift or ramp
ing. Such extension shall return to a wall, guard, is to be deployed, it shall comply with Section 507.
or the walking surface, or shall be continuous to 507.2 Surface. The pad shall have a firm, stable
the handrail of an adjacent stair flight. surface.
505.10.3 Bottom Extension at Stairs. At the 507.3 Size. The minimum clear length shall be
bottom of a stair flight, handrails shall extend at 96 .inches (2440 mm), measured perpendicular
the slope of the stair flight for a horizontal dis- from the curb or edge of the vehicle roadway. The
tance equal to one tread depth beyond the last minimum clear width shall be 60 inches (1525 mm),
riser nosing. Such extension shall continue with measured parallel to the curb or edge of the vehicle
a horizontal extension or shall be continuous to roadway.
the handrail of an adjacent stair flight or shall re-
turn to a wall, guard, or the walking surface. If 507.4 Slope. The slope of the pad parallel to the
provided at the bottom of a stair flight, a horizon- roadway shall be the same as the roadway. The
tal extension of a handrail shall be 12 inches slope of the pad perpendicular to the roadway shall
(305 mm) long minimum and a height equal to not be steeper than 1:48.
that of the sloping portion of the handrail as
measured above the stair nosings. Such exten- 507.5 L.ocation. Pads shall adjoin an accessible
sion shall return to a wall, guard, or the walking route complying with Sections 307 and 402.
38
ICC/ANSI A 117.1-1998 Chapter 6. Plumbing Elements and Facilities
601 General
39
Chapter 6. Plumbing Elements and Facilities ICC/ANSI A117.1-1998
603.2.3 Doors. Doors shall not swing into the or obstructions shall be within the water closet
clear floor or ground space or clearance for any clearance.
fixture.
604.3.2 Overlap. The clearance around the wa-
EXCEPTION: Where the room is for indi- ter closet shall be permitted to overlap the fix-
vidual use and a clear floor or ground space ture, associated grab bars, tissue dispensers,
complying with Section 305.3 is provided accessible routes, and clear floor or ground
within the room, beyond the arc of the door space, or clearances at other fixtures and the
swing. wheelchair turning .space.
603.3 Mirrors. Mirrors shall be mounted with the 604.4 Height. The top of water closet seats shall be
bottom edge of the reflecting surface 40 inches 17 inches (430 mm) minimum and 19 inches (485
(1015 mm) maximum above the floor or ground. mm) maximum above the floor or ground. Seats
shall not return automatically to a lifted position.
603.4 Coat Hooks and Shelves. Coat hooks pro-
vided within toilet rooms shall accommodate a for- 604.5 Grab Bars. Grab bars for water closets shall
ward reach or side reach complying with Section comply with Section 609. Grab bars shall be pro-
308. Where provided, a fold-down shelf shall be vided on the rear wall and on the side wall closest
40 inches (1015 mm) minimum and 48 inches (1220 to the water closet.
mm) maximum above the floor or ground. 604.5.1 Side Wall. Side wall grab bar shall be
42 inches (1065 mm) long minimum, 12 inches
604 Water Closets and Toilet Compartments (305 mm) maximum from the rear wall and
extending 54 inches (1370 mm) minimum from
604.1 General. Accessible water closets and toilet the rear wall.
compartments shall comply with Section 604.
o
mm) maximum from the side wall or partition, except
I
that the water closet shall be centered in the ambu-
latory accessible compartment specified in Section I
604.8.2. I
I
604.3 Clearance. . I
I
604.3.1 Size. Clearance around the water clos-
et shall be 60 inches (1525 mm) minimum, mea-
I
L _________ _
sured perpendicular from the side wall, and
56 inches (1420 mm) minimum, measured per-
pendicular from the rear wall. No other fixtures l
II
60 min
1525
~
Fig. 604.3.1
Size .of Clearance for Water Closet
e::=:::==============:»
17-19
430-485
405-455
40
ICC/ANSI A 117.1-1998 Chapter 6. Plumbing Elements and Facilities
54 min 36 min*
12 max 1370 915
305
42 min
1065
:::::=================:3
transfer
side I I======!==~ I
*36 inches (915 mm)
minimum when wall
space permits
12 min
305
o ~ 0
co E C\I
C\I
ct)
COT""
V
.180-230 180-230
(a) Below Grab Bar (b) Above Grab Bar
Fig. 604.7
Dispenser Location
604.5.2 Rear Wall. The rear wall grab bar shall be of a type that control delivery, or that do not allow
be 24 inches (610 mm) long minimum, centered continuous paper flow.
on the water closet. Where space permits, the
bar shall be 36 inches (915 mm) long minimum, 604.8 Toilet Compartments. Accessible toilet
with the additional length provided on the trans- compartments shall comply with Sections 604.8.1
fer side of the water closet. through 604.8.5. Compartments containing more
than one plumbing fixture shall comply with Section
604.6 Flush Controls. Flush controls shall be hand 603. Water closets in accessible toilet compart-
operated or automatic. Hand-operated flush con- ments shall comply with Sections 604.1 through
trols shall comply with Section 309. 604.7.
604.7 Dispensers. Toilet paper dispensers shall 604.8.1 Wheelchair Accessible Compart-
comply with Section 309.4 and shall be 7 inches ments.
(180 mm) minimum and 9 inches (230 mm) maxi-
mum in front of the water closet. The outlet of the 604.8.1.1 Size. Wheelchair accessible
dispenser shall be 15 inches (380 mm) minimum compartments shall be 60 inches (1525
and 48 inches (1220 mm) maximum above the floor mm) wide minimum measured perpendicu-
or ground. There shall be a clearance of 11/2 inches lar to the side wall, and 56 inches (1420
(38mm) minimum below and 12 inches (305 mm) mm) deep minimum for wall hung water
minimum above the grab bar. Dispensers shall not closets and 59 inches (1500 mm) deep
41
Chapter 6. Plumbing Elements and Facilities ICC/ANSI A 117.1-1998
44
mJ
r 1
I I
I
I I
c 0
I I
c
'E C\I I 'E
co -.:t I 0)
L{)
T"" I I L{)
I I
I I
I
!=-------
~ 60 min
1525
60 min
1525
(a) Wall-Hung Water Closet (b) Floor-Mounted Water Closet
Fig. 604.8.1.1
Wheelchair Accessible Toilet Compartments
partition
I
I
6min I
150 I
I
I
I
I
I 6 max
9min I
__:Y
150
J
230 ---~
150
(a) Elevation
(b) Plan
Fig. 604.8.1.4
Toilet Compartment Toe Clearance
minimum for floor mounted water closets, 604.8.1.4 Toe Clearance. In wheelchair
measured perpendicular to the rear wall. accessible compartments, the front parti-
tion and at least one side partition shall pro-
vide a toe clearance complying with Section
604.8.1.2 Doors. Compartment doors shall
306.2 and extending 6 inches (150 mm)
not swing into the minimum required
deep beyond the compartment-side face of
compartment area.
the partition, exclusive of partition support
members. Toe clearance at the front of the
604.8.1.3 Approach. Compartment ar- partition is not required in a compartment
rangements shall be permitted for left-hand greater than 62 inches (1575 mm) deep
or right-hand approach to the water closet. with a wall-hung water closet or 65 inches
42
ICC/ANSI A117.1-1998 Chapter 6. Plumbing Elements and Facilities
(1650 mm) deep with a floor-mounted wa- 604.8.4.2 Ambulatory Accessible Com-
ter closet. Toe clearance at the side parti- partments. A side-wall grab bar complying
tion is not required in a compartment great- with Section 604.5.1 shall be provided on
er than 66 inches (1675 mm) wide. both sides of the compartment.
604.8.2 Ambulatory Accessible Compart- 604.8.5 Coat Hooks and Shelves. Coat hooks
ments. Ambulatory accessible compartments provided within toilet compartments shall be 48
shall be 60 inches (1525 mm) deep minimum inches (1220 mm) maximum above the floor or
and 36 inches (915 mm) wide. Compartment ground. Where provided, a fold-down shelf shall
doors shall not swing into the minimum required be 40 inches (1015 mm) minimum and 48 inch-
compartment area. es (1220 mm) maximum above the floor or
ground.
604.8.3 Doors. Toilet compartment doors shall
comply with Section 404, except that if the ap- 605 Urinals
proach is to the latch side of the compartment
605.1 General. Accessible urinals shall comply with
door, the clearance between the door side of the
Section 605.
compartment and any obstruction shall be
42 inches (1065 mm) minimum. The door shall 605.2 Height. Urinals shall be of the stall type or
be hinged 4 inches (102 mm) maximum from shall be of the wall-hung type with the rim at
the adjacent wall or partition farthest from the 17 inches (430 mm) maximum above the floor or
water closet. The door shall be self-closing. A ground.
door pull complying with Section 404.2.7 shall
be placed on both sides of the door near the 605.3 Clear Floor or Ground Space. A clear floor
latch. or ground space complying with Section 305 posi-
tioned for forward approach shall be provided.
