PSYCHROMETRICS 101

NATIONAL CAPITAL CHAPTER ASHRAE


WEDNESDAY, OCTOBER 7, 2015

Jesse Fisher, PE
jfisher@wbengineering.com
What is psychrometrics?
The field of engineering concerned with the
determination of physical and thermodynamic
properties of gas-vapor mixtures.
Dry Air Water Vapor

• Mixture of gases. • Heat of Vaporization is


• 78% Nitrogen approximately 1000
• 21% Oxygen
BTU/lbm

• Standard Temp = 59°F • Maximum amount of


water in dry air is
• Standard Press = 14.7 psi function of temperature
• Sensible Heat and pressure.
• Saturation is the point of
equilibrium between
moist air and the
condensed water phase.
• Latent Heat
HVAC PSYCHROMETRICS
The Psychrometric Chart
HVAC Psychrometrics

Psychrometric Chart
55
0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

0.35
90
50 1.30
200

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
HVAC Psychrometrics

Psychrometric Properties
Psychrometric Properties of Air

• Dry Bulb
Temperature
• Wet Bulb
Temperature
• Dew Point
Temperature
• Relative Humidity
• Humidity Ratio
Dry Bulb Temperature (DBT) 55

• Units: °F
0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• T: Absolute temperature (R or K) 50
90
200
0.35
1.30

• t: Relative Temperature (F or C) 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
- 1.15
45

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 Dry Bulb Temperature 45 0.30
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F

Dry Bulb Temperature; °F


Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Wet Bulb Temperature (DBT) 55

• NOT adiabatic saturation temp.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Units: °F 50
90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
Wet Bulb Temperature 0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30 -
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Dew Point Temperature (DPT or DP) 55

• Temperature when condensation


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

occurs. 50
90
200
0.35
1.30

• Units: °F 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

Dew Point Temperature; °F


dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
Dew Point Temperature - 0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Relative Humidity (RH) 55

• Unit less measure


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Ratio of W / WS 50
90 50%
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 50% 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
50% 110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60
50% 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50%
50
50
15 0.35
13.2

50
40 %
45 0.30
45
50%
13.0

40
40 35 0.25
30 % 40
35
12.8

50% 30 35 0.20
32
10 30
20% 30
12.6

50% 0.15
20 25
50% DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Humidity Ratio 55

• Mass Ratio: Water Vapor to Air


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Units: grains / lbm or lbm / lbm 50


90
200
0.35
1.30

• W: Humidity Ratio 190 1.25

14.6
• WS: Saturated Humidity Ratio
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia

Humidity Ratio; gr/lbm –or- lbm/lbm


160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
Humidity Ratio - 60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
HVAC Psychrometrics

“Other” Properties
Enthalpy (BTU/lbm) 55

• Total Energy; adiabatic saturation


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

temperature. 50
90
200
0.35
1.30

• H = Sen + Lat 190 1.25

14.6
• Lines are parallel
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


Enthalpy 0.75
70
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
- 50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Specific Volume 55

• Cubic Feet Air / Pound Mass


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Measure of Density 50
90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
Specific Volume 0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10
- 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Sensible Heat Ratio 55

• Defines the slop for the space


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

Sensible Heat Ratio


being served 50
90
200
0.35
1.30

• QS / QT 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER

Sensible Heat Ratio


. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
SHR = 0.6
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- 5 0% SHR = 1.0 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
HVAC Psychrometrics

Determining State Points


Determining State Points 55

• Any condition can be fixed


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

on the chart with just two 50


90
200
0.35
1.30

properties. 190 1.25

14.6
• Every property can be
85
85

14.8

15.0
1.20
180 0.40

determined once the state


45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
point is fixed on the chart.
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air: 95 DBT / 78 WBT
120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 Return Air: 75 DBT & 50% RH 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
HVAC PSYCHROMETRICS
Psychrometric Processes
Mixing 55

• Process line connection the two


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

state points being mixed. 50


90
200
0.35
1.30

• Mixed state point is 190 1.25

14.6
proportionally along the mixing
85
85

14.8

15.0
1.20
180 0.40

line.
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
Mixed Air: 25% OA
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Heating 55

• Q=1.08 x CFM x Delta T


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Sensible Only Process 50


90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
Mixed Winter Air Heating Supply Air
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Cooling 55

• QSEN=1.08 x CFM x Delta T


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• QTOTAL=4.45 X CFM x Delta h 50


90
200
0.35
1.30

• Cooling is sensible only until the 190 1.25

14.6
air is cooled below the DPT.
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 Summer Mixed Air
0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
Leaving Cooling Coil 5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Adiabatic Saturation 55

• Evaporative Cooling
0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Evaporative Humidification 50
90
200
0.35
1.30

• Constant enthalpy process 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
Evaporatively Cooled Supply Air 45
0.70
100

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
Hot & Dry OA 60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Humidification – Steam Injection 55

