Howden Buffalo Inc.

For: Engineer:
Job:

Fan Mark: Date: 07-11-2018

The Fan Definition is Direct Drive Adjustable Pitch

60-26 Series 1000 Full-Bladed, 1.480 Rpm

The Inlet is Pulling from a Plenum. The Inlet Velocity is Zero

A Standard Outlet Connection is Assumed.


The Outlet is Connected to a Round Duct with Diameter of 72 Inches
The Outlet Connection is 34 Inches

The Specified Duty is 105000 CFM, 6,00 in W.G. Static Pressure


The Total Pressure is 7,03 in W.G. at Density = ,080 Lb/Ft3

The Calculated Power is 138,4 HP, The Efficiency is 83,9 %.

The Tip Angle Should be 24,6 Degrees, Which is Index Number 2,3

Additional Blade Setting = Index Number 4,0 Yields 99681 CFM/ Shaft HP = 110,8
Additional Blade Setting = Index Number 6,0 Yields 90571 CFM/ Shaft HP = 81,8

The Performance Curve for the Duty Blade Angle Follows:

Flow Total Pressure Power Eff'y


CFM in W.G. HP Percent
141063 1,85 86,3 47,5
128126 4,12 115,2 72,1
118455 5,72 132,1 80,8
104717 7,06 138,5 84,0
90452 7,82 135,1 82,4

Total Sound Power Levels -dB re 1 picoWatt


63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
104 107 114 119 118 115 112 107

Notes:
1 All performance and sound data is nominal and not guaranteed.
2 Sound levels are based upon the basic fan configuration. Any optional
accessories in the air stream may adversely affect these sound levels.
3 Consult factory for any special performance or noise requirements or testing.
4 Sound presssure levels are based on a point source in a spherical free field.