605.4 Flush Controls. Flush controls shall be hand
operated or automatic. Hand-operated flush con-
trols shall comply with Section 309.
43
Chapter 6. Plumbing Elements and Facilities ICC/ANSI A117.1-1998
G---)
"'0
c:
Q)
'0
._~.-=: - - - - - --I -
0
1,-·_·---.. ., I 1,-·_·---. .,
Ii ) i I Ii·) !
I . I I . I
Ii J i I II J i
1'-·_·--· ) I 1'-·_·--· )
L':':::·~~ _______ -.1----'1. L-=·=--__________ _
j, length of tub 1 length of tub
44
ICC/ANSI A 117.1-1998 Chapter 6. Plumbing Elements and Facilities
1~~===============:::::21
)
~
'0
C
Q)
Q) E T""
_ V (0 '0
a3
_v(O
ON Q) o N
.E £ .E
~.~~
N('I)
T""
long minimum and shall be 24 inches width of the bathtub. Controls shall comply with Sec-
(610 mm) maximum from the head end wall tion 309.4.
and 12 inches (305 mm) maximum from the
foot end wall. 607.6 Shower Unit. A shower spray unit shall be
provided, with a hose 59 inches (1500 mm) long
607.4.2.2 Foot End Wall. A grab bar minimum, that can be used as a fixed shower head
24 inches (610 mm) long minimum shall be and as a hand-held shower. If an adjustable-height
provided on the foot end wall at the front shower head on a vertical bar is used, the bar shall
edge of the bathtub. not obstruct the use of grab bars.
607.4.2.3 Head End Wall. A grab bar 607.7 Bathtub Enclosures. Bathtub enclosures
12 inches (305 mm) long minimum shall be shall not obstruct controls or transfer from wheel-
provided on the head end wall at the front chairs onto bathtub seats or into bathtubs. Bathtub
edge of the bathtub. enclosures shall not have tracks on the rim of the
bathtub.
607.5 Controls. Controls, other than drain stop-
pers, shall be on an end wall. Controls shall be be- 608 Shower Compartments
tween the bathtub rim and grab bar, and between
the open side of the bathtub and the mid-point of the 608.1 General. Accessible shower compa'rtments
shall comply with Section 608.
608.2 Size and Clearances.
608.2.1 Transfer-Type Shower Compart-
end ments. Transfer-type shower compartments
<£ wall shall be 36 inches (915 mm) wide by 36 inches
(915 mm) deep inside finished dimension, mea-
sured at the centerpoint of opposing sides, and
shall have a minimum 36 inches (915 mm) wide
entry on the face of the shower compartment.
The clearance in front of the compartment shall
be 48 inches (1220 mm) long minimum mea-
sured from the control wall and 36 inches (915
mm) wide minimum.
Fig. 607.5 608.2.2 . Standard Roll-In-Type Shower
Location of Bathtub Controls Compartment. Roll-in-type shower compart-
45
Chapter 6. Plumbing Elements and Facilities ICC/ANSI A 117.1-1998
ments shall be 30 inches (760 mm) wide mini- ·be provided at one end of the long side of the
mum by 60 inches (1525 mm) deep minimum, compartment. The shower unit and controls
clear inside dimension, measured at the center- shall be mounted on the end wall furthest from
point of. opposing sides and shall have a mini- the compartment entry.
mum 60 inches (1525 mm) wide entry on the
face of the shower. A 30 inches (760 mm) wide
608.3 Grab Bars. Grab bars shall comply with Sec-
minimum by 60 inches (1525 mm) long mini- tions 608.3 and 609 and shall be provided.
mum clearance shall be provided adjacent to 608.3.1 Transfer-Type Showers. Grab bars
the open face of the shower compartment. A shall be provided across the control wall and on
lavatory complying with Section 606 shall be the back wall to a point 18 inches (455 mm) from
permitted atthe end of the clear space, opposite the control wall.
the shower compartment side where shower
controls are positioned. 608.3.2 Roll-in-Type Showers. Grab bars
shall be provided on the three walls of the show-
608.2.3 Alternate Roll-in-Type Shower er. Grab bars shall be 6 inches (150 mm) maxi-
Compartment. Alternate roll-in shower mum from the adjacent wall.
compartments shall be 36 inches (915 mm) EXCEPTIONS:
wide and 60 inches (1525 mm) deep minimum. 1. Where a seat is provided in a roll-in
A 36 inch (915) mm) wide minimum entry shall shower, grab bars shall not extend over
back wall
seat
wall
~~" control
wall
LO
co ..-
C")en
-l
r
I 36
l
I
(
I
I ._-=.~~
I r·-·---. .~
- -- -- - - l I
I ?1 ;
c
915 'E LO I!I )! I
I I 0;
. I
I I co
C")
Ii ) i I
I I 1'---·_·---' ) I
-
L ________ J L--='~-=- _______ -.J--------T
1
'-
48 min 60 min
1220 1525
COLO
C")..-
en
back wall r 18
455 l
seat
wall
36 min
915
60 min
1525
Fig. 608.2.3 Fig. 608.3.1
Alternate Roll-in-Type Shower Compartment Grab Bars in Transfer-Type Showers
46
ICC/ANSI A117.1-1998 Chapter 6. Plumbing Elements and Facilities
~ ~ r
1 x
E LO
o
C,O.....
~r
E
C,O
LO
.....
~r
E LO
C,O..... "'~/'-----...
Fig. 608.3.2
Grab Bars in Roll-in-Type Showers
the seat at the control wall and shall not and as a hand-held shower. In transfer type show-
be behind the seat. ers, the controls and shower unit shall be on the con-
2. In alternate roll-in-type showers, grab trol wall within 15 inches (380 mm), left or right, of
bars shall not be required on the side the centerline of the seat. In roll-in-type showers,
wall opposite the control wall and shall shower spray units mounted on the back wall shall
not be behind the seat. be 27 inches (685 mm) maximum from the side wall.
If an adjustable-height shower head mounted on a
608.4 Seats. An attachable or integral seat shall be vertical bar is used, the bar shall not obstruct the use
provided in transfer-type shower compartments. of grab bars.
Seats shall comply with Section 610.
608.7 Thresholds. Shower compartment thresh-
608.5 Controls. Shower or bathtub/shower facili- olds shall be 1/2 inch (13 mm) high maximum and
ties shall deliver water that is thermal shock pro- shall comply with Section 303.
tected to 120 degrees F (49 degrees C) maximum. 608.8 Shower Enclosures. Shower compartment
Faucets and controls shall comply with Section enclosures for shower compartments shall not
309.4. Controls in roll-in showers shall be above the obstruct controls or obstruct transfer from wheel-
grab bar but no higher than 48 inches (1220 mm) chairs onto shower seats.
above the shower floor. In transfer-type shower
compartments, controls, faucets, and the shower
609 Grab Bars
unit shall be on the side wall opposite the seat 38
inches (965 mm) minimum and 48 inches (1220 609.1 General. Grab bars in accessible toilet or
mm) maximum above the shower floor. bathing facilities shall comply with Section 609.
608.6 Shower Unit. A shower spray unit shall be 609.2 Size. Grab bars shall have a circular cross
provided, with a hose 59 inches (1500 mm) long section with a diameter of 11/4 inch (32 mm) mini-
minimum, that can be used as a fixed shower head mum and 2 inches (51 mm) maximum, or shall pro-
47
Chapter 6. Plumbing Elements and Facifities ICC/ANSI A117.1-1998
15 max
27 max
~
~~ 380
.r
•
685 l'
control.
wall ~ ~
~~Wrol. back wall
~ I
X
p. «: I 5) if:::::============5)
I ttl 0
E C\I
C\I
I
I
I
00
o:::t
I
I
I
I I I I
I I I
(a) (b)
Fig. 608.5
Controls in Transfer-Type Fig. 608.6
Showers Location of Shower Spray Unit
vide equivalent graspability complying with Section EXCEPTION: The space between the grab bars
609.2.1. and shower controls, shower fittings, and other
grab bars above shall be 1112 inches (38 mm)
minimum.
609.2.1 Non-Circular Cross Sections. Grab
bars with other shapes shall be permitted pro- 609.4 Position of Grab Bars. Grab bars shall be
vided they have a perimeter dimension of mounted in a horizontal position, 33 inches (840
4 inches (102 mm) minimum and 4.8 inches mm) minimum and 36 inches (915 mm) maximum
(122 mm) maximum and with edges having a above the floor.
