Professional Documents
Culture Documents
Diesel Generator Set: Output Ratings
Diesel Generator Set: Output Ratings
DE33E0
Output Ratings
Technical Data
Engine Make & Model: ®C3.3
Fuel Consumption, Standby : l/hr (US gal/hr) 7.7 (2.0) 9.0 (2.4)
LEHE0690-00
DIESEL GENERATOR SET
Exhaust System 50 Hz 60 Hz
Cooling System 50 Hz 60 Hz
Silencer Type: Industrial
Cooling System Capacity: Silencer Model & Quantity: EXSY1 (1)
l (US gal) 10.2 (2.7) 10.2 (2.7) Pressure Drop Across
Water Pump Type: Centrifugal Silencer System: kPa (in Hg) 1.80 (0.532) 2.00 (0.591)
Heat Rejected to Water & Silencer Noise Reduction
Lube Oil: kW (Btu/min) Level: dB 20 19
-Standby: 18.0 (1024) 22.0 (1251) Max. Allowable Back
-Prime: 16.0 (910) 18.0 (1024) Pressure: kPa (in. Hg) 8.0 (2.4) 10.0 (3.0)
Heat Radiation to Room: Heat radiated from engine and alternator Exhaust Gas Flow:
kW (Btu/min) -Standby: 9.3 (529) 9.7 (552) m³/min (cfm) -Standby: 5.8 (205) 6.6 (233)
-Prime: 7.9 (449) 8.2 (466) -Prime: 5.7 (201) 6.4 (226)
Radiator Fan Load: kW (hp) 0.3 (0.4) 0.5 (0.7) Exhaust Gas Temperature: °C (°F)
Cooling system designed to operate in ambient conditions up to 50°C -Standby: 520 (968) 530 (986)
(122°F). Contact your local Cat dealer for power ratings at specific site -Prime: 500 (932) 520 (968)
conditions.
LEHE0690-00
DIESEL GENERATOR SET
Motor Starting
Capability* kVA 72 68 63 78 78 55 63 - 69
Short Circuit
Capacity % - - - - - - - - -
Reactances:
Per Unit
LEHE0690-00
DIESEL GENERATOR SET
Technical Data
Voltage Voltage
Prime Standby Prime Standby
50 Hz 60 Hz
kVA kW kVA kW kVA kW kVA kW
415/240V 30.0 24.0 33.0 26.4 480/277V 33.8 27.0 37.5 30.0
400/230V 30.0 24.0 33.0 26.4 220/127V 33.8 27.0 37.5 30.0
380/220V 30.0 24.0 33.0 26.4 380/220V 33.8 27.0 37.5 30.0
230/115V 30.0 24.0 33.0 26.4 240/120V 33.8 27.0 37.5 30.0
220/127V 30.0 24.0 33.0 26.4
220/110V 30.0 24.0 33.0 26.4 440/254V 33.8 27.0 37.5 30.0
200/115V 30.0 24.0 33.0 26.4 220/110V 33.8 27.0 37.5 30.0
208/120V 33.8 27.0 37.5 30.0
240/139V 33.8 27.0 37.5 30.0
diagrams.
!
"
#
#
$
Quality Standards
Prime Rating The equipment meets the following standards: IEC60034-1,
Output available with varying load for an unlimited time. Average IEC60034-22, ISO3046, ISO8528, NEMA MG 1-32,
power output is 70% of the prime power rating. Typical peak NEMA MG 1-33, 2004/108/EC, 2006/42/EC, 2006/95/EC.
demand is 100% of prime rated ekW with 10% overload capability
for emergency use for a maximum of 1 hour in 12.
Overload opeation cannot exceed 25 hours per year.
.
Standard Reference Conditions
Note: Standard reference conditions 25°C (77°F) air inlet temp,
100m (328ft) A.S.L. 30% relative humidity. Fuel consumption data
at full load with diesel fuel with specific gravity of 0.85 and
conforming to BS2869: 1998, Class A2.
www.Cat-ElectricPower.com
Performance No.: &!'+"&!'+;
© 2014 Caterpillar
Feature Code: <=>!<"<=>!'"<=>!$"<=>!?"<=>$" All rights reserved.
Materials and specifications are subject to change without notice.
<=>$@"<=>$+"<=>?
The International System of Units (SI) is used in this publication.
Gen. Arr. Number: '$+J'<++ CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the
"Power Edge" trade dress, as well as corporate and product
K
Q>
K
identity used herein, are trademarks of Caterpillar and may not be
LEHE0690-00 (08/14) used without permission.