Professional Documents
Culture Documents
Zone 2
Zone 21
Zone 22
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 1
ATEX in English
From the first of July 2003 all explosion-protected electrical apparatus must Division of explosion-protected a pparatus into temperature c lasses T1 –
ha ve a type approval according to the ATEX directive, to be allowed to T6. The ignition temperature is the lowest temperature of a surface at
manufacture and distribute within the European Union. which an explosive atmosphere will ignite.
In the new EG-Ex-Frame Directive 94/9/EG ( ATEX 95a) dust ignition protec- The maximum surface temperature of an apparatus must always be lower
tion has been included and is now handled in the same way as gas explo- than the ignition temperature of the gas/air or vapour/air mixture. Gener-
sion protection. ally speaking, explosion-protected apparatus must be suitable for an am-
bient temperature from –20 °C to +40 °C.
Standards for the manufacture of explosion-protected electrical appara-
tus
Temperature class Max surface temperature
GAS AREAS DUST AREAS T1 450 °C
T2 300 °C
Zone Standard Marking Zone Standard Marking
T3 200 °C
Zone 0 EN 50284 II 1 G Zone 20 EN 50281 II 1 D T4 135 °C
Zone 1 EN 50014-20 II 2 G Zone 21 EN 50281 II 2 D T5 100 °C
Zone 2 EN 50021 II 3 G Zone 22 EN 50281 II 3 D T6 85 °C
Areas, which are hazardous due to presence of explosive gas, vapours Temperature marking for dust Ex-apparatus
and mist or dust/air mixture are divided into Zones as follows:
Unlike the marking for gas Ex a pparatus the tempera ture class ( T1 – T6) is
Occurance of explosive gas/dust Zones acc. to not given but the max. suface temperature T... °C.
or dust/air mixture atmosphere CENELEC/IEC In addition the IP-rating of the enclosure must be given. Protection against
Explosive gases, vapours Continuously, for long periods or Zone 0 dust ingress in enclosures IP6x (Zone 20 and 21) and IP5X (zone 22)
and mist frequently.
Explosive gases, vapours Occasional occurence is likely Zone 1 For further information, please visit our web-site www.malux.fi.
and mist
Explosive gases, vapours Occurence is not likely, but if
and mist occurs then only rarely and only Zone 2 Product overview
for a short period
Dust/air mixture Combustible dust, as a cloud, In this catalogue Malux introduces light fittings for Zone 2, Zone 21 and
is present continuously or fre- Zone 20
quently during normal operation Zone 22 on page 4.
Dust/air mixture Combustible dust, as a cloud, is likely Zone 21
to occur during normal operation.
Dust/air mixture Combustible dust clouds may
occur infrequently, and persist for Zone 22
only short periods.
The ATEX directive also newly regulates the classifica tion and marking of
apparatus for use in hazardous areas.
Apparatus is now classified in two groups, which are divided into catego-
ries.
Apparatus Group I = Apparatus for mining operation
Apparatus Group II = Apparatus for use in all other hazardous areas
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
2 E-mail: info@malux.fi • Internet: www.malux.fi
ATEX suomeksi
Heinäkuun 1. päivästä 2003 lähtien kaikkien räjähdysturvallisten laitteiden Ryhmä I kaivoslaitteet – Luokat M1 ja M2
tulee olla ATEX-direktiivin mukaisesti tyyppihyväksyttyjä, jotta niitä saa Ryhmä II palavat kaasut ja pölyt – Luokat 1, 2, 3
valmistaa ja toimittaa EU-alueen sisällä.
Uudessa EG-Ex-Frame Direktiivissä 94/9 EG( ATEX 95a) räjähdysvaarallinen Palavat aineet Tilaluokat Laite- Laite- Lailte-
CENELEC/IEC ryhmä luokka merkintä
pöly on uutena asiana liitetty mukaan. Kaasu, höyr y, sumu Tilaluokka 0 II 1G II 1 G
Kaasu, höyr y, sumu Tilaluokka 1 II 2G II 2 G
Räjähdysturvallisten sähkölaitteiden standardit Kaasu, höyr y, sumu Tilaluokka 2 II 3G II 3 G