118 inch (3.2 mm) minimum radius.
EXCEPTION: Height of grab bars on the back
wall of a bathtub shall comply with Sections
609.3 Spacing. The space between the wall and 607.4.1.1 and 607.4.2.1.
the grab bar shall be 11/2 inches (38 mm). The space
between the grab bar and objects below and at the 609.5 Surface Hazards. Grab bars and any wall or
ends shall be 1112 inches (38 mm) minimum. The other surfaces adjacent to grab bars shall be free of
space between the grab bar and projecting objects sharp or abrasive elements. Edges shall have a
above shall be 15 inches (380 mm) minimum. radius of 1/8 inch (3.2 mm) minimum.
48
ICC/ANSI A117.1-1998 Chapter 6. Plumbing Elements and Facilities
609.6 Fittings. Grab bars shall not rotate within gular. The top of the seat shall be 17 inches (430
their fittings. mm) minimum and 19 inches (485 mm) maximum
above the bathroom floor. In a transfer-type shower,
609.7 Installation. Grab bars shall be installed in the seat shall extend from the back wall to a point
any manner that provides a gripping surface at the within 3 inches (76 mm) of the compartment entry.
locations specified in this standard and that does In a roll-in-type shower, the seat shall extend from
not obstruct the clear floor space. the control wall to a point within 3 inches (76 mm) of
the minimum required seat wall width.
609.8 Structural Strength. Allowable stresses in
bending, shear, and tension shall not be exceeded 610.3.1 Rectangular Seats. The rear edge of
for materials used where a vertical or horizontal a rectangular seat shall be 21/2 inches (64 mm)
force of 250 pounds (1112 N) is applied at any point maximum from the seat wall, and the front edge
on the grab bar, fastener mounting device, or sup- 15 inches (380 mm) minimum and 16 inches
porting structure. (405 mm) maximum from the seat wall. In a
transfer-type shower the side edge of a rectan-
610 Seats gular seat shall be 11/2 inches (38 mm) maxi-
mum. In a roll-in-type shower, the side edge of
610.1 General. Seats in accessible bathtubs and a rectangular seat shall be 11/2 inches (38 mm)
shower compartments shall comply with Section maximum from the control wall.
610.
610.3.2 L-Shaped Seats. The rear edge of an
610.2 Bathtub Seats. A removable in-tub seat shall L-shaped seat shall be 21/2 inches (64 mm)
be 15 inches (380 mm) minimum and 16 inches maximum from the seat wall, and the front edge
(405 mm) deep maximum, and shall be capable of 15 inches (380 mm) minimum and 16 inches
secure placement. A permanent seat shall be (405 mm) maximum from the seat wall. The rear
15 inches (380 mm) deep minimum and be posi- edge of the "L" portion of the seat shall be 11/2
tioned at the head end of the bathtub. The top of the inches (38 mm) maximum from the wall and the
seat shall be 17 inches (430 mm) minimum and front edge shall be 14 inches (355 mm) mini-
19 inches (485 mm) maximum above the bathroom mum and 15 inches (380 mm) maximum from
floor. the wall. The end of the "L" shall be 22 inches
(560 mm) minimum and 23 inches (585 mm)
610.3 Shower Compartment Seats. Where a seat maximum from the main seat wall.
is provided in a roll-in shower compartment, it shall
be a folding type and shall be on the wall adjacent 610.4 Structural Strength. Allowable stresses in
to the controls. Seats shall be L-shaped or rectan- bending, shear, and tension shall not be exceeded
<£ ]) LO IE 2>
0) co
T" V
<£ :ll r-!. 6
C") IE 2>
v
15-16 15 min
380 \
f
49
Chapter 6. Plumbing Elements and Facilities ICC/ANSI A117.1-1998
~
22-23
-
E co
(\JM
J-
~ co T ""
(\JM
_ _• T""
m~ LOCO
T""
a
M
.,;. Lb
LO
M
~ E ,......
M
(O 64
15-16
380-405
OD DO
o c=:J 0
LO
V(O
MCO
~ Lbo
LO co
E (0 M
v co
M
I I
I I
(a) Top Loading (b) Front Loading
Fig. 611.4
Height of Laundry Equipment
for materials used where a vertical or horizontal clear floor or ground space shall be centered on the
force of 250 pounds (1112 N) is applied at any point appliance.
on the seat, fastener mounting device, or supporting
structure. 611.3 OlPerable Parts. Operable parts, including
doors, lint screens, detergent and bleach compart-
ments, shall comply with Section 309.
611 Laundry Equipment
611.4 Height. Top loading machines shall have the
611.1 General. Accessible washing machines and door to the laundry compartment 34 inches (865
clothes dryers shall comply with Section 611. mm) maximum above the floor or ground. Front
loading machines shall have the bottom of the open-
611.2 Clear Floor or Ground Space. A clear floor ing to the laundry compartment 15 inches (380 mm)
or ground space complying with Section 305 posi- minimum and 34 inches (865 mm) maximum above
tioned for parallel approach shall be provided. The the floor or ground.
50
iCC/ANSI A117.1-1998 Chapter 7. Communication Elements and Features
51
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
52
ICC/ANSI A 117.1-1998 Chapter 7. Communication Elements and Features
4 -----> r---
~
E
ID
ID .$
.$ E LO
0 0 T""
... 0
T""
C')
J,
6LO T""
corridor
l
'I
50-100 feet 50-100 feet l
'I
l
15 feet max 'I / 15-30 m 15-30 m \ '115 feet max
4570 4570
Fig. 702.3.5.1
Appliance Spacing in Corridors
Fig. 702.3.6.2
Appliance Location in Sleeping Rooms
building fire alarm system shall be provided of the bed location, measured horizontally.
within the room or suite. The signaling line Appliances shall be permanently installed.
or channel between the activating device of Where a suite contains more than one
the appliance and the building fire alarm sleeping room, an appliance shall be pro-
system shall be monitored for integrity by vided in each sleeping room.
the building fire alarm system. Where the
same appliance is used for visual notifica-
tion of smoke detector and fire alarm sys- 702.3.6.3 Minimum Effective Intensity
tem activation, activation of the room or and Mounting Height. Wall-mounted ap-
suite smoke detectors shall not activate the pliances 24 inches (610 mm) minimum be-
building fire alarm system. low the ceiling shall have a minimum
effective intensity of 110 candela. Ceiling-
702.3.6.2 Location. In sleeping rooms or mounted appliances and wall-mounted ap-
suites having a linear dimension exceeding pliances less than 24 inches (610 mm) be-
16 feet (4875 mm), the appliance shall be low the ceiling shall have a minimum
16 feet (4875 mm) maximum from the head effective intensity of 177 candela.
53
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
0 100 0 100
5-30 90 5-25 90
35 65 30-45 75
40 46 50 55
45 34 55 45
50 27 60 40
55 22 65 35
60 18 70 35
65 16 75 30
70 15 80 30
75 13 85 25
80 12 90 25
85 12 - -
90 12 - -
54
ICC/ANSI A 117.1-1998 Chapter 7. Communication Elements and Features
20' x 20' 15
30' x 30' 30
10 feet
40' x 40' (3050 mm) 60
50' x 50' 95
20' x 20' 30
20' x 20' 55
55
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
703 Signs
-
LO (0
..-
complying with Section 703.4 provide the same
information.
703.2.4.4 Height. Character height, mea- 703.2.7 Mounting Height. Characters shall be
sured vertically from the baseline of the 48 inches (1220 mm) minimum and 60 inches
character, shall be 5/8 inch (16 mm) mini- (1525 mm) maximum above the adjacent floor
mum, and 2 inches (51 mm) maximum, or ground surface, measured from the baseline
based on the uppercase letter "I." of the characters.
EXCEPTION: Elevator car controls.
703.2.4.5 Stroke Thickness. Characters
with rectangular cross sections shall have 703.2.8 Mounting Location. Where a sign
a stroke thickness which is 10 percent mini- containing tactile characters is provided at a
mum, and 15 percent maximum, of the door, the sign shall be alongside the door on the
height of the character, based on the upper- latch side. Where a tactile sign is provided at
case letter "I". Characters with other cross double doors, the sign shall be to the right of the
56
ICC/ANSI A 117.1-1998 Chapter 7. Communication Elements and Features
W
sured vertically from the baseline of the
character, shall be 1/2 inch (13 mm) mini-
mum, and 314 inch (19 mm) maximum,
based on the height of the uppercase letter
455 "I."
