You are on page 1of 20

NH fuse-links gG 400VAC

double indicator/live gripping-lugs size 000, 00, 1, 2, 3

NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

LOW VOLTAGE IEC FUSES

IEC NH FUSE-LINKS

FEATURES & BENEFITS


• Dimensions according to DIN 43
620 Parts 1 to 4
• Non-isolated gripping lugs
• Double indicator
• Lead free contact blades
• 0% cadmium

APPLICATIONS
• gG: general purpose cable and line
protection

The NH system is classified among plug-in fuse systems and is STANDARDS


composed of: • VDE 0636 Part 201
• fuse-base (possibly including terminal covers and phase barriers) • IEC 60269-1 and -2

• fuse-link with blade contact

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
• fuse-link replacement device (LV HRC fuse puller)
Since the design of this system cannot guarantee
non-interchangeability of rated current it must be handled by a
qualified professional.

Type “gG” NH fuse-links are full range breaking capacity fuse-links


and are used to protect cables and equipment. They can interrupt
any current surge, from the lowest fusing current up to their breaking
capacity, and so can be used alone as protection. They also protect
electrical devices and industrial set-ups from the electrodynamic
effects of very high short-circuit currents.

Rated Power Dissipation values of Mersen NH fuse-links 400VAC are


below the maximum values required by standard IEC 60269.

TECHNICAL DATA OVERVIEW


Voltage AC 400 VAC
Ampere Range (A) 2 ... 630 A
Size per Standard Sizes 000 to 3
Speed/Characteristic gG
I.R. AC (IEC) 100 kA
Body Material ceramic
Contact Materials copper, silver-plated

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 1
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRODUCT RANGE
Size 000 gG 400VAC

Catalog Item Rated voltage AC Power dissipation


Rated current In Width Package Weight
number number (IEC) at In
NH000GG40V35
NH000GG40V2 Z223674 400 V 2 A 0.7 W 20.8 mm 3 0.13 kg
NH000GG40V4 A223675 400 V 4 A 0.9 W 20.8 mm 3 0.13 kg
NH000GG40V6 B223676 400 V 6 A 1.2 W 20.8 mm 3 0.13 kg
NH000GG40V10 C223677 400 V 10 A 1.3 W 20.8 mm 3 0.13 kg
NH000GG40V16 D223678 400 V 16 A 1.6 W 20.8 mm 9 0.13 kg
NH000GG40V20 E223679 400 V 20 A 1.9 W 20.8 mm 9 0.13 kg
NH000GG40V25 F223680 400 V 25 A 2.2 W 20.8 mm 9 0.13 kg
NH000GG40V32 G223681 400 V 32 A 2.7 W 20.8 mm 9 0.13 kg
NH000GG40V35 H223682 400 V 35 A 3.1 W 20.8 mm 9 0.13 kg
NH000GG40V40 J223683 400 V 40 A 3.5 W 20.8 mm 9 0.13 kg
NH000GG40V50 K223684 400 V 50 A 3.9 W 20.8 mm 9 0.13 kg
NH000GG40V63 L223685 400 V 63 A 5.2 W 20.8 mm 9 0.13 kg
NH000GG40V80 M223686 400 V 80 A 5.3 W 20.8 mm 9 0.13 kg
NH000GG40V100 N223687 400 V 100 A 5.7 W 20.8 mm 9 0.13 kg

Size 00 gG 400VAC

Catalog Item Rated voltage AC Power dissipation


Rated current In Width Package Weight
number number (IEC) at In
NH00GG40V160
NH00GG40V125 E223702 400 V 125 A 7.4 W 29.5 mm 3 0.2 kg
NH00GG40V160 F223703 400 V 160 A 8.3 W 29.5 mm 3 0.2 kg

Size 1 gG 400VAC

Catalog Item Rated voltage AC Power dissipation


Rated current In Width Package Weight
number number (IEC) at In

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
NH1GG40V35 J223706 400 V 35 A 4 W 29.5 mm 3 0.28 kg
NH1GG40V50 K223707 400 V 50 A 5.2 W 29.5 mm 3 0.28 kg
NH1GG40V125
NH1GG40V63 L223708 400 V 63 A 6.8 W 29.5 mm 3 0.28 kg
NH1GG40V80 M223709 400 V 80 A 6.2 W 29.5 mm 3 0.28 kg
NH1GG40V100 N223710 400 V 100 A 8.6 W 29.5 mm 3 0.28 kg
NH1GG40V125 P223711 400 V 125 A 9.8 W 29.5 mm 3 0.28 kg
NH1GG40V160 Q223712 400 V 160 A 12.4 W 39.5 mm 3 0.41 kg
NH1GG40V200 R223713 400 V 200 A 14.4 W 39.5 mm 3 0.41 kg
NH1GG40V224 S223714 400 V 224 A 15.6 W 39.5 mm 3 0.41 kg
NH1GG40V250 T223715 400 V 250 A 17.6 W 39.5 mm 3 0.41 kg