Pöly Tilaluokka 20 II 1D II 1 D
Kaasu Pöly Pöly Tilaluokka 21 II 2D II 2 D
Pöly Tilaluokka 22 II 3D II 3 D
Tilaluokka Standardi Merkintä Tilaluokka Standardi Merkintä
0 EN 50284 II 1 G 20 EN 50281 II 1 D
Lämpötilaluokat - kaasu
1 EN 50014-20 II 2 G 21 EN 50281 II 2 D
2 EN 50021 II 3 G 22 EN 50281 II 3 D Räjähdysturvallisten laitteiden luokitus lämpötilaluokkiin T1–T6.
Syttymislämpötila, on alhaisin lämpötila, jonka on oltava laitteen pinnalla,
jotta jokin tietty kaasusekoitus pystyy syttymään. Laitteen pinnan maksimi
Alueet, jotka katsotaan kuuluviksi räjähdysvaarallisten tilojen piiriin, on
lämpötila on aina oltava alhaisempi kuin kaasusekoituksen syttymis-
jaettu tilaluokkiin
lämpötila. Yleisesti voidaan sanoa että räjähdysturvallisten laitteiden on
oltava sopivia ympäristölämpötilaan –20°C...+40°C.
Palavat aineet Tilat Tilaluokat
CENELEC/IEC
mukaan Lämpötilaluokka Suurin sallittu pintalämpötila
Kaasu, höyry, sumu Tila, jossa ilman ja kaasun, höyryn tai T1 450 °C
sumun muodossa olevan palavan Tilaluokka 0
aineen muodostama räjähdyskelpoinen T2 300 °C
ilmaseos esiintyy jatkuvasti, pitkäaikaisesti T3 200 °C
tai usein T4 135 °C
Kaasu, höyry, sumu Tila, jossa ilman ja kaasun, höyryn tai sumun T5 100 °C
muodossa olevan palavan aineen muodosta-
ma räjähdyskelpoinen ilmaseos toden- Tilaluokka 1 T6 85 °C
näköisesti esiintyy normaalitoiminnassa
satunnaisesti.
Kaasu, höyry, sumu Tila, jossa ilman ja kaasun, höyryn tai sumun Lämpötilamerkinnät D (pöly) laitteille.
muodossa olevan palavan aineen muodosta- Räjähdysvaarallisissa pölyisissä ympäristöissä käytettävät laitteet merkitään
ma räjähdyskelpoisen ilmaseoksen esiinty- Tilaluokka 2
minen on normaalitoiminnassa epätoden- suurimmalla pintalämpötilalla Txx °C.
näköistä ja se kestää esiintyessään vain
lyhyen ajan. D laitteille on myös ilmoitettava kotelon IP luokitus. Vaatimus on IP6x
Pöly Tila, jossa ilman ja palavan pölyn muodos- (Tilaluokat 20 ja 21) ja IP5x (Tilaluokka 22)
tama räjähdyskelpoinen ilmaseos esiintyy Tilaluokka 20
jatkuvasti, pitkäaikaisesti ja usein.
Pöly Tila, jossa ilman ja palavan pölyn muodos- Valintasäännöt
tama räjähdyskelpoinen ilmaseos toden- Tilaluokka 21
näköisesti esiintyy normaalitoiminnassa Sähkölaitteiden valintasäännöt sähköturvallisuusmääräysten §14:n mukaan
satunnaisesti. umpeutuu 30.6.2003 ja 1.7.2003 on noudatettava standardi
Pöly Tila, jossa ilman ja palavan pölyn muodos- SFS-EN 60079-14 määräyksiä.
tama räjähdyskelpoisen ilmaseoksen esiin- Tilaluokka 22
tyminen normaalitoiminnassa on epätoden- Käytännössä tämä merkitsee muutoksia laitevalinnoissa esim. Tilaluokka
näköistä ja se kestää esiintyessään vain
lyhyen ajan. 2:n tiloissa. Vanhojen määräysten mukaan Tilaluokka 2:n tiloihin riitti IP54
kotelointiluokan valaisin – uusien määräysten mukaan voidaan Tilaluokkaan
2 asentaa seuraavia sähkölaitteita:
a) Tilaluokkien 0 tai 1 sähkölaitteita
Huomautukset: b) erityisesti Tilaluokkaan 2 suunniteltuja laitteita (esim. suojarakenne
”n” standardin SFS-EN 50021 mukaan) tai
1. Pölykerroksiin, -kertymiin, ja kasaantumiin on suhtauduttava kuten mihin
c) sähkölaitteita, jotka täyttävät teollisuussähkölaitteita koskevien standar-
tahansa lähteeseen, joka saattaa aiheuttaa räjähdyskelpoisen
dien vaatimukset, ja joissa normaalikäytössä ei esiinny sytyttämiseen
ilmaseoksen.