Fig. 703.2.8 703.3.3.5 Stroke Thickness. Characters
Mounting Location at Doors shall have a stroke thickness which is
15 percent maximum of the height of the
character, based on the uppercase letter
right-hand door. Where there is no wali space "I. ,~
on the latch side of a single door, or to the right
side of double doors, signs shall be on the near- 703.3.4 Character Spacing. Spacing shall be
est adjacent wall. Signs containing tactile char- measured between the two closest points of ad-
acters shall have an 18 inch (455 mm) minimum jacent characters within a message, excluding
by 18 inch (455 mm) minimum space on the word spaces. Spacing between individual char-
floor or ground, centered on the sign, beyond acters shall be 1/8 inch (3.2 mm) minimum to
the arc of any door swing between the closed 1/4 inch (6.4 mm) maximum.
position and 45 degree open position.
703.3.5 Line Spacing. Spacing between the
EXCEPTION: Door-mounted signs shall be
baseline of separate lines of characters within
permitted on the push side of doors with clos-
a message shall be 135 percent minimum and
ers and without hold-open devices.
170 percent maximum of the character height.
703.3 Tactile Characters. Where tactile characters 703.3.6 Mounting Height. Characters shall be
are required, and separate tactile and visual charac- 48 inches (1220 mm) minimum and 60 inches
ters with the same information are provided, tactile (1525 mm) maximum above the adjacent floor
characters shall comply with Sections 703.3.1 or ground surface, measured from the baseline
through 703.3.7 and visual characters shall comply of the characters.
with Section 703.4.
EXCEPTION: Elevator car controls.
703.3.1 Braille. Tactile characters shall be du- 703.3.7 Mounting Location. Where a tactile
plicated in Braille complying with Section 703.5. sign is provided at a door, the sign shall be
alongside the door on the latch side. Where a
703.3.2 Tactile Character Depth. Tactile char- tactile sign is provided at double doors, the sign
acters shall be raised 1/32 inch (0.8 mm) mini- shall be to the right of the right-hand door.
mum above their background. Raised borders Where there is no wall space on the latch side
and elements that are not required shall be of a single door, or to the right side of double
3/8 inch (9.5 mm) minimum from tactile doors, signs shall be on the nearest adjacent
characters. wall. Signs containing tactile characters shall
have an 18 inch (455 mm) minimum by 18 inch
703.3.3 Character Forms. Fonts shall have (455 mm) minimum space on the floor or
characters complying with Sections 703.3.3.1 ground, centered on the sign, beyond the arc of
through 703.3.3.5. any door swing between the closed position and
45 degree open position.
703.3.3.1 Case. Characters shall be upper- EXCEPTION: Door-mounted signs shall be
case. permitted on the push side of doors with clos-
ers and without hold-open devices.
703.3.3.2 Style. Characters shall be sans
serif. Characters shall not be italic, oblique, 703.4 Visual Characters. Accessible visual char-
script, highly decorative, or of other unusual acters shall comply with Sections 703.4.1 through
forms. 703.4.5.
57
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
703.4.1 Finish and Contrast. Characters and distance shall be measured as the horizon-
their background shall have a non-glare finish. tal distance where an obstruction prevents
Characters shall contrast with their back- further approach toward the sign.
ground, with either light characters on a dark
background, or dark characters on a light back- 703.4.2.5 Stroke Thickness. Characters
ground. shall have a stroke thickness which is
10 percent minimum, and 30 percent maxi-
703.4.2 Character Forms. Fonts shall have mum, the height of the character, based on
characters complying with Sections 703.4.2.1 the uppercase letter "I."
through 703.4.2.5.
703.4.3 Character Spacing. Spacing shall be
703.4.2.1 Case. Characters shall be upper- the two closest points of adjacent characters
case, lowercase, or a combination of both. within a message, excluding word spaces.
Spacing between individual characters shall be
703.4.2.2 Style. Characters shall be con- 10 percent minimum and 35 percent maximum
ventional in form. Characters shall not be of character height.
italic, oblique, script, highly decorative, or of
other unusual forms. 703.4.4 Line Spacing. Spacing between the
baselines of separate lines of characters within
703.4.2.3 Width. Character width shall be a message shall be 135 percent minimum to
55 percent minimum and 110 percent maxi- 170 percent maximum of character height.
mum the height of the character, with the
width based on the uppercase letter "0," 703.4.5 Mounting Height. Visual characters
and the height based on the uppercase "I." shall be 40 inches (1015 mm) minimum above
the floor or ground of the viewing position.
703.4.2.4 Height. Minimum character Mounting heights shall comply with Table
height, measured from the baseline of the 703.4.2.4, based on the size of the characters
character, shall comply with Table on the sign.
703.4.2.4, based on the height of the char-
acters above the floor or ground of the view- 703.5 Braille. Tactile characters shall be accompa-
ing location and the minimum viewing dis- nied by Grade II Braille complying with Sections
tance. Character height shall be based on 703.5.1 through 703.5.4 and Table 703.5. Braille
the uppercase letter "I." Minimum viewing dots shall have a domed or rounded shape.
Height above
Floor or Ground to Minimum
Top of Character Viewing Distance Minimum Character Height Notes
40 inches - s70 inches s 6 feet 5/8 inch (16 mm) Except
(1015 mm - 1780 mm) (1830 mm) elevators
40 inches - s70 inches > 6 feet 5/8 inch (16 mm), plus 1/8 inch per foot Except
(1015 mm - 1780 mm) (1830 mm) (3.2 mm per 305 mm) of viewing dis- elevators
tance beyond 6 feet (1830 mm)
58
ICC/ANSI A117:1-1998 Chapter 7. Communication Elements and Features
703.5.1 Location. Braille shall be below the 703.6.3 Text Descriptors. Where text descrip-
corresponding text. If text is multilined, Braille tors for pictograms are required, they shall be
shall be placed below entire text. Braille shall be directly below or adjacent to the pictogram and
separated 3/8 inch (9.5 mm) minimum from any shall comply with Section 703.2.
other tactile characters.
703.7 Symbols of Accessibility. Symbols of ac-
EXCEPTION: Braille provided on elevator
cessibility shall comply with Sections 703.7.1
car controls shall be separated 3/16 inch (4.8
through 703.7.2.
mm) minimum either directly below or adja-
cent to the corresponding raised characters 703.7.1 Finish and Contrast. Symbols of ac-
or symbols. cessibility and their backgrounds shall have a
non-glare finish. Symbols of accessibility shall
703.5.2 Raised Elements and Borders. contrast with their backgrounds, with either a
Raised borders and elements that are not re-
light symbol on a dark background or a dark
quired shall be 3/8 inch (9.5 mm) minimum from
symbol on a light background.
tactile characters.
•
the baseline of the Braille cells.
EXCEPTION: Elevator car controls.
703.5.4 Braille Standard. Braille shall comply
with literary Braille.
EXCEPTION: The indication of an upper-
case letter or letters shall only be used before
the first word of sentences, proper nouns and
names, individual letters of the alphabet, ini-
tials, or acronyms.
59
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
1111111111
11111111
1111111111
II Q II iV}~~; ,-
I
20 max
I l~ I
510
I I I
I I I
I I I
I I I
L________ J I
(a) Parallel Approach I
L ____ ~
Fig. 704.2.1
Clear Floor or Ground Space for Telephones
60
ICC/ANSI A 117.1-1998 Chapter 7. Communication Elements and Features
from the edge of the telephone enclosure to 705.2 Standardization. Detectable warnings shall
the face of the telephone unit shall be be standard within a building, facility, site, or com-
10 inches. (255 mm) maximum. plex of buildings.
61
Chapter 7. Communication Elements and Features ICC/ANSI A117.1-1998
superior, reliable communication of the impend- edge of key surfaces shall have a radius of
ing change to pedestrians who are blind or visu- 1/50 inch (0.5 mm) maximum. .
ally impaired. The information to be communi- EXCEPTION: The touch areas of video dis-
cated must include 24 inches (610 mm) of play screens.
advance warning of the platform edge and the
precise orientation of the platform edge in rela- 707.4.3 Separation Between Keys. Any key
tion to the pedestrian. surface shall be separated from other key sur-
faces by 1/8 inch (3.2 mm) minimum. Function
keys shall be separated from the keypad equal
706 Assistive Listening Systems to a distance that is not less than three times
greater than the actual distance between the
706.1 General. Accessible assistive listening sys- numeric keys.
tems in assembly areas shall comply with Section
706. 707.4.4 Numeric Keys. Where provided, nu-
meric keys shall comply with Sections 707.4.4.1
706.2 Placement. Individual fixed seats, served by and 707.4.4.2.
an assistive listening system, shall have complete
707.4.4.1 Arrangement. Numeric keys
view of the stage, playing area, or cinema screen.
shall be arranged in a 12-key telephone
keypad layout with the number one key in
706.3 Types of Systems. Induction loops, infrared the upper left hand corner.
systems, FM and AM radio fr'equency systems,
hard-wired earphones, and other equivalent 707.4.4.2 Marking. The number five key
devices shall be permitted as acceptable listening shall have a single raised dot.
systems.