• Adds both sensible and latent


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

heat to the airstream. 50


90
200
0.35
1.30

• Exact slope varies by selection. 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 Winter: Humidified Air 80 0.90


60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 Winter: Dry Air TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Energy Recovery: Sensible 55

• OA: 95/78 to 83/75


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• EA: 75/63 to 89/67 50


90
200
0.35
1.30

• DtOA = 12°F 190 1.25

14.6
• DhOA = 3.3 BTU/lbm
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35
Summer: Leaving OA Summer: Entering OA

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 Summer: Entering EA Summer: Leaving EA 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Energy Recovery: Sensible 55

• OA: 10/9 to 49/34


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• EA: 70/53 to 33/32 50


90
200
0.35
1.30

• DtOA = 39°F 190 1.25

14.6
• DhOA = 9.1 BTU/lbm
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 Winter: Entering EA 35 0.25
30 % 40
35
12.8

Winter: Leaving EA 30 35 0.20


32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
r: Entering OA Winter: Leaving OA 10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Heat Recovery Performance
Energy Recovery: Total 55

• OA: 95/78 to 83/71


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• EA: 75/64 to 89/74 50


90
200
0.35
1.30

• DtOA = 12°F 190 1.25

14.6
• DhOA = 6.7 BTU/lbm
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Summer OA: Entering 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 Summer EA: Leaving 0.70
0.70
100 45

13.8
Summer OA: Leaving 0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
Summer EA: Entering 0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Energy Recovery: Total 55

• OA: 0/0 to 46/45.2


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• EA: 75/64 to 28.2/28.2 50


90
200
0.35
1.30

• DtOA = 46°F 190 1.25

14.6
• DhOA = 16.9 BTU/lbm
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
Winter EA: Entering 0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
Winter OA: Leaving 40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30Winter EA: Leaving
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Enthalpy Wheel Performance
HVAC PSYCHROMETRICS
Psychrometrics of Systems
HVAC Psychrometrics

DRAWING A SYSTEM
Drawing a System 55

• Identify the Outdoor Air Condition


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Identify the Return Air Condition 50


90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
%
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Drawing a System 55

• Draw the mixing line between both


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

state points. 50
90
200
0.35
1.30

• Locate the mixed air condition based 190 1.25

14.6
on OA percentage.
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
0.55
13.6

60 Mixed Air: 20% OA 80 0.90


60
0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
%
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Drawing a System 55

• Draw the cooling coil curve


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

down to the leaving cooling 50


90
200
0.35
1.30

coil condition. 190 1.25

14.6
• Does not quite reach
85
85

14.8

15.0
1.20
180 0.40

saturation; most
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed
psychrometric charts have

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and
cooling coil lines.

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
0.55
13.6

60 Mixed Air: 20% OA 80 0.90


60
0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
Leaving Cooling Coil %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Drawing a System 55

• The leaving cooling coil


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

condition, in the draw through 50


90
200
0.35
1.30

system, is not the supply air 190 1.25

14.6
temperature.
85
85

14.8

15.0
1.20
180 0.40

• Fan heat is a sensible only


45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed
heating process.

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
0.55
13.6

60 Mixed Air: 20% OA 80 0.90


60
0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Supply Air Temperature %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Drawing a System 55

• Close the system.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Be careful and follow the 50


90
200
0.35
1.30

sensible heat ratio slope from 190 1.25

14.6
your load calculations.
85
85

14.8

15.0
1.20
180 0.40

• DO NOT just close the system


45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed
loop.

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
0.55
13.6

60 Mixed Air: 20% OA 80 0.90


60
Space Condition 0.95 0.50
%
60 70
1.00
20 Return Air 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Supply Air Temperature %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Drawing a System 55

• Iterate to determine system


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

conditions. 50
90
200
0.35
1.30

• Sometimes you will find that 190 1.25

14.6
the space conditions are
85
85

14.8

15.0
1.20
180 0.40

outside acceptable design


45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed
conditions.

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
70
% Mixed Air: 20% OA 0.85
0.55
13.6

60 80 0.90
60
ReturnCondition
Space Air 0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Supply Air Temperature %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
HVAC Psychrometrics

AIR SIDE SYSTEM ANALYSIS


AIR SIDE SYSTEM ANALYSIS

Common Equations

QSensible = 1.08 x CFM x Dt [BTU/hr]


QLatent = 0.68 x CFM x Dw Change [BTU/hr]
QTotal = 4.45 x CFM x Dh [BTU/hr]

QTotal = Qsensible + QLatent


Constant Air Volume (CAV): 55

Design Day - Auditorium


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• High (60%) space RH at design 50


90
200
0.35
1.30

day. 190 1.25

14.6
• Design loads are with lights on.
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
Mixed Air: 25% OA 90 0.80 0.60
25
%
70
0.85
ReturnCondition
Space Air 0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Supply Air Temperature %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
CAV - Off Design: No Reheat 55

• Lights turned off.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• CAV adjusts SAT for temperature 50