pystyviä kuumia pintoja ja
2. Normaalitoiminnalla tarkoitetaan tilannetta, jossa laitetta käytetään 1) jotka normaalitoiminnassa eivät aiheuta valokaaria tai kipinöitä, tai
suunnitteluarvojen sallimissa rajoissa. 2) jotka normaalitoiminnassa aiheuttavat valokaaria tai kipinöitä, mutta
piirin (kaapelointi mukaanlukien) sähköiset parametrit (U,I,L,C) eivät
ylitä standardissa SFS EN-50020 määriteltyjä arvoja varmuus-
Tarkemmat tiedot ATEX direktiivistä löytyy kotisivuillamme kertoimella 1. Arvioinnissa on noudettava standardissa SFS EN50021
www.malux.fi tai soittamalla meille (019) 5745 700. annettuja vaatimuksia rajoitetun energian laitteille ja piireille.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 3
Table of content
Sisällysluettelo
In this catalogue Malux introduces light fittings for Zone 2, Zone 21 and Zone 22
Tässä luettelossa Malux esittelee Tilaluokka 2:n valaisimia, jotka ovat sivulla 3 “Valintasääntöjen” b) vaihtoehdon mukaisia.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
4 E-mail: info@malux.fi • Internet: www.malux.fi
Light fitting for Zone 2, Zone 21
and Zone 22
Technical data:
Series nLLK 98
Marking Ex II 3 G (gas)
Ex II 2 D/3D T80°C (dust)
Diffuser Polycarbonate
Degree of protection IP 65
Protection class I
Cable entries 2 x EEx e cable entry M25 x 1,5 for cables Ø 8–17 mm
2 x EEx e M25 blanking plug
Accessories
Type Item no.
D92 580 506 Ceiling bracket, one pair
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 5
Fittings for Zone 2 and Zone 22
Technical data:
EB versions:
• Recessing frames
Note!
Also available in explosion proof version, zone 1 as well as in n181... / n182 with ceiling brackets 15A P
industrial version.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
6 E-mail: info@malux.fi • Internet: www.malux.fi
Fittings for Zone 2 and Zone 22
EB - recessing frames
SA - Swivelarm
The n 181 / 182 can be supplied with swivelarm mounting systems. The
swivelarm can be mounted at anytime.
SA Swivelarm
Accessories
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 7
Light fitting for Zone 2 and Zone 22
Diffuser Polycarbonate
Degree of protection IP 65
Protection class II
nD 161 nD 162
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
8 E-mail: info@malux.fi • Internet: www.malux.fi
Light fitting for Zone 2 and Zone 22
with battery for emergency light
Technical data:
Protection class I
switch switch
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 9
Hermetically sealed fitting for dust
Ex-hazardous areas, Zone 21 and 22
Technical data:
Diffuser Polycarbonate
Accessories:
• Protective grid
• Mast mounted by clamp
• Protection canopy, angular or curved. A hermetically sealed case for fluorescent tubes,
that is very easy to maintain. Its resistance to cor-
• Inner colour film rosion and impacts and its total air-tightness make
• Support handle it suitable for damp and corrosive environments.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
10 E-mail: info@malux.fi • Internet: www.malux.fi
Hermetically sealed fitting for dust
Ex-hazardous areas, Zone 2, 21 and 22
Technical data:
Series KEPLER T8
Diffuser Polycarbonate
KEPL 118E G13 PO SA1941 0010 1 x 18W G13 133 745 3,0
KEPL 136E G13 PO SA1941 0020 1 x 36W G13 133 1355 5,0
KEPL 158E G13 PO SA1941 0030 1 x 58W G13 133 1655 5,6
KEPL 218E G13 PO SA1942 0010 2 x 18W G13 133 745 3,1
KEPL 236E G13 PO SA1942 0020 2 x 36W G13 133 1355 5,0
KEPL 258E G13 PO SA1942 0030 2 x 58W G13 133 1655 5,6
Accessories:
• Protective grid
• Mast mounted by clamp
• Protection canopy, angular or curved.