707.4.5 Function Keys. Where provided, func-
tion keys shall comply with Sections 707.4.5.1
707 Automatic Teller Machines (ATMs) and Fare through 707.4.5.3.
Machines
707.4.5.1 Arrangement. Function keys
707.1 General. Automatic teller machines and fare shall be in the order of enter, clear, cancel,
machines that are required to be accessible shall add value, and decrease value horizontally
comply with Section 707. from left to right or vertically from top to bot-
tom. Where provided, add value and de-
crease value shall be grouped with other
707.2 Clear Floor or Ground Space. A clear floor
function keys.
or ground space complying with Section 305 shall
be provided. . 707.4.5.2 Marking. Function keys shall be
EXCEPTION: Clear floor or ground space is not marked with tactile characters as follows:
required at drive-up only machines. - Enter or proceed key: raised circle;
- Clear or correct key: raised vertical line
707.3 Operable Parts. Operable parts shall comply
or bar;
with Section 309. Each operable part shall be able
to be differentiated by sound or touch, without - Cancel key: raised letter "x";
activation.
- Add value key: raised plus sign;
EXCEPTION: Drive-up only machines shall not
- Decrease value key: raised minus sign.
be required to comply with Section 309.2 or
309.3. 707.4.5.3 Color Coding. Where function
keys are color coded, they shall be colored
707.4 Input. Input devices shall comply with Sec- as follows:
tions 707.4.1 through 707.4.5.
.- Enter or proceed key: green;
707.4.1 Privacy. The opportunity for the same - Clear or correct key: black;
degree of privacy of input shall be available to - Cancel key: red;
all individuals utilizing the equipment.
- Add value key: blue;
707.4.2 Key Surfaces. All keys used to operate - Decrease value key: yellow.
a machine shall be tactually discernible. Key
surfaces shall be offset from the surrounding 707.5 Output. Output devices shall comply with
surface by 1/25 inch (1 mm) minimum. The outer Sections 707.5.1 through 707.5.6.
62
ICC/ANSI A 117.1-1998 Chapter 7. Communication Elements and Features
707.5.1 Privacy. The opportunity for the same transmission system, or another mechanism
degree of privacy of output shall be available to that is readily available to all customers.
all individuals utilizing the equipment.
707.5.4 Video Display Screen. The video dis-
707.5.2 Operating Instructions. Machines play screen shall comply with Sections
shall provide visual and audible instruction for 707.5.4.1 and 707.5.4.2.
operation. Visual and audible instruction shall
include all information required by Sections 707.5.4.1 Visibility. The video display
707.5.2.1 through 707.5.2.5. screen shall be visible from a point 40 inch-
es (1015 mm) above the center of the clear
707.5.2.1 Initiation. Instruction shall be ini- floor or ground space in front of the
tiated by the user of the machine. machine.
EXCEPTION: This requirement shall not
707.5.2.2 Expedited Process. After initia- apply to drive-up only machines.
tion, instructions shall be available to the
experienced user to expedite the trans- 707.5.4.2 Characters. Characters dis-
action. played on the screen shall be in a sans serif
font. Characters shall be 3/16 inch (4.8 mm)
707.5.2.3 Orientation. Orientation and as- high minimum, based on the uppercase let-
sistance for unfamiliar users to the physical ter "I." Characters shall contrast with the
features of the machine, operational op- background with either light characters on
tions, and details for each function shall be a dark background, or dark characters on a
provided. light background.
707.5.2.4 Transaction Prompts. All trans- 707.5.5 Dispensing of Bills. Machines that
action prompts within each operation shall dispense paper currency shall dispense the
be provided. currency so that bills are dispensed in descend-
ing order with the lowest denomination on top.
707.5.2.5 Input Verification. Verification of
all user inputs shall be provided. 707.5.6 Receipts and Verification. Where a
receipt is available and is requested, the follow-
707.5.3 Audible Instruction. Audible instruc- ing options shall be provided: a printed receipt,
tion shall be provided through a standard audio audible presentation of the transaction informa-
mini jack, a telephone handset, a wireless tion provided on the receipt, or both.
63
64
ICC/ANSI A117.1-1998 Chapter 8. Special Rooms and Spaces
802 Auditorium and Assembly Areas 802.4 Depth. Where a wheelchair space can be en-
tered from the front or rear, the wheelchair space
802.1 General. Wheelchair spaces in auditorium
shall be 48 inches (1220 mm) deep minimum.
and assembly areas with fixed seating shall comply
Where a wheelchair space can only be entered from
with Section 802.
the side, the wheelchair space shall be 60 inches
802.2 Surfaces. The floor or ground surface of (1525 mm) deep minimum.
wheelchair spaces shall have a slope not steeper
than 1:48 and shall comply with Section 302.
36 min min " 33 min r
1---
915 1r" - 33840 1 840
---,-------,
;
I I I I
I I I I
I I I I
I I I I
I I I I
I I I I
I I I I
I I I I
L _ _ _ _ _ ---1 L _ _ _ _ _ -L _ _ _ _ _ ..J
1-----1
--, I I
I I I
I I I
I I I
I .~E
I co
0
C\I ~I I~~/L-,
oo:;t
C\I
,..... ~I ICD,.....~
I I I
I I I
I I I
L _ _ _ _ _ ---1
I I
L _____
1f
~
65
Chapter 8. Special Rooms and Spaces ICC/ANSI A117.1-1998
802.5 Approach. One side of the wheelchair space 804.3 Wheelchair Turning Space. A wheelchair
shall adjoin an accessible route or adjoin another turning space complying with Section 304 shall be
wheelchair space. Access to any wheelchair space provided within the room. The wheelchair turning
shall not be through more than one adjoining wheel- space shall be adjacent to or overlap clear floor or
chair space. ground areas required by Section 804.
802.6 Integral Part of Seating. Wheelchair loca- 804.4 Work Surface. The work surface shall com-
tions shall be an integral part of any fixed seating. ply with Section 902.
802.7 Companion Seat. At least one seat for a 804.5 Sink. The sink and surrounding counter shall
companion shall be provided beside each wheel- comply with Section 606.
chair space.
804.6 Kitchen Storage. Kitchen storage shall com-
802.8 Lines of Sight. Wheelchair spaces shall pro- ply with Section 905.
vide lines of sight comparable to those of all viewing
areas. 804.7 Appliances. Where provided, kitchen ap-
pliances shall comply with Sections 804.7.1 through
804.7.6.
803 Dressing, Fitting, and Locker Rooms
804.7.1 Clear Floor or Ground Space. A clear
803.1 General. Accessible dressing, fitting, and floor or ground space complying with Section
locker rooms shall comply with Section 803.
305 shall be provided at each kitchen appli-
ance. Clear floor or ground spaces are per-
803.2 Wheelchair Turning Space. A wheelchair mitted to overlap.
turning space complying with Section 304 shall be
provided within the room. 804.7.2 Operating Controls. All appliance
controls shall comply with Section 309.
803.3 Doors. Doors shall not swing into any part of
the turning space. 804.7.3 Dishwasher. Clear floor or ground
space shall be positioned adjacent to the dish-
803.4 Benches. A bench complying with Section washer door. The dishwasher door in the open
903 shall be provided within the room. position shall not obstruct the clear floor or
ground space for the dishwasher or the sink.
803.5 Coat Hooks and Shelves. Accessible coat
hooks provided within dressing and fitting rooms 804.7.4 Range or Cooktop. Where a forward
shall accommodate a forward reach or side reach approach clear floor or ground space is pro-
complying with Section 308. Where provided, a fold- vided, the clear floor or ground space shall pro-
down shelf shall be 40 inches (1015 mm) minimum vide knee and toe clearance complying with
and 48 inches (1220 mm) maximum above the floor Section 306. Where knee and toe space is pro-
or ground. vided, the underside of the range or cooktop
shall be insulated or otherwise configured to
804 Kitchens prevent burns, abrasions, or electrical shock.
The location of controls shall not require reach-
804.1 General. Accessible kitchens shall comply ing across burners.
with Section 804.
804.7.5 Oven. For side-opening ovens, the
804.2 Clearance. Clearance complying with Sec- door latch side shall be next to a countertop.
tions 804.2.1 and 804.2.2 shall be provided. Ovens shall have controls on front panels, on ei-
ther side of the door.