90
200
0.35
1.30

control. 190 1.25

14.6
• Results in 73% RH in the space.
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
50% Load Space Condition 100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
ReturnCondition
Space Air 0.55
13.6

60
- 50% Load SAT 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Supply Air Temperature %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
CAV - Off Design: With Reheat 55

• Lights turned off.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• CAV adjusts SAT for temperature 50


90
200
0.35
1.30

control. 190 1.25

14.6
• Reheat coil kicks in for humidity
85
85

14.8

15.0
1.20
180 0.40

control.
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
ReturnCondition
-Space Air 0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- - 50% Load SAT
%
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Air System – Plenum Return 55

• Air Side Delta T increased.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Airflow decreased. 50
90
200
0.35
1.30

• Same Coil Capacity. 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ure
oist
170

m
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ed t

14.4
55

ocia
160 1.05

as s
0.45

- °F
80
80

and

E
UR
1.00

air

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
MP
0.95

er lb
0.50

TE
WE
TB

14.2
140

LB
up
ULB

BU
TEM

- Bt
0.90
PER

T
75

Y
ATU

WE
75 50

ALP
RE 130 0.55
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


TH
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70
0.85
Mixed Air: 25% OA 0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 Rm T Return Temperature 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
LC Supply Air Temp %
50 60 0.40
50
50
15 0.35
13.2

50
40%
45 0.30
45
13.0

40
40 35 0.25
30% 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Face and Bypass Cooling Coil 55

• Airstream splits through coil.


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Mixing of fully condition and 50


90
200
0.35
1.30

unconditioned air. 190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
Entering Cooling Coil 0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
Leaving Cooling Coil
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Min OA Cooling Coil 55

• Staged Coil Control


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Cools and Dehumidifies OA 50


90
200
0.35
1.30

before Return Air 190 1.25

14.6
• Provides dry supply air
85
85

14.8

15.0
1.20
180 0.40

temperatures at part load.


45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 Return Air 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
Leaving Coil
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Dedicated Outdoor Air Unit 55

• Total Energy Recovery


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Integral exhaust fan 50


90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 Exhaust Air 0.70
0.70
100 45

13.8
Entering Coil 0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
- Return Air 60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 LCC Supply Temp 0.45
13.4

55
5 0% 60 0.40
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Energy Recovery AHU 55

• Total Energy Recovery


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• 25% Outdoor air 50


90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45
OA: Post ERU

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
% Mixed Air
70 0.85
0.55
13.6

60 80 0.90
60
Return Air 0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
5 0% 60 0.40
- SAT
50
50
15 0.35
13.2

50
40 %
45 0.30
45
13.0

40
40 35 0.25
30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
High Latent Cooling AHU 55

• Space Design: 68°F & 35% RH


0.20 0.25 0.30
SENSIBLE HEAT RATIO = Qs / Qt

• Chilled Water: 45°F 50


90
200
0.35
1.30

190 1.25

14.6
85
85

14.8

15.0
1.20
180 0.40
45 1.15

ureist
170

mo
BAROMETRIC PRESSURE: 29.921 in. HG 1.10

ted
55

14.4
ocia
160 1.05

ass
0.45

- °F
80
80

nd

E
ir a

UR
1.00

AT
40 150

dry

ER
. of

HUMIDITY RATIO (or Specific Humidity) GRAINS OF MOISTURE PER POUND OF DRY AIR
P
0.95

EM
er lb
WE 0.50

BT
T

14.2
BU 140

up
LB

UL
T

- Bt
EM 0.90

TB
75 PER

LPY
ATU

WE
75 50
RE 130 0.55

HA
- °F 0.85

ENTHALPY - Btu per lb. of dry air and associated moisture


T
EN
35

VAPOR PRESSURE - INCHES OF MERCURY


Outdoor Air 120 0.80
0.60

14.0

DEW POINT TEMPERATURE - °F


70 0.75
110 70 0.65

%
90
30 0.70
0.70
100 45

13.8
0.65

%
0.75

80
65
65
90 0.80 0.60
25
%
70 0.85
0.55
13.6

60 80 0.90
60
0.95 0.50
%
60 70
1.00
20 40

SENSIBLE HEAT RATIO = Qs / Qt


55 0.45
13.4

55
- Lvg Regen
5 0% 60 0.40
50
Lvg Cooling Coil 50
15 0.35
13.2

50
40 %
Mixed Air Lvg Preheat
45 0.30
45
13.0

Return Air 40
40 35 0.25
Lvg Wheel 30 % 40
35
12.8

30 35 0.20
32
10 30
20% 30
12.6

0.15
20 25
DITY 20 0.10
25 TIVE HUMI
10% RELA
10 10 0.05
0 30
20
0
30 40 50 60 STANDARD AIR 70 80 90 100 110 115
DRY BULB TEMPERATURE - °F
Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

10 15 20 25
ENTHALPY - Btu per lb. of dry air and associated moisture
Questions?

THANK YOU!