Size 2 gG 400VAC

Catalog Item Rated voltage AC Power dissipation


Rated current In Width Package Weight
number number (IEC) at In

NH2GG40V35 T227257 400 V 35 A 4.1 W 29.5 mm 3 0.42 kg


NH2GG40V50 V227258 400 V 50 A 5.4 W 29.5 mm 3 0.42 kg
NH2GG40V250 NH2GG40V63 W227259 400 V 63 A 6.8 W 29.5 mm 3 0.42 kg
NH2GG40V80 F223726 400 V 80 A 6.4 W 29.5 mm 3 0.42 kg
NH2GG40V100 G223727 400 V 100 A 8.1 W 29.5 mm 3 0.42 kg
NH2GG40V125 H223728 400 V 125 A 10.2 W 29.5 mm 3 0.42 kg
NH2GG40V160 J223729 400 V 160 A 10.8 W 29.5 mm 3 0.42 kg
NH2GG40V200 K223730 400 V 200 A 15.2 W 29.5 mm 3 0.42 kg
NH2GG40V224 L223731 400 V 224 A 14.7 W 29.5 mm 3 0.42 kg
NH2GG40V250 M223732 400 V 250 A 17.1 W 29.5 mm 3 0.42 kg
NH2GG40V315 N223733 400 V 315 A 20.1 W 39.5 mm 3 0.64 kg
NH2GG40V355 P223734 400 V 355 A 22.6 W 39.5 mm 3 0.64 kg
NH2GG40V400 Q223735 400 V 400 A 25.4 W 39.5 mm 3 0.64 kg

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 2
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRODUCT RANGE
Size 3 gG 400VAC

Catalog Item Rated voltage AC Power dissipation


Rated current In Width Package Weight
number number (IEC) at In

NH3GG40V250 R223736 400 V 250 A 15.4 W 39.5 mm 1 0.65 kg


NH3GG40V315 S223737 400 V 315 A 19.8 W 39.5 mm 1 0.65 kg
NH3GG40V400 T223738 400 V 400 A 25.1 W 39.5 mm 1 1.05 kg
NH3GG40V500 V223739 400 V 500 A 31.1 W 51 mm 1 1.05 kg
NH3GG40V630 W223740 400 V 630 A 39 W 51 mm 1 1.05 kg

TECHNICAL DATA
Size 000 gG 400VAC Size 00 gG 400VAC Size 1 gG 400VAC Size 2 gG 400VAC Size 3 gG 400VAC
Rated current 2 ... 100 A 125 ... 160 A 35 ... 250 A 35 ... 400 A 250 ... 630 A
Rated breaking capacity AC 100 kA 100 kA 100 kA 100 kA 100 kA
Rated voltage AC 400 V 400 V 400 V 400 V 400 V
Indication System double indicator double indicator double indicator double indicator double indicator
Width 21 mm 30 mm 40 mm 51 mm 70 mm

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 3
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

TIME CURRENT CHARACTERISTIC CURVES


Size 000

10000
7000
5000
2A
3000

2000 4A
Pre-arcing time (s)

6A
1000
700 10 A
500
16 A
300

200 20 A

25 A
100
70 32 A
50
35 A
30

20 40 A

50 A
10
7 63 A
5
80 A
3

2 100 A

1
0.7
0.5

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.3

0.2

0.1
0.07
0.05

0.03

0.02

0.01
0.007
0.005

0.003

0.002

0.001
0.0007
0.0005

0.0003

0.0002

0.0001
3

10

20

30

50

70

100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

RMS value of prospective current (A) +/- 8%

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 4
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

TIME CURRENT CHARACTERISTIC CURVES


Size 00

10000
7000
5000

3000

2000
Pre-arcing time (s)

1000
700
500

300

200

100
70
50

30

20

10
7
5

2
125 A
1
0.7
0.5 160 A

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.3

0.2

0.1
0.07
0.05

0.03

0.02

0.01
0.007
0.005

0.003

0.002

0.001
0.0007
0.0005

0.0003

0.0002

0.0001
10

20

30

50

70

100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

RMS value of prospective current (A) +/- 8%

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 5
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