804.2.1 Galley Areas. Clearance between all
opposing base cabinets, counter tops, ap- 804.7.6 Refrigerator/Freezer. Combination
pliances, or walls within kitchen work areas refrigerators and freezers shall have at least
shall be 40 inches (1015 mm) minimum. 50 percent of the freezer space 54 inches (1370
mm) maximum above the floor or ground. The
804.2.2 U-Shaped Areas. In kitchens with clear floor or ground space shall be positioned
counters, appliances, or cabinets on three con- for a parallel approach to the space dedicated
tiguous sides, clearance between all opposing to a refrigerator/freezer with the centerline of
base cabinets, countertops, appliances, or the clear floor or ground space offset 24 inches
walls within ~itchen work areas shall be 60 inch- (610 mm) maximum from the centerline of the
es (1525 mm) minimum. dedicated space.
66
ICC/ANSI A 117.1-1998 Chapter 9. Built-In Furnishings and Equipment
902.1 General. Accessible seating at fixed tables, 904.1 General. Accessible checkout and service
counters and work surfaces shall comply with Sec- counters shall' comply with the applicable provisions
tion 902. of Section 904.
902.2 Clear Floor or Ground Space. Clear floor or 904.2 Checkout Counters. Checkout counter sur-
ground space complying with Section 305 shall be faces shall be 38 inches (965 mm) maximum above
provided. Knee and toe clearance complying with the floor or ground. The top of the counter edge
Section 306 shall be provided. protection shall be 2 inches (51 mm) maximum
above the counter surface.
902.3 Height. The tops of tables, counters, and
work surfaces shall be 28 inches (710 mm) mini- 904.3 Service Counters. Counters for sales or dis-
mum and 34 inches (865 mm) maximum from the tribution of goods and services to the public shall
floor or ground. have a portion of the counter 36 inches (915 mm)
long minimum by 36 inches (915 mm) high maxi-
902.4. Food and Drink Counters. Accessible food mum above the floor or ground.
and drink counters shall be 60 inches (1525 mm)
long minimum.
903 Benches
67
Chapter 9. Built-In Furnishings and Equipment ICC/ANSI A117.1-1998
904.4 Tray Slides. The tops of accessible portions 905.2 Cle-ar Floor or Ground Space. A clear floor
of tray slides shall be 28 inches (710 mm) minimum or ground space complying with Section 305 shall
and 34 inches (865 mm) maximum above the floor be provided.
or ground.
905.3 Height. Accessible storage areas shall com-
ply with at least one of the reach ranges specified in
905 Storage Facilities Section 308.
905.1 General. Accessible storage facilities shall 905.4 Operable Parts. Operable parts of storage
comply with Section 905. facilities shall comply with Section 309.4.
68
ICC/ANSI A 117.1-1998 Chapter 10. Dwelling Units
69
Chapter 10. Dwelling Units ICC/ANSI A117.1-1998
1002.7.6 Illumination Levels. The level of illu- 1002.9 Operable Parts. Lighting controls, electrical
mination at the car controls, platform, and car switches and receptacles, environmental controls,
threshold and landing sill shall be 5 footcandles appliance controls, operating hardware for operable
(54 lux) minimum. windows, plumbing fixture controls, and user con-
trols for security or intercom systems shall comply
1002.7.7 Car Controls. Elevator car controls with Section 309.
shall comply with Sections 1002.7.7.1 through
1002.7.7.3. EXCEPTIONS:
1. Electrical receptacles serving a dedicated
1002.7.7.1 Buttons. Control buttons shall use.
be 3/4 inch (19 mm) minimum in their small- 2. A single outlet where all of the following con-
est dimension. Control buttons shall be ditions are met:
raised or flush. (a) the outlet is above a length of countertop
1002.7.7.2 Height. Buttons with floor des- that is uninterrupted by a sink or appli-
.ignations shall comply with Section 309.3. ance; and
(b) at least one receptacle complying with
1002.7.7.3 Location. Controls shall be on Section 1002.9 is provided for that length
a side wall, 12 inches (305 mm) minimum of countertop; and
from any adjacent wall. (c) all other receptacles provided for that
length of countertop comply with Section
1002.7.8 Emergency Communications. A 1002.9.
telephone and emergency signal device shall 3. Floor electrical receptacles.
be provided in the car and shall comply with
4. HVAC diffusers.
ASME/ANSI A 17.1, Rule 509. The telephone
and emergency signaling device shall comply 5. Controls mounted on range hoods if accessi-
with Section 309.3. If the device is in a closed ble redundant controls are provided.
compartment, the compartment door hardware 6. Controls mounted on ceiling fans.
shall comply with Section 309. The telephone
cord shall be 29 inches (735 mm) long 1002.10 Laundry Equipment. Washing machines
minimum. and clothes dryers shall comply with Sections
1002.10.1 and 1002.10.2.
1002.8 Wheelchair Lifts. Wheelchair (platform)
lifts shall comply with ASME/ANSI A17.1 and with
Sections 302,305, and 309. 1002.10.1 Clear Floor or Ground Space. A
clear floor space positioned for parallel ap-
proach shall be provided and shall be centered
on the appliance.
12 min
305 1002.10.2 Operable Parts. All controls and
operating mechanisms, including doors, lint
screens, detergent and bleach compartments,
shall comply with Section 309.
70
ICC/ANSI A117.1-1998 Chapter 10. Dwelling Units
1002.11.3 Lavatory. Lavatories shall comply and to one side. The centerline of the water
with Section 606. closet shall be 16 inches (405 mm) mini-
mum and 18 inches (455 mm) maximu'm
EXCEPTION: Cabinetry shall be permitted
to be added under the lavatory, provided from the side wall.
such cabinetry can be removed without re- 1002.11.5.2 Clearance. Clearance around
moval .or replacement of the lavatory, and the water closet shall comply with Sections
provided the finish floor extends under such 1002.11.5.2.1 through 1002.11.5.2.3.
cabinetry.
1002.11.5.2.1 Parallel Approach.
1002.11.4 Mirrors. Mirrors above lavatories Where only a parallel approach is pro-
shall have the bottom edge of the reflecting sur- vided to the water closet, the clearance
face 40 inches (1015 mm) maximum above the shall be 56 inches (1420 mm) mini-
floor or ground. mum, measured perpendicular from
the rear wall, and 48 inches (1220 mm)
1002.11.5 Water Closet. Water closets shall minimum, measured perpendicular
comply with Sections 1002.11.5.1 through from the side wall. A lavatory complying
1002.11.5.5. with Section 1002.11.3 shall be per-
mitted on the rear wall, 18 inches (455
1002.11.5.1 Location. The water closet mm) minimum from the water closet
shall be positioned with a wall to the rear centerline.
405-455
Fig. 1002.11.5.1
Location of Water Closet in Type A Dwelling Units
i r'-F i r·-F .
. I I i I I I i I
:\..l -1.--.) .Ji i
l l._._)
l ) i
o
I
·,-._.L._.~·
--.-.L.-.~ I
I I I
.~ a c I
E C\I I 'E :e I I
i~e{>
co~
L{)
I I COCO
I
co
:e{>
I
~
I
I
I
i~
~
L _________ _
~--r-~~~---1
I
L ________ -1
J
>\,--_ _
60 min
1220 J 48 min
1220
1525
(a) Parallel Approach (b) Forward Approach (c) Parallel and Forward Approach
Fig. 1002.11.5.2
Water Closet Clearance in Type A Dwelling Units
71
Chapter 10. Dwelling Units ICC/ANSI A 117.1-1998
1002.11.5.2.2 Forward Approach. 2. Grab bars are not required, provided re-
Where only a forward approach is pro- inforcement has been provided in walls
vided to the water closet, the clearance to permit the installation of grab bars
shall be 66 inches (1675 mm) mini- complying with Section 608.3.
mum, measured perpendicular from
the rear wall, and 48 inches (1220 mm) 1002.12 Kitchens. Kitchens shall comply with Sec-
minimum, measured perpendicular tions 1002.12.1 through 1002.12.6.
from the side wall. A lavatory complying 1002.12.1 Clearance. Clearance complying
with Section 1002.11.3 shall be per- with Sections 1002.12.1.1 and 1002.12.1.2
mitted on the rear. wall, 18 inches (455 shall be provided.
mm) minimum from the water closet
centerline. 1002.12.1.1 Galley. Clearance between all
opposing base cabinets, counter tops, ap-
1002.11.5.2.3 Parallel and Forward pliances, or walls within kitchen work areas
Approach. Where both a parallel and shall be 40 inches (1015 mm) minimum.