• Inner colour film A hermetically sealed case for fluorescent tubes,
that is very easy to maintain. Its resistance to cor-
• Support handle rosion and impacts and its total air-tightness make
it suitable for damp and corrosive environments.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 11
Compact light fitting for
Zone 2 and Zone 22
Technical data:
Series nD 131... EVG
Explosion protection Ex II 3 G EEx nA II T4
II 3 D T70° IP 65
Certificate Manufacturers certificate
Enclosure Polycarbonate
Diffuser Polycarbonate
Rated voltage 230–240V ± 10%, 0 alt. 50–60 Hz
Degree of protection IP65/I
Ambient temp. –20 °C to +40 °C
Applications In humid, wet and dusty explosive atmospheres of Zone 2 and Zone 22
nD 131... EVG
1)
Asymetric light beam
Installation:
• There are two holes for ceiling mounting. Rubber gaskets and washers
are inside the fitting.
• Cable entry:
2 entries M20x1,5 mm2 (2 glands, one of them is plugged),
3-pole terminal connection. 265/76
• Not for through-wiring.
Accessories:
• Self-adhesive pictograms for illuminating emergency exit acc. to VGB 125
and DIN 4844.
• Sighting distance acc. to DIN 5035, section 5 and DIN 4844 = 15 m.
• Further sign labels or legends can be supplied upon request.
Last update 8/2007
Malux Finland Oy, P.O.Box 69 • FI-06151 Porvoo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 13
Explosion-proof floodlight
of Zone 2 and Zone 22
Technical data:
n 2770... n 2770
up to 150 W, low bay / high bay version
n 2780
up to 500 W, low bay version
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 13
Explosion-proof non-sparking
light fitting, Zone 2
Technical data:
Series 800 N
Protection Ex N II
Design Options
• Highly corrosion resistant stainless steel 316 S31 construction. • Spigot mounting
• Quick release fasteners for ease of relamping and access to mains • Pole mounting bracket.
terminals and internal control gear. • Wide and narrow beam reflector. Floodlight version
• High efficiency asymmentric reflector. containing ignitor only for remote operation.
• UL 595 listing. Available to special order only.
1) This luminaire contains an ignitor only and must be supplied by a remote control gearbox
of appropriate wattage.
Dimensions:
Types A B C D E F
844 308 443 75 348 150 175
854 415 630 150 490 185 260
864 456 640 150 490 219 260
2 x M20 entries
3 x ∅ 13 (854, 864)
3 x ∅ 12 (844)
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
14 E-mail: info@malux.fi • Internet: www.malux.fi
Floodlight with induction
lighting systems, Zone 2
Technical data:
Temperature class T4
Degree of protection IP 54
Protection class I
Applications:
• For use in industrial halls, especially for applications where changing light source
is difficult. The ENDURA lamp has a lifetime of > 60.000 hours.
Design:
• Material sheet steel, powder coated in yellow (RAL 1004). Safety glass with
hinges. Aluminium mirror reflector.
Connection:
• L1+N+PE max 2,5 mm2
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 15
Torch light with LED for Zone 2,
Zone 21 and Zone 22
Technical data:
EX II 2 D T90°C IP52
Dimension 140 x 26 mm (l x Ø)
Type Acticle
107540 Torch Light LITE-EX LED 30
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
16 E-mail: info@malux.fi • Internet: www.malux.fi
Light fittings for motor vehicle pits
Technical data:
Series 183
Degree of protection IP 65
Protection class I
Lighting fittings with sheet steel housings are not suitable for repair pits
where exists a continuous humidity or any corrosive atmosphere.
Angle of reflec-
tion max 45°
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 17
Light fitting for high IP68
- up to 3 Bar
Technical data:
Series AVL-TRITEGO
Design: Options:
• Protection tube of clear plastic (PMMA), op- • Version with T16 lighting tubes and two
tionally available in polycarbonate or boro- tinplates covering the connectors.
silicate glass, depending on the applications. • Protection tube of borosilicate glass 4 mm
• Plastic seals and fittings M20 in either end strong.
cap, resisting even water under pressure, • Through-wired by Y-system with screw fit-
one end sealed. tings. Version for continuous row lighting
• After unscrewing the two stainless steel includes round sleeve of stainless steel for
bolts at the end cap, the slide-in-unit of architeturally important areas.
the lamp can be removed easily. • Lamps have masks of punched tinplate for
• Connector plugs L1, N, PE up to 2,5 mm2 the starter and the connectors in 126 ver-
wire strength. sion.