TIME CURRENT CHARACTERISTIC CURVES


Size 1

10000
7000
5000

3000

2000
Pre-arcing time (s)

35 A
1000
700
50 A
500

300 63 A
200
80 A

100
100 A
70
50 125 A
30
160 A
20

200 A
10
7 224 A
5
250 A
3

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.7
0.5

0.3

0.2

0.1
0.07
0.05

0.03

0.02

0.01
0.007
0.005

0.003

0.002

0.001
0.0007
0.0005

0.0003

0.0002

0.0001
30

50

70

100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

RMS value of prospective current (A) +/- 8%

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 6
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

TIME CURRENT CHARACTERISTIC CURVES


Size 2

10000
7000
5000

3000

2000
Pre-arcing time (s)

1000
700
500 35 A

300
50 A
200
63 A
100
70 80 A
50
100 A
30

20 125 A

10 160 A
7
5 200 A

3 224 A
2
250 A
1
0.7 315 A
0.5
355 A

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.3

0.2 400 A

0.1
0.07
0.05

0.03

0.02

0.01
0.007
0.005

0.003

0.002

0.001
0.0007
0.0005

0.0003

0.0002

0.0001
10

20

30

50

70

100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

RMS value of prospective current (A) +/- 8%

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 7
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

TIME CURRENT CHARACTERISTIC CURVES


Size 3

10000
7000
5000

3000

2000
Pre-arcing time (s)

250 A
1000
700
500

300
315 A
200

100
70
50 400 A

30

20

10 500 A
7
5

2 630 A

1
0.7
0.5

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
0.3

0.2

0.1
0.07
0.05

0.03

0.02

0.01
0.007
0.005

0.003

0.002

0.001
0.0007
0.0005

0.0003

0.0002

0.0001
100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06

RMS value of prospective current (A) +/- 8%

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 8
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

CUT-OFF CURRENT CHARACTERISTIC


Size 000

20000
100 A
80 A
10000 lm = 2.3 lp
63 A
7000

5000
50 A
Maximum peak let thru current Ic (A)

40 A
3000
35 A
2000
32 A
25 A
1000
20 A
700
16 A
500
10 A
300 6A

200 4A
2A

100

70

50

30

20
10

20

30

50

70

100

200

300

500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
50 Hz RMS symmetrical prospective current Ip (A)

Size 00

30000

20000 lm = 2.3 lp 160 A

125 A

10000
Maximum peak let thru current Ic (A)

7000

5000

3000

2000

1000
500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06

50 Hz RMS symmetrical prospective current Ip (A)

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 9
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

CUT-OFF CURRENT CHARACTERISTIC


Size 1

50000
250 A

30000 224 A

200 A
20000
160 A
Maximum peak let thru current Ic (A)

lm = 2.3 lp
125 A
10000
100 A
7000
80 A
5000 63 A

50 A
3000
35 A
2000

1000
500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06
50 Hz RMS symmetrical prospective current Ip (A)

Size 2

100000

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
400 A
70000
355 A
50000
315 A

250 A
Maximum peak let thru current Ic (A)

30000
lm = 2.3 lp 224 A
20000
200 A

160 A
10000 125 A

7000 100 A

5000 80 A

63 A
3000 50 A

2000 35 A

1000
500

700

1000

2000

3000

5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06

50 Hz RMS symmetrical prospective current Ip (A)

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 10
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

CUT-OFF CURRENT CHARACTERISTIC


Size 3

100000
lm = 2.3 lp 630 A
70000
500 A
50000

400 A
Maximum peak let thru current Ic (A)

30000
315 A
20000

250 A

10000
5000

7000

10000

20000

30000

50000

70000

100000

200000

300000

500000

700000

1e+06
50 Hz RMS symmetrical prospective current Ip (A)

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 11
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRE-ARCING AND OPERATING I²T CHARACTERISTICS


Size 000

200000
400V
230V

100000 pre-arcing I²t

70000
Pre-arcing and operating I²t (A²s)

50000

30000

20000

10000

7000

5000

3000

2000

1000

700

500

300

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
200

100

70

50

30

20

10

2
2

10

16

20

25

32

35

40

50

63

80

100

Rated current (A)