a forward approach are provided to the 1002.12.1.2 U-Shaped. In kitchens with
water closet, the clearance shall be counters, appliances, or cabinets on three
56 inches (1420 mm) minimum, mea- contiguous sides, clearance between all
sured perpendicular from the rear wall, opposing base cabinets, countertops, ap-
and 60 inches (1525 mm) minimum, pliances, or walls within kitchen work areas
measured perpendicular from the side shall be 60 inches (1525 mm) minimum.
wall. No fixtures or obstructions, other
than the water closet, shall be within 1002.12.2 Clear Floor or Ground Space.
the clearance. Clear floor or ground spaces required by Sec-
tions 1002.12.3 through 1002.12.6 shall comply
1002.11.5.3 Height. The top of the toilet with Section 305.3.
seat shall be 15 inches (380 mm) minimum
and 19 inches (485 mm) maximum above 1002.12.3 Work Surface. At least one 30 inch-
the floor or ground. es (760 mm) wide minimum section of counter
shall provide a work surface that complies with
1002.11.5.4 Grab Bars. Grab bars comply- Sections 1002.12.3.1 through 1002.12.3.3.
ing with Section 604.5 shall be provided. 1002.12.3.1 Clear Floor or Ground
EXCEPTION: Where reinforcement has Space. A clear floor space complying with
been provided in walls to permit the Section 305.3 positioned for a forward ap-
installation of such grab bars. proach shall be provided. The clear floor or
ground space shall be centered on the work
1002.11.5.5 Flush Controls. Hand-oper- surface. The clear floor or ground space
ated flush controls shall comply with Sec- shall provide knee and toe clearance com-
tion 1002.9. plying with Section 306.
EXCEPTION: Cabinetry shall be per-
.1002.11.6 Bathtub. Bathtubs shall comply with mitted to be added under the work sur-
Section 607. face, provided such cabinetry can be re-
EXCEPTIONS: moved without removal or replacement
1. The removable in-tub seat required by of the work surface, and provided the fin-
Section 607.3 is not required. ish floor extends under such cabinetry.
2. Grab bars are not required, provided re- 1002.12.3.2 Height. The work surface shall
inforcement has been provided in walls be 34 inches (865 mm) maximum above
to permit the installation of grab bars the floor or ground.
complying with Section 607.4. EXCEPTION: A counter that is adjust-
able to provide a work surface at variable
1002.11.7 Shower. Showers shall comply with . heights 29 inches (735 mm) minimum
Section 608. and 36 inches (915 mm) maximum.
EXCEPTIONS:
1002.12.3.3 Exposed Surfaces. There
1. A shower seat shall not be required in . shall be no sharp or abrasive surfaces un-
transfer-type showers, provided rein- der the work surface counters.
forcement has been provided in a wall to
permit the installation of a seat comply- 1002.12.4 Sink. The sink and surrounding
ing with Section 610.3. counter shall comply with Sections 1002.12.4.1
72
ICC/ANSI A117.1-1998 Chapter 10. Dwelling Units
30 min
r
30 min
760 ;r 760
.., A ,.,.
i== 6 1/2 max
"-., ./ 165
x
I.{) co I.{)
CD E CD
co v co
C")
I
I I
I
I I
through 1002.12.4.5. The width of the sink and 1002.12.4.4 Faucets. Faucets shall com-
surrounding counter complying with this section ply with Section 309.
shall be 30 inches (760 mm) minimum.
1002.12.4.5 Exposed Pipes and Sur-
faces. Water supply and drain pipes under
1002.12.4.1 Clear Floor or Ground
sinks shall be insulated or otherwise config-
Space. A clear floor space positioned for a
ured to protect against contact. There shall
forward approach shall be provided. The
be no sharp or abrasive surfaces under
clear floor or ground space shall be cen-
sinks.
tered on the sink bowl. The clear floor or
ground space shall provide knee and toe 1002.12.5 Kitchen Storage. Cabinets shall
clearance complying with Section 306. have a clear floor or ground space complying
EXCEPTIONS: with Section 305.3, positioned for parallel or for-
ward approach.
1. Cabinetry shall be permitted to be
added under the sink, provided such 1002.12.6 Appliances. Where provided, kitch-
cabinetry can be removed without en appliances shall comply with Sections
removal or replacement of the sink, 1002.12.6.1 through 1002.12.6.7.
and provided the finish floor extends
under such cabinetry. 1002.12.6.1 Clear Floor or Ground
2. Adjustable-height sinks complying Space. A Clear floor or ground space com-
with Section 1002.12.4.3 are not plying with Section 305.3 positioned for
required to provide knee clearance parallel or forward approach shall be pro-
where placed at heights below vided at each kitchen appliance. Clear floor
34 inches (865 mm). or ground spaces shall be permitted to
overlap.
1002.12.4.2 Height. The sink and sur- 1002.12.6.2 Operable Parts. All appliance
rounding counter shall be 34 inches (865 controls shall comply with Section 309.
mm) maximum above the floor or ground,
measured to the higher of the fixture rim or 1002.12.6.3 Dishwasher. Clear floor or
the counter surface. ground space shall be positioned adjacent
to the dishwasher door. The dishwasher
EXCEPTION: Sink and counter that is
door in the open position shall not obstruct
adjustable to variable heights 29 inches
the clear floor or ground space for the dish-
(735 mm) minimum and 36 inches (915
washer or the sink.
mm) maximum, provided rough-in
plumbing permits connections of supply 1002.12.6.4 Range or Cooktop. Where a
and drain pipes for sinks mounted at the forward approach clear floor or ground
height of 29 inches (735 mm). space is provided, the clear floor or ground
space shall provide knee and toe clearance
1002.12.4.3 Sink Bowl. The depth of a sink complying with Section 306. Where knee
bowl shall be 61/2 inches (165 mm) maxi- and toe space is provided, the underside of
mum. Multiple-compartment sinks shall the range or cooktop shall be insulated or
have at least one compartment complying otherwise configured to prevent burns,
~ith this requirement. abrasions, or electrical shock. The location
73
Chapter 10. Dwelling Units ICC/ANSI A117.1-1998
of controls shall not require reaching across 1003.3 Accessible Route. Accessible routes with-
burners. in Type B dwelling units shall comply with Sections
1003.3.1 and 1003.3.2.
1002.12.6.5 Oven. For side-opening
EXCEPTION: One of the following is not required
ovens, the door latch side shall be next to
to be on an accessible route:
a countertop. Ovens shall have controls on
front panels, on either side of the door. 1. A raised floor area in a portion of a living, din-
ing, or sleeping room; or
1002.12.6.6 Refrigerator/Freezer. Com- 2. A sunken floor area in a portion of a living,
bination refrigerators and freezers shall dining, or sleeping room; or
have at least 50 percent of the freezer 3. A mezzanine that does not have plumbing
space 54 inches (1370 mm) maximum fixtures or an enclosed habitable space.
above the floor or ground. The clear floor or
ground space shall be positioned for a par- 1003.3.1 Location. At least one accessible
allel approach to the space dedicated to a route shall connect all spaces and elements
refrigerator/freezer with the centerline of which are a part of the dwelling unit. Where only
the clear floor or ground space offset one accessible route is provided, it shall not
24 inches (610 mm) maximum from the pass through restrooms, closets, or similar
centerline of the dedicated space. spaces.
74
ICC/ANSI A117.1-1998 Chapter 10. Dwelling Units
doors shall be measured between the face 1003.10 Laundry Equipment. Washing machines
of the door and stop, with the door open and clothes dryers shall comply with Section
90 degrees. 1003.10.1.
75
Chapter 10. Dwelling Units ICC/ANSI A117.1-1998
76
ICC/ANSI A 117.1-1998 Chapter 10. Dwelling Units
1003.11.3.2.1 Lavatory. Lavatories shall 1003.12 Kitchens. Kitchens shall comply with Sec-
comply with Sections 1003.11.3.2.1.1 tions 1003.12.1 and 1003.12.2.
through 1003.11.3.2.1.3.
1003.12.1 Clearance. Clearance complying
with Sections 1003.12.1.1 and 1003.12.1.2 shall
1003.11.3.2.1.1 Clear Floor or be provided.
Ground Space. A clear floor or
ground space complying with Sec- 1003.12.1.1 Galley. Clearance between all
tion 305.3, positioned for a parallel opposing base cabinets, counter tops, ,ap-
approach shall be provided. pliances, or walls within kitchen work areas
EXCEPTION: A lavatory com- shall be 40 inches (1015 mm) minimum.
plying with Section 606.
1003.12.1.2 U-Shaped. In kitchens with
1003.11.3.2.1.2 Position. The counters, appliances, or cabinets on three
centerline of the lavatory shall align contiguous sides, clearance between all
with the centerline of the clear floor opposing base cabinets, countertops, ap-
or ground space. pliances, or walls within kitchen work areas
shall be 60 inches (1525 mm) minimum.