• Safe contacts by isolated spring-clamps • Version with separately mounted protection
• Mounting to walls and ceilings in every po- tubes for the lamps and the starter device.
sition is possible. Suspension by chains or
ropes, or by using the stainless steel clamps
for direct installation on wall.
Type W L
MK2320EVG 1 x 18 1150
MK2330EVG 1 x 36 1720
MK2355EVG 1 x 58 2030
Mountingbrackets 2 pcs/lighting
MK4614 Wall and cealing
MK4616 Rope/chain suspension
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
18 E-mail: info@malux.fi • Internet: www.malux.fi
Dustproof/Waterproof fittings for
low ambient temperatures
Technical data:
Degree of protection IP 65
Protection class I
161...TT 162...TT
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 19
Fitting for damp and corrosive
environment, low temperatures
Technical data:
Series Pauli 2
Diffuser Polycarbonate
Degree of protection IP 68
Protection class I
IP 68 -I 850°
Ambient temperature +30 °C to -40 °C or 20 °C to -50 °C
-50° < T° < +20°
Fire resistant +850°C (see page 21) -40° < T° < +30°
Design:
• Neoprene or silicone gaskets
• Protective stainless steel top cover (optional)
• Internal reflector made of high-grade aluminium (optional for single fitting)
• Hermetically sealed
• Totally corrosion resistant
• Two-bracket mounting giving 360° adjustment angle
• Cable entry by 1 gland of 13 (sealed plug op tional)
• Special control gear 230 V, 50 Hz, compensated
• Connection to 3 x 2.5 mm2 teminal block
• No internal cleaning required
Options:
• Blanking cap, 2nd cable gland, alternate sizes of cable gland
• Input through a waterproof plug and socket 3 or 5 pin
• Special metal cable gland (brass, nickel plated brass, stainless steel)
• Special mounting brackets
• Internal aluminium reflector
• With electronic ballast or starter
• With borosilicate glass diffuser
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
20 E-mail: info@malux.fi • Internet: www.malux.fi
Dustproof/Waterproof fittings for
high ambient temperatures
Technical data:
Diffuser Polycarbonate
Degree of protection IP 65
162...HT
Protection class II
161...HT
Design:
• Housing made from glass fibre reinforced polyester resin.
Polyurethane gasket.
+50 °C luminaires:
Cover made out of injected, clear acrylic glass with internal
prisms (index: "PK"). The fittings have got external plastic clips
(KKL); safety plastic clips can be supplied as well at addi-
tional cost.
162...HT
Wiring:
• Uncomp., comp., capacitive or lead/lag.
+60 °C luminaires:
+50 °C (ambient temperature) luminaires
Cover made out of injected, clear polycarbonate glass with
internal prisms (index: "MAC"). The fittings have got external Type Item no. Lamps/watts kg
plastic clips (KKL); Safety plastic clips can be supplied at ad- 161118 PK HT50 SC16102 0001 1 x T26/18W 2,2
ditional cost. 161136 PK HT50 SC16102 0004 1 x T26/36W 3,3
161158 PK HT50 SC16102 0007 1 x T26/58W 4,7
Wiring: 162218 PK HT50 SC16203 0001 2 x T26/18W 2,8
• Uncomp., comp., capacitive or lead/lag. 162236 PK HT50 SC16203 0004 2 x T26/36W 5,0
+70 °C luminaires: 162258 PK HT50 SC16203 0007 2 x T26/58W 6,2
Cover made out of injected, clear polycarbonate glass with
internal prisms (index: "PC"). External stainless steel clip (KHV). +60 °C (ambient temperature) luminaires
Wiring: Type Item no. Lamps/watts kg
• The diffusers are marked at the front side either with PMMA- 161118 PK PC HT60 SC16102 0010 1 x T26/18W 2.2
S (acrylic) or with PC (polycarbonate). The ballasts and other 161136 PK PC HT60 SC16102 0013 1 x T26/36W 3.3
electrical components are mounted on the detachable white 161158 PK PC HT60 SC16102 0016 1 x T26/58W 4.7
polyester reflector and, thus, they are protected against acci- 162218 PK PC HT60 SC16203 0010 2 x T26/18W 2.8
dental contact. 162236 PK PC HT60 SC16203 0013 2 x T26/36W 5.0
• The standard equipment of each lighting fitting comprises a 162258 PK PC HT60 SC16203 0016 2 x T26/58W 6.2
2-pole connection terminal block as well as 2 plugs Pg 13.5.
