HAKODATE DOCK Co.,LTD 0712263C
PATIENT
FOR FINAL
CARBON DIOXIDE FIRE EXTINGUISHING SYSTEM
SMOKE DETECTING SYSTEM
SPECIFICATION & DRAWINGS
SNO.793
FINISHED PLAN
35767-3928
5763-6360CHAPTER-1 SPECIFICATION OF CO, FIRE EXTINGUISHES SYSTEMS
JOBNO. : 0712263C
- . DATE : 2004/9/10
SHIPYARD. : HAKODATE DOCK CO.,LTD
SHIPNO, —:_-SNO.793
General
This specification is provided for CO2 Fire Extinguishing System to be installed in
ENGINE ROOM and CARGO HOLD.
Scope of System
(1) 1 set of CO2 Fire Extinguishing System. (See detail on enclosed list)
(2) 1 set of Smoke Detecting System. (See detail on enclosed list)
Date of Delivery
2004/5/1
Applied Rules and Regulations
FLAG : PANAMA
CLASS : NK
REGULATIONS : JIS,SOLAS 1974,1978,2000.
Production Test
(1) CO2 Cylinders, Selection Valves, CO2 Manifold Pipes and Guide Pipes to be tested
under the présence of NIPPON HAKUYOHIN KENTEI KYOKAI (THE EQUIPMENT
INSPECTION SOCIETY OF JAPAN)
(2) CO2 Cylinder Valves to be tested under the presence of JAPANESE GOVERNMENTCALCI
1. Required Quantity of CO2 is Shown in The Following Table.
W : Necessary quantity of CO2 (Kg)*
Volume of protected space (m3)
CO2 concentration )
Quantity of CO2 cylinder (contained 55.0 Kg of CO2)
Quantity of Nozzle
Size of Selection Valve (A)
wozwmacd
* 1 [Kg] of CO2 = 0.56 [m3] W=V XC X 1/0.56
hol . |
NAME OF SPACE Vim3] | Cx) | Wikel ALARM
ENGINE ROOM 3853m3}
CASING SIREN X 2
ENGINE ROOM
INO.1 CARGO HOLD:
INO.2 CARGO HOLD
INO.3 CARGO HOLD
INO.4 CARGO HOLD
a
6 [NO.5 CARGO HOLD
1
* Free air of air reservoir in engine room is included. (127.5m3)
1. Quantity of CO2 on Board is as Follows
(1) Type of CO2 Bottle : 82.5 {L] / 55 [Kg]
(2) Quantity of CO2 Bottle : 88
3) Total Quantity of CO2 : 4840.0 [Kg]”
‘The largest of calculated quantity for each protected objects shown in the above table is the quantity of
CO2 on board.