1003.11.3.2.1.3 Height. The front 1003.12.2 Clear Floor or Ground Space.
of the lavatory shall be 34 inches Clear floor or ground space at appliances shall
(865 mm) maximum above the comply with Section 305.3 and Sections
floor or ground, measured to the 1003.12.2.1 through 1003.12.2.6.
higher of the fixture rim or counter
surface. 1003.12.2.1 Sink. The sink shall comply with
Sections 1003.12.2.1.1 and 1003.12.2.1.2.
1003.11.3.2.2 Water Closet. The wa-
ter closet shall comply with Section 1003.12.2.1.1 Approach. Clear floor
1003.11.3.1.2. or ground space shall be positioned for
a para"el approach.
1003.11.3.2.3 Bathing Facilities. EXCEPTION: Sink complying with
Where either a bathtub or shower Section 606.
compartment is provided, it shall con-
form with Section 1003.11.3.2.3.1 or 1003.12.2.1.2 Position. The center-
1003.11.3.2.3.2. line of the sink shall align with the cent-
erline ofthe clear floor or ground space.
1003.11.3.2.3.1 Bathtub. Clear-
ance in front of bathtubs shall be 1003.12.2.2 Dishwasher. Clear floor or
30 inches (760 mm) wide minimum ground space shall be positioned for paral-
by 48 inches (1220 mm) long mini- lel or forward approach. Clear floor or
mum measured from the foot end ground space shall be positioned beyond
of the bathtub. the swing of the dishwasher door.
77
Chapter 10. Dwelling Units ICC/ANSI A117.1-1998
1003.12.2.3 Range or Cooktop. Clear upon activation of the building fire alarm in the
floor or ground space shall be positioned for portion of the building containing the dwelling
parallel approach. unit.
EXCEPTION: Where a forward ap-
proach clear floor or ground space is pro- 1004.4.3 Interconnection. The same visible
vided, the clear floor or ground space notification appliances shall be permitted to pro-
shall provide knee and toe clearance vide notification of dwelling unit smoke detec-
complying with Section 306. Where knee tion and building fire alarm activation.
and toe space is provided, the underside
ofthe range or cooktop shall be insulated 1004.4.4 Prohibited Use. Visible notification
or otherwise configured to prevent appliances used to indicate dwelling unit smoke
burns, abrasions, or electrical shock. detection or building fire alarm activation shall
not be used for any other purpose within the
1003.12.2.4 Oven. Clear floor or ground dwelling unit.
space shall be positioned for parallel or for-
ward approach. 1004.5 Dwelling Unit Primary Entrance. Commu-
nication features shall be provided at the dwelling
1003.12.2.5 Refrigerator/Freezer. Clear unit primary entrance complying with Sections
1004.5.1 and 1004.5.2.
floor or ground space shall be positioned for
parallel or forward approach.
1004.5.1 Notification. A hard-wired electric
doorbell shall be provided. A button or switch
1003.12.2.6 Trash Compactor. Clear floor
shall be provided on the public side of the dwell-
or ground space shall be positioned for par-
ing unit primary entrance. Activation of the but-
allel or forward approach.
ton or switch shall initiate an audible tone within
the dwelling unit.
1004 Dwelling Units with Accessible
Communication Features 1004.5.2 Identification. A means for visually
identifying a visitor without opening the dwelling
1004.1 General. Dwelling units required to have ac- unit entry door shall be provided. Peepholes,
cessible communication features shall comply with where used, shall provide a minimum 180 de-
Section 1004. gree range of view.
1004.2 Dwelling Unit Smoke Detection. Where 1004.6 Site, Building, or Floor Entrance. Where
provided, dwelling unit smoke detection shall in- a system permitting voice communication between
clude audible notification complying with NFPA 72. a visitor and the occupant of the dwelling unit is pro-
vided at a location other than the dwelling unit entry
1004.3 ,Building Fire Alarm System. Where a door, the system shall comply with Sections
building fire alarm system is provided, the system 1004.6.1 and 1004.6.2.
wiring shall be extended to a point within the dwell-
ing unit in the vicinity of the dwelling unit smoke 1004.6.1 Public or Common-Use Interface.
detection system. The public or common-use system interface
shall include the capability of supporting voice
1004.4 Visible Notification Appliances. Visible and TTY communication with the dwelling unit
notification appliances, where provided within the interface.
dwelling unit as part of the dwelling unit smoke
detection system or the building fire alarm system, 1004.6.2 Dwelling Unit Interface. The dwell-
shall comply with Sections 1004.4.1 through ing unit system interface shall include a tele-
1004.4.4. phone jack capable of supporting voice and
TTY communication with the public or common-
1004.4.1 Appliance. Visible notification appli- use system interface.
ance shall comply with NFPA 72.
1004.7 Closed-Circuit Communication Sys-
1004.4.2 Activation. All visible notification ap- tems. Where a closed-circuit communication sys-
pliances provided within the dwelling unit for tem is provided, the public or common-use system
smoke detection notification shall be activated interface shall comply with Section 1004.6.1, and
upon smoke detection. All visible notification the dwelling unit system interface in units required
appliances provided within the dwelling unit for to have accessible communication features shall
building fire alarm notification shall be activated comply with Section 1004.6.2.
78
ANSI A117.1
79
80
ICC/ANSI A117.1-1998
ANSI A117.1
1992 -1998 CROSS REFERENCE
(Continued)
81
ICC/ANSI A117.1-1998
~~§ll,tf~l:.i~'."
4.17 Water Closets 604 Water Closets and Toilet Compartments
~--------------------------------~
4.18 Toilet Stalls
4.19 Urinals 605 Urinals
4.20 Lavatories and Sinks 606 Lavatories and Sinks
4.21 Bathtubs 607 Bathtubs
4.22 Shower Stalls 608 Shower Compartments
4.23 Storage 905 Storage
4.24 Grab Bars, and Tub and Shower Seats 609 Grab Bars
610 Seats
4.25 Operable Parts of Equipment and Appliances 309 Operable Parts
4.26 Alarms 702 Alarms
4.27 Detectable Warnings - Standardization 705 Detectable Warnings
4.28 Signage 703 Signs
4.29 Telephones 704 Telephones
4.30 Automatic Teller Machines 707 Automatic Teller Machines
4.31 Seating, Tables, Work Services and Service 902 Seating at Tables, Counters and Work Sur-
Counters faces
903 Benches
904 Sales and Service Counters
4.32 Auditorium and Assembly Areas 706 Assistive Listening Systems
802 Auditorium and Assembly Areas
4.33 Dwelling Units Chapter 10 Dwelling Units
1002 Type A Dwelling Units
1003 Type B Dwelling Units
1004 Dwelling Units with Accessible Communica-
tion Features
82
Errata to ICC/ANSI A117.1-1998, First Printing
1. Page 15, Table 404.2.4.1: In footnote 2, change the metric equivalent to 305 mm
2. Page 17, Section 404.2.4.4: Typo in title (Recessed)
3. Page 23: Revise Figure 407.2.4 as follows:
LO
ON
COLO
T""
4. Page 27: Revise cross reference in Section 407.3: " ... shall also comply with 407.3.1 through
407.3.5407.3.6 and ... "
5. Page 28: Revise Figure 407.3.5 as follows:
6. Page 29: Revise cross-reference in 407.4.9 as follows: " ... shall comply with Sections
407.4.9.1 through 407.4.9.3 407.4.9.4."
7. Page 42: Revise Figure 604.8.1.4(a) by changing "max" to "min" in both places.
8. Page 48: Change metric equivalent for 4.8 inches to 120 (not 160).
9. Page 48: Revise cross reference in 609.2 as follows: " ... equivalent graspability complying
with Section 505.7.1 609.2.1."
10. Page 48: Revise Figure 609.2(a) to show the range of the grab bar diameter as 11;4- 2 (not
11;4 - Ph)
11. Page 72: Revise cross reference in 1002.11.5.5 as follows: " ... shall comply with Section
~1002.9."
83
ICC/ANSI A117.1-1998
1. Page 1: Change in Section 101, second paragraph: " ... Federal Fair Housing l\numdm@Hts
Act Accessibility Guidelines."
2. Page 51: Figure 702.3.3.1: Add an ".(a)" at the symbol indicated at 80-96 inches above the
floor. Add a "(b.)" for the symbol indicated at 4-12 inches below the ceiling.
3. Page 77: Change Section "1003.11.1.2 (right-hand column under 1003.12.1.1) to
"1003.12.1.2".
4. Page 73: In the illustrations at the top of the page, change the "34 min" to "34 max".
84