A through wiring system up to 5 x 2.5 mm2 can be installed +70 0C (ambient temperature) luminaires
during assembly at extra charge.
Type Item no. Lamps/watts kg
Mounting system: 162118 PK PC HT70 SC16203 0019 1 x T26/18W 3.0
• There are rough-moulded holes in the housing for direct ceil- 162136 PK PC HT70 SC16203 0022 1 x T26/36W 4.7
ing mounting. Rubber sealing washers are inside each fitting. 162158 PK PC HT70 SC16203 0025 1 x T26/58W 6.4
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 21
Fitting for damp and corrosive
environment, high temperatures
Technical data:
Series Pauli 1
Degree of protection IP 68
Protection class I
Pauli 1 218 HT 80 SA3610 0010 2 x 18W G13 150 675 5,6 +80°C
Pauli 1 236 HT 80 SA3610 0020 2 x 36W G13 150 1285 10,3 +80°C
Pauli 1 258 HT 80 SA3610 0030 2 x 58W G13 150 1585 12,8 +80°C
Polycarbonate diffuser
Design:
• Neoprene or silicone gaskets.
• Hermetically sealed.
• Totally corrosion resistant.
• Two-bracket mounting giving 360° adjustment.
• Cable entry by 1 gland of 13 (sealed plug optional).
• Special fixture 230 V, 50 Hz compensated.
• Connection to 3 x 2.5 mm2 teminal block
• No internal cleaning required.
Options:
• Blanking cap, 2nd cable gland, alternate sizes of cable gland.
• Input through a waterproof plug and socket 3 or 5 pin.
• Special metal cable gland (brass, nickel plated brass, stainless steel)
• Special mounting brackets.
• Internal aluminium reflector
• With electronic ballast or starter A hermetically sealed case designed for damp
• Versions with polycarbonate diffuser and 2 lamps for +50 °C or corrosive environments and suitable for high
temperatures (kitchen extraction hoods, oven
• Versions for +100 °C with external ballast box
outlets).
Accessories:
• Protective grid
• Mast mounted by clamp
• Protection canopy, angular or curved.
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
22 E-mail: info@malux.fi • Internet: www.malux.fi
Portable Emergency light
Technical data:
Series W276.3/4
With Emergency lighting function (non-maintained mode) and integrated charging unit.
Power consumption 10 VA
Insulation class II
Lighting data:
distance illumination
5m 256 lux
20 m 16 lux
80 m 1 lux
Item no Type
590565 w 276.3/4
158910 sparelamp 5V/5W (5 pcs)
158905 sparelamp 4.8V/1.5W (10 pcs)
590850 wall bracket
590906 rechargable NiCd akku 4.8V/4Ah
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
E-mail: info@malux.fi • Internet: www.malux.fi 23
Classification of appliance
Insulation classes
The insulation class specifies the protection of persons against indi-
rect electric contact.
Protection Insulation Fire
index class resistance
Class
0 Functional insulation without earthing
IP XX - I I 960° Operating
I functional insulation with earthing
- 40° < T° < + 40° temp.
II double insulation without earthing
III Operation under ELV (V <50 v)
IP Test 1st figure: protection IP Test 2nd figure: protection IP Test 3rd figure:
against solid bodies against liquids mechanical protection
No protection
0 No protection 0 No protection 0
the vertical
500 g
Dust (no harmful Water jets projected by a nozzle
5 5 5 40cm 2j
deposit) from any direction.
9 40cm
20 j
Malux Finland Oy, P.O.Box 69 • FI-06151 Por voo • Phone: +358 (0)19 5745 700 • Fax: +358 (0)19 5745 750
24 E-mail: info@malux.fi • Internet: www.malux.fi
Other products
Ex-light fittings
Ex-installation units
Ex-sockets and plugs
Ex-control switches and safety switches
Ex-alarm equipment
Ex-heating devices
Ex-telephones
Exi-components and equipment
Ex-actuators
Ex-motors
Tachogenerators and encoders
Emergency lighting
Outdoor lighting
Underwater lighting