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 12
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRE-ARCING AND OPERATING I²T CHARACTERISTICS


Size 00

300000
400V
200000 230V

pre-arcing I²t

100000
Pre-arcing and operating I²t (A²s)

70000

50000

30000

20000

10000

7000

5000

3000

2000
125

160

Rated current (A)

Size 1

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
1000000
400V
700000 230V

500000 pre-arcing I²t

300000
Pre-arcing and operating I²t (A²s)

200000

100000

70000

50000

30000

20000

10000

7000

5000

3000

2000
35

50

63

80

100

125

160

200

224

250

Rated current (A)

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 13
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRE-ARCING AND OPERATING I²T CHARACTERISTICS


Size 2

3000000
400V
2000000 230V

pre-arcing I²t

1000000
Pre-arcing and operating I²t (A²s)

700000

500000

300000

200000

100000

70000

50000

30000

20000

10000

7000

5000

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
3000

2000
35

50

63

80

100

125

160

200

224

250

315

355

400
Rated current (A)

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 14
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

PRE-ARCING AND OPERATING I²T CHARACTERISTICS


Size 3

10000000
400V
7000000 230V

5000000 pre-arcing I²t

3000000
Pre-arcing and operating I²t (A²s)

2000000

1000000

700000

500000

300000

200000

100000
250

315

400

500

630

Rated current (A)

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 15
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

DIMENSIONS
Size 000 with double indicator (0118997C)

+5
49 ± 1.5 16
-2
45 ± 1.5 0
Indicator lever +0.1 10
2 -0.3
visible after -0.5 0
operation of fuse 6
-0.3

+0.5
0

2 min
2.5
0
-1
10
15 min.

35 ± 0.8
52.5

41 max
= =

78.5 ± 1.5

21 max

Visibility of red indicator signals conduction of the fuse-link.

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
After operation the red indicator is no longer visible
6 ± 0.2

Dimensions in mm

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 16
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

DIMENSIONS
Size 00 with double indicator (118998 D)

20 ± 5 0
49 ± 1.5 10
-0.3

Indicator lever 45 ± 1.5 0


visible after 6
-0.3
operation of fuse

0.5
0
+1
2

2.5

2 min
-0.5

0
-1
10

35 ± 0.8
60 max.
15 min.

48 max.
= =

78.5 ± 1.5
30 max

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
Visibility of red indicator signals conduction of the fuse-link.
After operation the red indicator is no longer visible
6 ± 0.2

Dimensions in mm

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 17
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

DIMENSIONS
Size 1 with double indicator (118997 D)

+5
20 0
68 ± 2.5 -2 10
+1.5 -0.3
Indicator lever 62 ± 2.5 2.5
visible after -0.5

+0.5
0
operation of fuse

2 min
2.5
0
-2
11
(64 max)

40 ± 0.8
20 min

53 max
= =

135 ± 2.5 40 max

Visibility of red indicator signals conduction of the fuse-link.


After operation the red indicator is no longer visible

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
6 ± 0.2

Dimensions in mm

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 18
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

DIMENSIONS
Size 2 with double indicator (119001 C)

+5
68 ± 2.5 20
Indicator lever 0
-2 10
visible after +1.5 0
62 ± 2.5 2.5 -0.3
6

+0.5
0
operation of fuse -0.5 -0.3

2.5
0
-2

2 min
11

48 ± 0.8
74 max.

60 max.
25 min.
= = 52 max

150 ± 2.5

Visibility of red indicator signals conduction of the fuse-link.


After operation the red indicator is no longer visible

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
6 ± 0.2

Dimensions in mm

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 19
NH fuse-links gG 400VAC
double indicator/live gripping-lugs size 000, 00, 1, 2, 3

DIMENSIONS
Size 3 with double indicator (119002 C)

+5
20
68 ± 2.5 -2 0
10
Indicator lever 62 ± 2.5 +1.5 0 -0.3
2.5 6

+0.5
0
visible after
-0.5 -0.3
operation of fuse

2 min
2.5
0
-2
10

60 ± 0.8
89 max.

76 max.
32 min.

= =

150 ± 2.5 72 max.

Visibility of red indicator signals conduction of the fuse-link.


After operation the red indicator is no longer visible

MERSEN reserves the right to change, update or correct, without notice, any information contained in this datasheet.
6 ± 0.2

Dimensions in mm

Low Voltage IEC Fuses / / DS-LFBCG4-04-0717_EN

EP.MERSEN.COM 20